DIx
PWR
10-30V dc
DIx
GND
dc common
Wiring Diagrams for Discrete Outputs
Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.
Discrete Output Wiring (NPN or NMOS)
DOx
GND
PWR
10-30V dc
Load
dc common
Wiring Diagram for Thermocouple Inputs
Ax+
Ax−
TC
+
−
Thermocouple: When wiring the thermocouple, x is the same number. For ex-
ample, a thermocouple is wired to A1+ and A1-.
Supported Thermocouple Types
The thermocouple Node is configured, by default, to use J-type thermocouples. The following thermocouples are available by configuring
the Node.
Thermocouple
Range °F
Range °C
Type B
212 to 3,272 °F
100 to 1,800 °C
Type C
32 to 4,208 °F
0 to 2,320 °C
Type E
-58 to 1,832 °F
-50 to 1,000 °C
Type J
-292 to 1,382 °F
-180 to 750 °C
Type K
-292 to 2,282 °F
-180 to 1,250 °C
Type L
-328 to 1,652 °F
-200 to 900 °C
Type N
32 to 2,192 °F
0 to 1,200 °C
Type R
32 to 2,912 °F
0 to 1,600 °C
Type S
32 to 2,642 °F
0 to 1,450 °C
Type T
-238 to 752 °F
-150 to 400 °C
Type U
-148 to 1,112 °F
-100 to 600 °C
LED Behavior for the Nodes
After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its
inputs until it is communicating with the Gateway to which it is bound. When testing communication between the Gateway and Node,
SureCross Performance FlexPower Node
P/N 155863_web
Rev. C