The SureCross

®

 Performance Wireless Network

The SureCross

®

 Performance wireless I/O network provides reliable monitoring without the burden of wiring or conduit installation. The

SureCross wireless network can operate independently or in conjunction with a host system, PLC, and/or PC software.
Each wireless network system consists of one Gateway and one or more Nodes. Devices ship with factory defined inputs and outputs
that may be all discrete, all analog, or a mix of discrete and analog I/O.

Gateway

Node

Node

FlexPower Node with
integrated battery

The SureCross

®

 Performance network is a deterministic system—the network identifies when the radio signal is lost and drives relevant

outputs to user-defined conditions. Once the radio signal is reacquired, the network returns to normal operation.

SureCross

®

 Performance Gateways and Nodes

Gateway is the master device within each radio network. Every wireless network must have one Gateway that schedules communica-
tion traffic and controls the I/O configuration for the network. A radio network contains only one Gateway, but can contain many Nodes.
Similar to how a gateway device on a wired network acts as a “portal” between networks, the SureCross Gateway acts as the portal
between the wireless network and the host controller. When the Gateway, using its Modbus RTU RS-485 connection, is a Modbus slave
to a Modbus RTU host controller, the wireless network may contain up to 47 Nodes in a single wireless network and the Gateway holds
the Modbus registers of all wireless devices within the network.
Node is a wireless network end-point device used to provide sensing capability in a remote area or factory. The Node collects data
from sensors and communicates the data back to the Gateway. Nodes are available in a wide variety of power or input/output options.
Each Node device can be connected to sensors or output devices and reports I/O status to the Gateway.

SureCross User Configuration Tool

The User Configuration Tool (UCT) offers an easy way to link I/O points in your
wireless network, view I/O register values graphically, and set system communi-
cation parameters when a host system is not part of the wireless network.
The UCT requires a special USB to RS-485 (model number BWA-UCT-900 for 1
Watt radios, BWA-HW-006 can be used for all other radios) converter cable to
pass information between your computer and the Gateway. Download the most
recent revisions of the UCT software from Banner Engineering's website: 

http://

www.bannerengineering.com/wireless

.

Setting Up Your Wireless Network

To set up and install your wireless network, follow these steps:

1. Configure the DIP switches of all devices.
2. Connect the sensors to the SureCross devices.

 

 

SureCross Performance FlexPower Node

2

www.bannerengineering.com - tel: 763-544-3164

P/N 155863_web

Rev. C

Содержание SureCross Performance DX80N9X2S-P3 FlexPower

Страница 1: ...te list of accessories refer to Banner Engineering s website www bannerengineering com surecross Models Frequency Power Housing I O DX80N9X2S P3 900 MHz ISM Band 10 to 30V dc or battery supply mod ule...

Страница 2: ...its Modbus RTU RS 485 connection is a Modbus slave to a Modbus RTU host controller the wireless network may contain up to 47 Nodes in a single wireless network and the Gateway holds the Modbus regist...

Страница 3: ...To access the internal DIP switches follow these steps 1 Unscrew the four screws that mount the cover to the bottom housing 2 Remove the cover from the housing without damaging the ribbon cable or the...

Страница 4: ...600 degrees Fahrenheit or 1600 degrees Celsius switch the DIP switch to the ON position and use low resolution mode In high resolution the device cannot store values larger than 1600 Temperature Units...

Страница 5: ...OUT x GND Ground dc common connection PWR Power 10 to 30V dc power connection DX80 C Wiring Wiring power to the DX80 C models varies depending the power requirements of the model Terminal Label Gatewa...

Страница 6: ...optional 2 RS 485 D1 B RS 232 Tx 3 dc common GND dc common GND 4 RS 485 D0 A RS 232 Rx The BAT connection is a low voltage connection to the internal battery Remove the internal battery if a low volta...

Страница 7: ...ocouples are available by configuring the Node Thermocouple Range F Range C Type B 212 to 3 272 F 100 to 1 800 C Type C 32 to 4 208 F 0 to 2 320 C Type E 58 to 1 832 F 50 to 1 000 C Type J 292 to 1 38...

Страница 8: ...an integrated battery ship from the factory in storage mode to conserve the battery To wake the device press and hold button 1 for five seconds To put any FlexPower or integra ted battery SureCross r...

Страница 9: ...isk of explosion if the battery is re placed incorrectly 4 After replacing the battery allow up to 60 seconds for the device to power up Properly dispose of your used battery according to local regula...

Страница 10: ...FF Condition PNP Less than 5V NPN Greater than 2V or open Thermocouple Inputs Sample Rate 8 seconds Report Rate 32 seconds Accuracy 0 1 of full scale reading 0 8 C Resolution 0 1 C 24 bit A D converte...

Страница 11: ...the most recent version of any documentation refer to our website www bannerengineering com 2006 2010 Banner Engineering Corp All rights reserved Banner Engineering Corp Limited Warranty Banner Engine...

Отзывы: