5.8.3 Node Link Failure

A Node Link Failure is determined by the polling interval/rate or the out-of-sync timing.

When a Node detects a communications failure with the Gateway and the Node Link Failure flag is set, the output points

are set to the user-defined states and the inputs are frozen. When output points are set to their default states because of

an error condition, only the Gateway can clear the error condition and resume normal operation. The front panel buttons

or the Gateway’s register I/O 15 clear error conditions.

Clearing a lost radio link error does not restore communications. Banner recommends determining and resolving the cause

of the radio link error, then allowing the system to auto-recover the lost communications.

Polling Interval. The global polling interval defines the time interval during which the Node should expect a polling

request from the Gateway.

Out of Sync. An out of sync condition is met when a Node fails to receive the Gateway’s beacon within a factory-set time

period, about 10 seconds. Both the out of sync and polling interval conditions are used to detect a failure because the

Node can remain in sync with the Gateway but be unable to transmit data. If the Gateway drops out of the network, the

Nodes detects the out of sync condition long before the polling interval expires.

5.9 Units Defined

The units parameter defines the range and/or type of data value associated with an input or output.

Selecting Units from within any configuration tool changes the units definition of several parameters, including threshold,

hysteresis, and delta. For example, if the units are 0 to 20 mA, the threshold, hysteresis, and delta values are entered as

milliampere values. Selecting Temp °C changes the threshold, hysteresis, and delta units to degrees Celsius.

Signed values range from 

32768 to +32767 and allow for the measurement of negative values. Signed values are

typically used for measuring temperatures. Signed values are stored as two's complement values.

Unsigned values range from 0 to 65535 and are used to measure values that do not go below zero, such as 4 to 20 mA,

distance, or a counter.

5.9.1 Input Units

Units

Description

Definition

0

Raw

Displays the raw A/D conversion data with data ranges from 0 to 65535. This units type is typically used only for

factory calibration.

LCD: Raw A/D hex value

1

4 to 20 mA

Analog unit. Modbus register contents are scaled such that 0 represents 4 mA and 65535 represents 20 mA.

LCD: 4.00mA–20.00mA

2

0 to 20 mA

Default analog input unit. Modbus register contents are scaled such that 0 represents 0 mA and 65535 represents 20

mA.

LCD: 0.00mA–20.00mA

3

Discrete (ON/OFF) Default discrete input unit.

LCD: ON/OFF

4

0 to 10 V (Volts)

Analog input using 0 to 10 V instead of current. Modbus register contents are scaled such that 0 represents 0V and

65535 represents 10V.

LCD: 0.00V–10.00V

6

Temp °C

Celsius, high resolution. Analog input for temperature devices such as thermocouples, RTD, and thermistors. In high

resolution mode, temperature = (Modbus register value) ÷ 20.

LCD: 0000.0C

7

Temp °F

Fahrenheit, high resolution. Analog input for temperature devices such as thermocouples, RTD, and thermistors. In high

resolution mode, temperature = (Modbus register value) ÷ 20.

LCD: 0000.0F

8

Temp °C (Low

Res)

Celsuis, low resolution. To measure a greater temperature range, use the low resolution unit. In low resolution mode,

temperature = (Modbus register value) ÷ 2.

LCD: 0000.0C

9

Temp °F (Low

Res)

Fahrenheit, low resolution. To measure a greater temperature range, use the low resolution unit. In low resolution

mode, temperature = (Modbus register value) ÷ 2.

LCD: 0000.0F

10

Asynchronous

Counter, 32-bit

The 32-bit counter value records counts up to 4.29 billion.

LCD: 0000 0000

 

 

Sure Cross

®

 Performance DX80 Wireless I/O Networks

 

www.bannerengineering.com - Tel: 763.544.3164

45

Содержание Sure Cross Performance GatewayPro DX80P*A6...

Страница 1: ...Sure Cross Performance DX80 Wireless I O Networks Instruction Manual Original Instructions 132607 Rev K 7 December 2016 Banner Engineering Corp All rights reserved 132607...

Страница 2: ...ults 18 3 7 3 Site Survey Troubleshooting 19 3 7 4 Conduct a Site Survey Using Modbus Commands 19 4 Installing Your Sure Cross Radios 21 4 1 Mounting SureCross Devices Outdoors 21 4 1 1 Watertight Gla...

Страница 3: ...Radios with DX85 Modbus RTU Remote I O Devices 58 6 4 3 Data Radios with a Gateway as the Modbus Master 59 7 Sensor Connections 60 7 1 Discrete Inputs 60 7 1 1 Discrete Inputs Sourcing 60 7 1 2 Discr...

Страница 4: ...1 2 7 Antenna Cables RP SMA to N Type 85 11 2 8 Antenna Cables N Type 86 11 2 9 Surge Suppressors 86 11 3 Power Supplies 86 11 3 1 DC Power Supplies 86 11 3 2 FlexPower Supplies and Replacement Batter...

Страница 5: ...Gateway Nodes are available in a wide variety of power or input output options 1 2 Sure Cross Performance GatewayPro The Sure Cross Performance GatewayPro combines the function of a Sure Cross Perfor...

Страница 6: ...to the Modbus network Host controlled DX80 wireless systems are configured using an Ethernet network connection and a Web page browser An Ethernet connection can be established from a DX80 GatewayPro...

Страница 7: ...software runs on any computer with the Windows Vista Windows 7 Windows 8 or Windows 10 operating system Use a USB to RS 485 adapter cable to connect a standalone DX80 Gateway to the computer For DXM C...

Страница 8: ...ake integrated battery models from the hibernation mode they ship in 4 Push button 2 Double click to select a menu and to enter manual scrolling mode Double click to move up one level at a time 5 LED...

Страница 9: ...Double click to select a menu and to enter manual scrolling mode Double click to move up one level at a time 5 LED 1 and 2 Provide real time feedback to the user regarding RF link status serial commun...

Страница 10: ...d by 3 6 to 5 5 V dc Refer to Specifications to verify the power requirements of your device For FlexPower devices do not apply more than 5 5 V to the gray wire 5 pin M12 Euro style male Pin Wire Colo...

Страница 11: ...hole dimensions 2 6 1 Gateways and Nodes 65 0 2 56 65 0 2 56 80 3 3 16 80 8 3 18 60 2 36 120 4 72 127 5 19 0 75 30 65 1 21 22 2 0 875 7 9 0 31 7 65 0 30 14 67 0 578 DX80 C Gateways and Nodes 7 9 0 31...

Страница 12: ...9 mm 2 20 2X Dia 8 3 mm 0 33 2 6 2 GatewayPro 65 0 2 56 65 0 2 56 80 3 3 16 80 8 3 18 136 5 35 7 9 0 31 7 65 0 30 60 2 36 14 67 0 578 2 6 3 DX83 Ethernet Bridge 65 0 2 56 7 9 0 31 80 3 3 16 65 0 2 56...

Страница 13: ...0 13 167 4 mm 6 59 75 3 mm 2 96 2X 12 14 NPSM 20 1 mm 0 79 87 6 mm 3 45 13 7 mm 0 54 36 2 mm 1 42 148 1 mm 5 83 55 9 mm 2 20 2X Dia 8 3 mm 0 33 Sure Cross Performance DX80 Wireless I O Networks www ba...

Страница 14: ...ressing mode allows you to use up to 47 Nodes with a single Gateway Without extended addressing only 15 Nodes can communicate with a single Gateway The extended address code in the Gateway defaults to...

Страница 15: ...apply power to a FlexPower Node with an integrated battery install the battery into the housing The Node starts in RUN mode displays the current network ID then identifies itself as a Node and lists...

Страница 16: ...en the left dial is at 3 Positions A through F are invalid network ID numbers When installing special kits with pre mapped I O indicated by device model numbers beginning in DX80K return the rotary di...

Страница 17: ...across the menu levels until reaching the Site Survey SITE menu 4 Single click button 2 to enter the Site Survey menu 5 Single click button 2 to begin conducting a Site Survey with the Node selected i...

Страница 18: ...ckets received at a strong signal strength A strong signal strength is greater than 90 dBm at the receiver Yellow Packets received at a good signal strength A good signal is between 90 and 100 dBm at...

Страница 19: ...er position Use a higher gain antenna Decrease the distance between devices or Use data radios to extend the position of the Gateway relative to the host system 3 7 4 Conduct a Site Survey Using Modbu...

Страница 20: ...mber 0 0x0 3 7 4 Site Survey Data Holding With Site Survey active registers I O 7 and 8 are Site Survey data holding registers that store the accumulated Site Survey results Error collections in holdi...

Страница 21: ...1 1 Watertight Glands and NPT Ports To make glands and plugs watertight use PTFE tape and follow these steps 1 Wrap four to eight passes of polytetrafluoroethylene PTFE tape around the threads as clo...

Страница 22: ...onal regulations 4 2 When Installing Performance or MultiHop 1 Watt Radios Notice This equipment must be professionally installed The output power must be limited through the use of firmware or a hard...

Страница 23: ...f the year Figure 2 During spring and summer leaves may block more of the radio signal 4 4 Basic Remote Antenna Installation A remote antenna system is any antenna system where the antenna is not conn...

Страница 24: ...he rubber splicing tape one inch away from the connection and continue wrapping until you are one inch past the other end of the connection Each new round of tape should overlap about half the previou...

Страница 25: ...connected to the antenna Use this extension cable to connect the antenna directly to the radio To mount drill a hole in the enclosure and insert the antenna Models Description List Price BWA 9O2 D Ant...

Страница 26: ...9Y6 A 900 MHz 6 5 dBd 6 8 13 inches Outdoor 135 BWA 9Y10 A 10 dBd 6 8 24 inches Outdoor 150 Models Frequency Description List Price BWA 9O6 A 900 MHz 6 dBd Fiberglass Full wave 71 5 inches 355 BWA 2O...

Страница 27: ...1 BWC LFNBMN DC Surge Suppressor bulkhead N Type dc Blocking N Type Female N Type Male 120 Use the RP SMA to N Type male cables to connect the radio to the surge suppressor Model Description List Pric...

Страница 28: ...2 adjust right rotary switch to survey the selected Node Single click Button 2 Double click Button 2 Double click Button 2 NOD XX EC XX CLEAR ERR ERASED ERR DISABL ERROR DISABL IGNORE Next Device Sing...

Страница 29: ...etwork ID DINFO RUN FCTRY DVCFG DERR AUTO DISPLAY LOOP AUTO DISPLAY LOOP AUTO DISPLAY LOOP DEV NOD XX NAME NODE XX KIT XXXXX NID XX DEV NOD XX RADIO MICRO V 00 0 A DX80 S N 0x0000 2 LCD MICRO 0x0000 2...

Страница 30: ...Single click Button 1 0 00 Gateway Node On the Gateway the I O displayed may be the I O of the Gateway or of a selected Node To view the I O of a specific Node set the position of the rotary dials to...

Страница 31: ...ice name the network ID NID slave ID baud rate and parity When in extended address mode the DINFO menu also displays the maximum Node setting and the extended addressing XADR or binding code used to f...

Страница 32: ...CRO V 00 0 A DX80 S N 0000 DX80 MODEL 0000 00 PROD DATE 00 00 Single click Button 1 Factory Info FCTRY AUTO DISPLAY LOOP DEV NOD XX RADIO MICRO V 00 0 A DX80 S N 0x0000 2 LCD MICRO 0x0000 2 PROD DATE...

Страница 33: ...ITE menu displays the device number of the Node the Site Survey was conducted with as well as the missed green yellow and red received packet count The SITE menu is only available on the Gateways To a...

Страница 34: ...or baud rate are 19200 38400 or 9600 For parity select None Even or Odd Extended Address Binding Code Binding Nodes to a Gateway ensures the Nodes only exchange data with the Gateway they are bound to...

Страница 35: ...ton 2 PRIOR NADR XX NEW NADR XX CONFRM NADR XX Single click Button 1 to advance through menu Node 5 1 6 DERR Device Error Menu Use the DERR menu to manage device error messages DERR Single click Butto...

Страница 36: ...page browser An Ethernet connection can be established from a GatewayPro or from a DX83 Ethernet Bridge serially connected to the Gateway The Ethernet Bridge and GatewayPro each ship with an Ethernet...

Страница 37: ...sed Configuration Screens The configuration Web pages are served from the DX83 Ethernet Bridge or GatewayPro and are accessed using any Internet browser Before accessing the Web based configuration sc...

Страница 38: ...page tabs at the top of the page to select the hierarchical path System Setup Network To change the IP address type in the new IP address and click the Change IP button The IP address change activate...

Страница 39: ...of 15 Nodes can be used in the wireless network A maximum of 47 Nodes 48 total devices can be used in the wireless network 5 4 1 Manually Choosing an Extended Address Code Gateway Manually choosing t...

Страница 40: ...de 9 Single click button 2 to enter the extended address code entry step The LCD shows SET XADR 000000 10 Use the right rotary switch to begin setting the extended address code Digit selection begins...

Страница 41: ...stopping at XADR The Gateway s LCD displays XADR 6 Single click button 2 to enter XADR mode When the display reads AUTO single click button 2 again to begin the automatic binding mode The LEDs flash...

Страница 42: ...ay first need to configure system level communication parameters on the Gateway The following procedures are necessary to change the Gateway s slave ID baud rate and parity Setting up the Network and...

Страница 43: ...the available options Stop on the desired setting The options are NONE EVEN ODD The factory default is NONE 3 Single click Gateway push button 2 to save the new setting 4 If using a network ID NID adj...

Страница 44: ...the Gateway and Node have successfully exchanged N number of good polling messages The N number is the re link count or the number of messages required to re establish a radio link When the Node s Ga...

Страница 45: ...values range from 32768 to 32767 and allow for the measurement of negative values Signed values are typically used for measuring temperatures Signed values are stored as two s complement values Unsign...

Страница 46: ...e Celsius conversions only Use null to set the start point and span to define the range The null value is the starting temperature to be associated with 4 mA The span is the entire temperature range t...

Страница 47: ...ndicates a functioning sensor whereas a value below 4 mA indicates an error condition such as a broken wire or loose connection Some Sure Cross devices allow you to configure the analog inputs and out...

Страница 48: ...e Null 5 20 15 Offset 4 Output 0 22857 15 4 7 42 mA Example Distance Map Map a distance input from a Node to a 0 to 10 V output The starting distance is 200 mm and the last distance will be 2000 mm 4...

Страница 49: ...ddress for all devices re install the rotary dial access covers referring to the Installation section for IP67 instructions A successful radio link is identified by a blinking green LED 1 on each Node...

Страница 50: ...nnel Search Mode runs LED 1 is solid red and LED 2 ashes yellow The device tests Network ID 2 for availability and counts down from one minute zero seconds The selected Network ID is available for use...

Страница 51: ...thernet Bridge DX80 Gateway 900 MHz DX80DR9M H MultiHop Radio 6 1 Stand Alone Systems 6 1 1 Mapped Pairs DX70 In this system a DX70 pair is used to map I O in a simple one to one configuration Inputs...

Страница 52: ...map inputs and outputs between Nodes and Gateways 1 2 2 2 Item Model No Description 1 DX80G DX80 or DX80 Performance Gateway 2 DX80N DX80 or DX80 Performance Node 81398 User Configuration Tool free t...

Страница 53: ...I O points to the network through hard wired fieldbus connections on the Gateway side Fieldbus Connection Modbus Slave 2 Modbus Slave 3 2 2 1 Gateway as Modbus Master Slave ID 1 3 Wireless Network It...

Страница 54: ...a Modbus slave In this configuration the wireless network collects I O data and sends it back to a Modbus host system 1 Wireless Network Host System Modbus Master 2 Modbus Slave Item Model No Descript...

Страница 55: ...85 connected as shown below are Modbus slave devices to the host system Purpose This wireless network also collects I O data and sends it back to a Modbus host system but adds local wired I O points F...

Страница 56: ...ices to the host system Purpose This wireless network collects I O data and sends it back to a Modbus host system but adds local wired I O points and expands the network using a fieldbus connection Fi...

Страница 57: ...figuration Web pages 1 Wireless Network Host System 2 3 1 Wireless Network 3 1 Host System 5 4 3 Wireless Network Item Model No Description 1 DX80P 6S DX80 or DX80 Performance GatewayPro Protocol conv...

Страница 58: ...Modbus master device 4 Modbus slave device 6 4 2 Data Radios with DX85 Modbus RTU Remote I O Devices In this example network DX85 Extended Remote I O devices are wired to the data radios and act as Mo...

Страница 59: ...the Modbus network 5 3 5 3 2 1 4 Item Model No Description 1 DX80G DX80 or DX80 Performance Gateway configured as a Modbus master for this example 2 DX85M DX85 Modbus RTU Remote I O configured as a M...

Страница 60: ...r sources do not have to be the same 7 1 1 Discrete Inputs Sourcing Two Wire Sensors Three Wire Sensors Discrete IN PWR 10 30V dc Discrete IN GND dc common PWR 10 30V dc Wiring diagram for a sourcing...

Страница 61: ...as the SureCross device power source 7 3 Analog Inputs Analog Sensors For analog sensors the ground dc common of the sensor should be connected to the ground of the DX80 device For best results Banner...

Страница 62: ...ratings for analog inputs Only connect sensor outputs to analog inputs Two Wire Sensors Three Wire Sensors Analog IN GND dc common external power sensor Analog IN GND external power dc common sensor T...

Страница 63: ...dc sensor AOx GND dc common external power sensor Three wire analog output device powered by the SureCross device Three wire analog output device powered externally not from the SureCross device 7 4 2...

Страница 64: ...supply module DX81P6 a 6 pack of lithium batteries DX81H a single battery supply module designed specifically to power the DX99 Intrinsically Safe devices with polycarbonate housings and BWA SOLAR 00...

Страница 65: ...n used with a FlexPower Node and sensors the FlexPower Solar Assembly supplies enough power to run most sensors at higher sample and report rates than a single battery can reasonably support The solar...

Страница 66: ...a warm up time of 500 milliseconds and a sample and report rate of 15 minutes should have a battery life of 4 45 years All battery life calculations are approximations based on a strong radio signal W...

Страница 67: ...case as far as battery use because we are assuming for each sample of the sensor s output a change in state has occurred e g target present to target absent or vice versa sending a radio message from...

Страница 68: ...ed in our list use the configuration and cable shown Banner cable BWA HW 010 to measure the current draw of your system 1 Connect the cable to the FlexPower Node and the battery supply module as shown...

Страница 69: ...e solar powered assembly to power data radios FlexPower Gateways or FlexPower Nodes connected to sensors that require more power than a single battery unit can supply 1 2 5 Powering a data radio or da...

Страница 70: ...es 8 DX80G M2S P Performance FlexPower Gateway Serial RS 485 Interface No I O 8 4 Battery Backup Feature The FlexPower Solar Supply can be ORed with the DX81P6 Battery Supply Module using the CSRB M12...

Страница 71: ...or Operation A single FlexPower Solar Assembly can supply any continuously powered 4 to 20 mA two wire transmitter at 13 V and power the DX80 FlexPower Node for continuous sensor operation This applic...

Страница 72: ...2 DX80N DX80 or DX80 Performance FlexPower Node or 10 to 30 V dc Node 3 DX80G M2S P Performance FlexPower Gateway No I O 4 DX80DR M H MultiHop Data Radio 900 MHz or 2 4 GHz 5 CSRB M1250M125 47M125 73...

Страница 73: ...Replacement 9 3 1 Replacing the Battery When the FlexPower Supply Module is installed outdoors or in a high humidity environment apply dielectric grease to the battery terminals to prevent moisture a...

Страница 74: ...in the case The negative end is toward the spring Caution There is a risk of explosion if the battery is replaced incorrectly 5 After replacing the battery allow up to 60 seconds for the device to pow...

Страница 75: ...l number BWA BATT 001 For pricing and availability contact Banner Engineering WARNING Do not replace battery when an explosive dust atmosphere may be present The replacement battery MUST be a Banner a...

Страница 76: ...bon cable has been unplugged from the radio board verify the ribbon cable is fully seated and that it has been plugged into all pins It is possible to accidentally plug in the ribbon cable and miss th...

Страница 77: ...sult the factory for options 3 Use a qualified antenna on both the Gateway and Node devices 4 After any system parameter change cycle the power to re synchronize all devices 5 When a Node loses synchr...

Страница 78: ...p 10 3 1 Modbus Message Codes for Register 8 Register I O 8 is reserved for device messages or Site Survey data when in Site Survey mode Conditions are detected as they occur and are reported to the G...

Страница 79: ...wireless devices employ a deterministic link time out method to address radio link interruption or failure When a specific Node Gateway radio link fails all pertinent wired outputs are de energized u...

Страница 80: ...rmal OUT 1 Normal OUT 2 Normal OUT 1 Normal OUT 2 Normal OUT 3 Normal OUT 4 Normal Figure 6 Radio link between the Gateway and Node 1 has recovered Sure Cross Performance DX80 Wireless I O Networks 80...

Страница 81: ...With Opaque Covers Models Description List Price BWA AH664 Enclosure Polycarbonate with Opaque Cover 6 6 4 93 BWA AH864 Enclosure Polycarbonate with Opaque Cover 8 6 4 98 BWA AH1084 Enclosure Polycar...

Страница 82: ...iption List Price BWA AH6DR DIN Rail Kit 6 Includes 2 Trilobular Self Threading Screws and DIN Rail 12 BWA AH8DR DIN Rail Kit 8 Includes 2 Trilobular Self Threading Screws and DIN Rail 14 BWA AH10DR D...

Страница 83: ...needs There are three basic antenna solutions Use the supplied rubber duck antenna inside the enclosure DX80 products come with a 2 dBi rubber duck antenna Often simply attaching the supplied antenna...

Страница 84: ...12 ft cable RP SMA Male 80 11 2 4 Antennas Fiberglass N Type The following fiberglass antennas are typically used outdoors Omni Directional Fiberglass Antennas with N Type Female Connections Models Fr...

Страница 85: ...31 BWC 1MRSFRSB2 RG58 RP SMA Male to RP SMA Female Bulkhead 2 m 33 BWC 1MRSFRSB4 RG58 RP SMA Male to RP SMA Female Bulkhead 4 m 36 Models Description List Price BWC 2MRSFRS3 LMR200 RP SMA Male to RP S...

Страница 86: ...adio Remote antenna configurations installed without a surge suppressor invalidate the manufacturer s warranty Model Description Connection List Price BWC LMRSFRPB Surge Suppressor Bulkhead RP SMA Typ...

Страница 87: ...PANEL 3W Solar Panel 12 V 3 W Multicrystalline 188 195 15 Wall Pole clamp style mounting bracket included 60 BWA SOLAR PANEL 5W Solar Panel 12 V 5 W Multicrystalline 270 222 17 Wall Pole clamp style...

Страница 88: ...ly replacement part 13 11 5 Brackets and Mounting Options BWA HW 001 Mounting Hardware Kit List Price Screw M5 0 8 x 25 mm SS 4 Screw M5 0 8 x 16 mm SS 4 Hex nut M5 0 8 mm SS 4 Bolt 8 32 x 3 4 SS 4 4...

Страница 89: ...r spacing A 26 0 A to B 13 0 Hole size A 26 8 7 0 B 6 5 C 19 0 12 BWA BK 001 Includes magnetic mounting bracket SMB42FLM12 and 2 mounting screws 42 42 50 BWA BK 002 Includes SMB42FL stainless steel br...

Страница 90: ...2 meter integral cable 11 6 2 DX85 Modbus RTU Remote I O Devices These remote I O devices have a Modbus interface and are used to expand the I O of the Gateway or the Modbus host DX85 IP67 Housing Mod...

Страница 91: ...or RS 485 Modbus interface 125 K50UX2RA U GAGE K50U Ultrasonic RS 485 Modbus interface 195214 Other Sensors Models Description List Price BWA THERMISTOR 001 NTC Thermistor 2 2 KOhms 0 2 C blue bead Fo...

Страница 92: ...c Receiver QS30 Max Range 100 feet 10x excess gain at 50 feet 1 wire serial interface 91 QM42VT1 Vibration and Temperature Sensor with 1 wire serial interface 186209 195 K50UX1RA U GAGE Ultrasonic Sen...

Страница 93: ...0F with Push Button Contact integral 8 pin M12 Euro style QD 137302 11 6 5 Cables Ethernet Cables Use a crossover cable to connect the GatewayPro or DX83 Ethernet Bridge to a host system without using...

Страница 94: ...k 0 m male Branches 0 14 m and 0 22 m female Straight Male 1 4 5 3 2 Female 2 3 4 1 5 1 Brown 2 White 3 Blue 4 Black 5 Gray CSRB M1253 28M1253 28M1253 28 Trunk 1 m female Branches 1 m male 44 Typ 2X M...

Страница 95: ...Threaded M12 Euro Style Cordsets Single Ended Model Length Style Dimensions Pinout Female MQDC1 501 5 0 50 m 1 5 ft Straight 44 Typ 14 5 M12 x 1 2 3 4 1 5 1 Brown 2 White 3 Blue 4 Black 5 Gray MQDC1 5...

Страница 96: ...s Hardware Kit Plastic threaded plugs PG 7 4 Nylon gland fittings PG 7 4 Hex nuts PG 7 4 Plug 1 2 inch NPT Nylon gland fitting 1 2 inch NPT 25 BWA HW 003 PTFE Tape 1 4 inches wide 600 inches long 4 BW...

Страница 97: ...ing Accessories Model No Description List Price BWA HW 016 Antenna Feedthrough Stainless Steel 1 2 NPT 62 BWA HW 017 Antenna Feedthrough Stainless Steel 3 4 NPT 66 BWA HW 012 DX99 Antenna Extension Pa...

Страница 98: ...the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful...

Страница 99: ...n a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try...

Страница 100: ...erence to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures R...

Страница 101: ...x Germany x Greece x Guatemala x x Hungary x Iceland x India x Ireland x Israel x Italy x Korea Republic of South x Latvia x Liechtenstein x Lithuania x Luxembourg x Malta x Mexico x x x Netherlands...

Страница 102: ...tements 900 MHz This device has been designed to operate with the antennas listed on Banner Engineering s website and having a maximum gain of 9 dBm Antennas not included in this list or having a gain...

Страница 103: ...or at the discretion of Banner Engineering Corp replacement IN NO EVENT SHALL BANNER ENGINEERING CORP BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS EXPENSES LOSSES LOSS OF PROF...

Страница 104: ...Engineering Shanghai Rep Office Xinlian Scientific Research Building Level 12 Building 2 1535 Hongmei Road Shanghai 200233 China Phone 86 212 422 6888 Website www bannerengineering com cn Email senso...

Страница 105: ...3 26 link time out 79 M mechanical stress 22 Modbus communication parameters 42 43 Modbus time out error code 78 N network ID 40 no LCD 78 null 46 48 O offset 46 48 outdoor installations 21 overvoltag...

Отзывы: