Thermistor Inputs

Counter Inputs

AX2

GND

AX1

GND

Counter

Set the MultiHop Radio (Slave) ID

On a MultiHop radio, use the rotary dials to set the device’s MultiHop Radio ID.

Modbus Slave IDs 01 through 10 are reserved for slaves directly connected to the host (local

I/O). Polling messages addressed to these devices are not relayed over the wireless link. Use

Modbus Slave IDs 11 through 60 for MultiHop master, repeater, and slave radios. Up to 50

devices (local slaves and remote slaves) may be used in this system.

With the left dial acting as the left digit and the right dial acting as the right digit, the

MultiHop Radio ID can be set from 01 through 60.

Modbus Register Maps

Register

(4xxxx)

Input

#

Input Type

Units

I/O Range

Holding Register

Representation

Terminal

Block Labels

Min. Value Max.

Value

Min.

(Dec.)

Max.

(Dec.)

1

1

Discrete IN 1

-

0

1

0

1

DI1

2

2

Discrete IN 2

-

0

1

0

1

DI2

3

3

Discrete IN 3

-

0

1

0

1

DI3

4

4

Discrete IN 4

-

0

1

0

1

DI4

5

5

Analog IN 1

mA

0.0

20.0

0

65535

AI1

6

6

7

7

Analog IN 3

mA

0.0

20.0

0

65535

AI3

8

8

Thermistor

°F

-1638.3

+1638.4

-32768

32767

AX2

9

9

Counter IN 1

MSW 1

0

65535

0

65535

AX1

10

LSW 2

0

65535

0

65535

Register

(4xxxx)

Output

#

Output Type

Units

I/O Range

Holding Register

Representation

Terminal

Block Labels

Min. Value Max.

Value

Min.

(Dec.)

Max.

(Dec.)

501

1

Discrete OUT 1

-

0

1

0

1

DO1

502

2

Discrete OUT 2

-

0

1

0

1

DO2

503

3

504

4

1 Most Significant Word

2 Least Significant Word

SureCross MultiHop Data Radio

 

 

P/N 148947 Rev. C

www.bannerengineering.com - tel: 763-544-3164

7

Содержание SureCross DX80DR2M-H1

Страница 1: ...y module IP67 NEMA 6 Inputs Four sinking discrete two 0 to 20 mA analog one thermistor one sinking counter Outputs Two NMOS discrete two switch power Serial interface RS 485 DX80DR9M H1E 10 to 30 V dc...

Страница 2: ...op Master Radio Within a network of MultiHop data radios there is only one master radio The master radio controls the overall timing of the network and is always the parent device for other MultiHop r...

Страница 3: ...duct Manual 151317 MultiHop Register Guide End User Edition 155289 Configure the DIP Switches Before making any changes to the DIP switch positions disconnect the power DIP switch changes will not be...

Страница 4: ...ible to enable broadcast acknowledgement of the data packets to provide better throughput In transparent mode there is no access to the radio s I O Baud Rate and Parity The baud rate bits per second i...

Страница 5: ...dc 10 to 30 V dc Tx RS 485 D1 B RS 485 D1 B V dc common GND dc common GND Rx RS 485 D0 A RS 485 D0 A B 3 6 to 5 5 V dc Wiring for DX80 E Radios Connecting dc power to the communication pins will cause...

Страница 6: ...connection PWR Power 10 to 30 V dc power connection SPx Switch Power Provides variable power sources for external devices Discrete Input Wiring for PNP Sensors Discrete Input Wiring for NPN Sensors D...

Страница 7: ...60 Modbus Register Maps Register 4xxxx Input Input Type Units I O Range Holding Register Representation Terminal Block Labels Min Value Max Value Min Dec Max Dec 1 1 Discrete IN 1 0 1 0 1 DI1 2 2 Dis...

Страница 8: ...ut 2 output 1 etc Operation type specific parameters discrete counter analog 4 to 20 mA are grouped together based on the I O type number analog 1 analog 2 counter 1 etc Not all inputs or outputs may...

Страница 9: ...Remove the four screws mounting the face plate to the housing and remove the face plate Do not remove the radio cover from the face plate 2 Remove the discharged battery and replace with a new battery...

Страница 10: ...on covers Weight 0 26 kg 0 57 lbs M Hx and M HxC models Mounting 10 or M5 SS M5 hardware included M HxE models Mounting 1 4 inch or M7 SS M7 hardware included Max Tightening Torque 0 56 N m 5 lbf in I...

Страница 11: ...BWA 9O2 C 900 MHz or BWA 2O2 C 2 4 GHz Antenna 2 dBd Omni Rubber Swivel RP SMA Male Not included with Internal antenna models Quick Start Guide 128185 for DX80 Gateways or 152653 for MultiHop models...

Страница 12: ...ted Warranty Banner Engineering Corp warrants its products to be free from defects in material and workmanship for one year following the date of shipment Banner Engineering Corp will repair or replac...

Отзывы: