WARNING:

Connecting safety switches in series

Monitoring multiple guards with a series connection of multiple safety interlock switches is not a Safety
Category 4 Application (per ISO 13849-1). A single failure can be masked or not detected at all. The
loss of a safety stop signal or an inappropriate reset can lead to serious injury or death.

When such a configuration is used, procedures must be performed regularly to verify proper operation of
each switch. Correct all failures immediately (for example, immediately replace a failed switch).

Specifications

Contact Rating

3 A at 230 V AC max., 1.0 A at 24 V DC max.

2.5 kV maximum rated impulse withstand voltage (U

imp

)

European Rating:

U

i

 = 250 V

U

e

 = 230 V AC, 24 V DC

Ithe = 4A

Utilization categories:

 AC-15: U

e

/I

e

 230 V / 3 A; DC-13: U

e

/I

e

 24 V / 1 A

(IEC/EN 90497-5-1)

Electrical Protection Class

II, protective insulation

Contact Function

Slow make and break contacts, 2 NC, 1 NO

Wire Connections

6-pin Micro-style quick-disconnect fitting (M12 Dual-Key-Way). Cordsets are

ordered separately.

Construction

SI-HG63..:

 Hinge: Cast Stainless Steel (X22CrNi 17); Switch: PBT

SI-HGZ63..:

 Hinge: zinc die cast (nickel finish); Switch: PBT

Environmental Rating

IP67 acc. to IEC/EN 60529

W models are IEC IP69 according to IEC/EN 60529

Operating Conditions

–25 °C to +70 °C (–13 °F to +158 °F)

(connecting cable permanently mounted; no freezing over / no condensation)

Mounting

4 × M6 screws DIN EN ISO 7984 (on flat and stiff surface)

Switching Frequency

Max. 300 operations/h (5 operations per minute)

Switching Angle

NC Contact: ± 3°, Positive-opening ± 6° (wear can cause increase by 2°)

NO Contact: ± 9°

Tolerance for all angles: 1.5°

Mechanical Load

SI-HG63..:

 F

R1

 = 1800 N max., F

R2

 = 750 N max., F

A

 = 1800 N max.

SI-HGZ63..:

 F

R1

 = 1200 N max., F

R2

 = 500 N max., F

A

 = 1200 N max.

For direction of loaded forces, see Operating Range

Mechanical Life

1 million operations

Excessive loading (force) and/or vibration, as well as improper installation,

can reduce the service life.

Weight

SI-HG63..:

 approximately 0.45 kg

SI-HG63A:

 approximately 0.27 kg

SI-HGZ63..:

 approximately 0.4 kg

SI-HGZ63A:

 approximately 0.22 kg

Cabled 

SI-HG63..:

 approximately 0.65 kg

Double 

SI-HG63..:

 approximately 1 kg

Application Notes

To avoid excessive radial stress in applications containing large doors, the

hinge switch must be mounted either in pairs of two, or in conjunction with a

blank hinge.

Applicable Standards

VDE 0660 T100, DIN EN 60947-1, IEC 60947-1

VDE 0660 T200, DIN EN 60947-5-1, IEC 60947-5-1

B10d

2 × 10

6

 cycles (at DC-13; 24 V; I

e2

 = 0.1 A)

Short Circuit Protection

4 amp Slow Blow (gG). Recommended external fusing or overload

protection.

Rated conditional short-circuit current: 1000 A

Operating Range

0 to 270°

EU-Conformity

According to directive 2006/42/EG

According to directive 2006/95/EC

Approvals

C

CSA

US

 B300

Certifications

Banner Engineering Europe

 Park

Lane, Culliganlaan 2F bus 3, 1831

Diegem, BELGIUM

Turck Banner LTD

 Blenheim House,

Blenheim Court, Wickford, Essex

SS11 8YT, Great Britain

Dimensions

All measurements are listed in millimeters [inches], unless noted otherwise.
For blank hinge dimensions, see 

Blank Hinge 

on page 13.

SI-HG(Z)63 Hinge Wing Safety Interlock Switch

 

 

P/N 129465 Rev. G

www.bannerengineering.com - Tel: + 1 888 373 6767

9

Содержание SI-HG63 Series

Страница 1: ...nless Steel Inline QD With QD facing down switch is mounted on left side of hinge SI HGZ63FQDL Zinc Die cast SI HG63F5ML W Stainless Steel Inline Cable With cable exiting down switch is mounted on lef...

Страница 2: ...ver panel barrier or other physical means that separates an individual from a hazard The SI HG Z 63 will issue a signal to the machine control system to prevent or stop halt hazardous situations when...

Страница 3: ...se requirements Pass through hazards and Perimeter Guarding A pass through hazard is associated with applications where personnel may pass through a safeguard which issues a stop command to remove the...

Страница 4: ...nd that the guard or gate swings freely throughout its range of motion without binding If binding is noticed repeat the Mechanical Installation on page 3 2 Place the guard in its closed and latched po...

Страница 5: ...in a new location for example Changing the setting requires replacement of the red plastic washer See Replacement Accessory Kit on page 13 for a kit that includes a replacement washer The hinge must...

Страница 6: ...nto the enclosure until the switch cylinder arrow aligns with mark B on the switch housing The switch element should sink into the enclosure during this process Figure 16 Align to B 7 Press the switch...

Страница 7: ...codes such as the NEC National Electrical Code NFPA 79 or IEC 60204 1 and all applicable local standards and codes Connection to a Machine Electrical connection is via a 6 pin dual key M12 micro styl...

Страница 8: ...reliability OSHA 29CFR1910 or ANSI B11 19 or Category 3 or 4 ISO 13849 1 This is required to provide monitoring for safety switch failure and to provide the necessary reset routine as required by NFP...

Страница 9: ...r minute Switching Angle NC Contact 3 Positive opening 6 wear can cause increase by 2 NO Contact 9 Tolerance for all angles 1 5 Mechanical Load SI HG63 FR1 1800 N max FR2 750 N max FA 1800 N max SI HG...

Страница 10: ...mm 1 30 18 mm 0 71 4 0 mm 0 16 19 5 mm 0 77 Figure 23 Model SI HG Z 63F5MB 8 5 mm 0 33 191 0 mm 7 52 10 5 mm 0 41 37 0 mm 1 46 37 0 mm 1 46 19 5 mm 0 77 50 5 mm 1 99 63 0 mm 2 48 50 5 mm 1 99 82 0 mm...

Страница 11: ...ning direction assuming that the point has not been finely adjusted In the table find the B row of 900 and then follow over to the 6 column and note the number 94 1 mm The approximate opening in the g...

Страница 12: ...utputs with Ethernet SC26 2de XS26 2de 26 convertible I O and 2 redundant solid state safety outputs with display and Ethernet SC10 2roe 10 inputs 2 redundant relay safety outputs 3 contacts each ISD...

Страница 13: ...erity of the operating environment and the frequency of switch actuations Adjust repair or replace components as needed If inspection reveals contamination on the switch thoroughly clean the switch an...

Страница 14: ...lenheim Court Wickford Essex SS11 8YT Great Britain Banner Engineering Corp Limited Warranty Banner Engineering Corp warrants its products to be free from defects in material and workmanship for one y...

Отзывы: