background image

5-Pin M12/Euro-style Male Quick Disconnect

Integral 5-pin M12/Euro-style male quick disconnect (QD) wiring depends on the model and power requirements of the

device. Not all models can be powered by 10 to 30 V dc and not all models can be powered by 3.6 to 5.5 V dc. Refer to

Specifications to verify the power requirements of your device. For FlexPower devices, do not apply more than 5.5 V to the

gray wire.

5-pin M12/Euro-style (male)

Pin

Wire Color

Powered by 10 to 30 V dc

Powered by Battery or Battery Pack

1

4

5

3

2

1

Brown

10 to 30 V dc

2

White

3

Blue

dc common (GND)

dc common (GND)

4

Black

5

Gray

3.6 to 5.5 V dc

Terminal Blocks

Refer to the Class I Division 2/Zone 2 control drawings (p/n 

143086

) for wiring specifications or limitations.

IP67 Housing (P2 Models)

IP20 Housing (P2C Models)

G B − W +

A1

A2

GND

PWR

PWR

GND

AO2

AO1

DO4

DO3

DO2

DO1 DI1

DI2

DI3

DI4

AI1

AI2

G

B

W

+

DO4

TX/+
RX/

DO3

V+

AO2

AO1

DO2

DO1

DI2

DI1

AI2

AI1

V

V+

V

DI3
DI4

A1

A2

AIx or Ax. Analog IN x
AOx. Analog OUT x
DIx. Discrete IN x
DOx. Discrete OUT x
GND. Ground/dc common connection
PWR. 10 to 30 V dc power connection

RX/-. Serial communication line for the Gateway. No

connection for Nodes
TX/+. Serial communication line for the Gateway; no

connection for Nodes
V+. 10 to 30 V dc power connection
V–. Ground/dc common connection

DX80...C Wiring

Wiring power to the DX80...C models varies depending the power requirements of the model. Connecting dc power to the

communication pins (Tx/Rx) causes permanent damage. For FlexPower devices, do not apply more than 5.5 V to the B+

terminal.

Terminal Label

Gateway and DX85

10 to 30 V dc Powered Nodes

Battery Powered Nodes

V+

10 to 30 V dc

10 to 30 V dc

Tx/+

RS485 / D1 / B / +

V–

dc common (GND)

dc common (GND)

dc common (GND)

Rx/–

RS485 / D0 / A / -

B+

3.6 to 5.5 V dc

Wiring Diagrams for Discrete Inputs

Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the

wiring diagram refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board. To power

the sensor using the switch power output (SPx), replace the PWR with SPx in these wiring diagrams.

Sure Cross

®

 Performance Node

 

 

P/N 155862 Rev. G

www.bannerengineering.com - Tel: +1-763-544-3164

5

Содержание Sure Cross DX80N9X6S-P2

Страница 1: ...P2 900 MHz ISM Band IP67 NEMA 6 Inputs Four selectable discrete two 0 to 20 mA default or 0 to 10 V user configurable Outputs Four sourcing discrete two 0 to 20 mA DX80N2X6S P2 2 4 GHz ISM Band DX80 C...

Страница 2: ...nstructions are not included in the datasheet refer to the product manual for binding instructions 5 Observe the LED behavior to verify the devices are communicating with each other For two LED models...

Страница 3: ...A input allows you to determine when you have an error condition with the sensor A normal input reading between 4 and 20 mA indicates a functioning sensor whereas a value below 4 mA indicates an error...

Страница 4: ...Refer to the Modbus Register table for the I O number for each analog input Writing a four 4 to the Units parameter defines the units as 0 to 10V Writing a two 2 to the Units parameter defines the un...

Страница 5: ...x DOx Discrete OUT x GND Ground dc common connection PWR 10 to 30 V dc power connection RX Serial communication line for the Gateway No connection for Nodes TX Serial communication line for the Gatew...

Страница 6: ...t damage Do not exceed analog input ratings for analog inputs Only connect sensor outputs to analog inputs Analog Input Wiring 10 30 V dc Power Analog Input Wiring 4 20 mA 2 Wire Externally Powered Se...

Страница 7: ...de 16 Discrete IN 4 0 1 0 1 5 5 5 Node 16 Analog IN 1 mA V 0 0 0 0 20 0 10 0 0 65535 6 6 6 Node 16 Analog IN 2 mA V 0 0 0 0 20 0 10 0 0 65535 7 7 7 Node 16 Reserved 8 8 8 Node 16 Device Message 9 9 9...

Страница 8: ...ications Certifications for DX8x C External Wiring Terminal and DX8x E Models CSA Class I Division 2 Groups ABCD Class I Zone 2 AEx Ex nA II T4 Certificate 1921239 ATEX II 3 G Ex nA IIC T4 Gc Group II...

Страница 9: ...tion country is not on this list Any misuse abuse or improper application or installation of this product or use of the product for personal protection applications when the product is identified as n...

Отзывы: