To reset the Escape Release Mechanism, turn the dial 180° counterclockwise. The unit is now ready normal operation.

2.4 Access the Wiring Chamber

1. To access the wiring chamber, loosen the top cover's four screws (centered at top, bottom, and on each side) with a

screwdriver (TX 10).
The screws are captive screws and should not come all the way out of the cover.

2. Select the best wiring entrance and, if required, thread in the ½" x 14 NPT conduit adapter (SI-QS-M20, ordered

separately) or an M20 × 1.5 cable gland (SI-QS-CGM20, ordered separately). For more information, see 

Accessories

on p. 20.

3. Tighten the conduit adapter or cable gland to 6 N·m.

The switch knockout breaks loose with the final turns of the conduit adapter or cable gland.

2.4.1 Wiring the Terminals

The electrical contacts of the switching elements have screw connections. Use a flathead screwdriver to loosen and tighten

the terminals.
See 

Models

 on p. 3 for contact assignments. The connections require a stranded flexible wire with ferrule having a cross

section of 0.34 mm

2

 to 1.5 mm

2

. Strip length should be between 6 mm and 7 mm. Tighten the screws to 0.8 N·m.

When using the locking mechanism for personal protection, use the contacts marked with 

. Because the locking element

can only go to the engaged position if the actuator is present, this contact signifies the closed position and the locking

status of the guard so it can be checked by the monitoring device of the safety circuit (per ISO 14119).
When using the locking mechanism for process control purposes (only the fact that the door is closed is used for personnel
safety), the contacts marked with the 

 symbol can be used, which signals the status of the actuator (present or not).

For units with pre-installed M12 quick disconnect connections, please refer to the corresponding model addendum for pin

assignments.

2.5 Connection to a Machine

Perform a risk assessment to determine the means of interfacing the switch(es) with the machine control circuit. Although

Banner Engineering always recommends the highest level of safety in any application, it is the responsibility of the user to

safely install, operator and maintain each safety system and comply with all relevant laws and regulations.
To ensure the highest level of reliability (e.g. Control Reliable or Category 4/PL e), we recommend wiring the safety contacts

from two safety switches per interlocked guard in a dual-channel connection to a safety module, safety controller, or other

safety related parts of the control system (see 

Accessories

 on p. 20 for a list of safety evaluation devices from Banner

Engineering) that comply with the required level of safety performance as shown.

 

 

SI-GL42 Series Locking-Style Safety Interlock Switch

 

www.bannerengineering.com - Tel: + 1 888 373 6767

13

Содержание SI-GL42 Series

Страница 1: ...SI GL42 Series Locking Style Safety Interlock Switch Instruction Manual Original Instructions 220476 Rev A 22 January 2021 Banner Engineering Corp All rights reserved 220476...

Страница 2: ...4 Access the Wiring Chamber 13 2 4 1 Wiring the Terminals 13 2 5 Connection to a Machine 13 3 Operating Instructions 16 3 1 Checkout Procedures 16 3 1 1 Initial and Daily Checks 16 3 1 2 Periodic Chec...

Страница 3: ...ions 1 1 Models A complete safety system is typically made up of two interlocks two actuators two cables and a safety monitoring device The use of an emergency release mechanism depends on the applica...

Страница 4: ...1 24 V AC DC 1 NO 2 NC 1 NO Actuator Contacts Solenoid Monitor Contacts 43 44 E1 E2 13 14 31 32 21 22 Actuator Contacts Solenoid Monitor Contacts 43 44 E1 E2 13 14 31 32 21 22 Actuator Contacts Soleno...

Страница 5: ...than otherwise possible in applications where the guard can be opened and the hazard can be accessed A guard can be a gate door cover panel barrier or other physical means that separates individuals f...

Страница 6: ...al obstruction mounting in a concealed position Mounting them securely so that their physical position cannot shift using reliable fasteners that require a tool to remove Preventing the switch or the...

Страница 7: ...ugh the use of rings or guards If any areas within the guarded area are not visible from the reset switch additional safeguarding must be provided WARNING Perimeter guarding applications Failure to ob...

Страница 8: ...e switch length If vertical actuation is required move the small cover from the opening in the top of the head to the opening in the side of the head To rotate the head 1 Loosen the four screws TX10 o...

Страница 9: ...r Figure 3 Actuator dimensions and necessary minimal travel Screw on Surface Y X p p X 29 3 Y 29 3 Necessary Minimal Travel When the actuator is withdrawn from the switch s head the active axis must b...

Страница 10: ...open 25 mm The end of the tongue will still be in the opening of the switch head The head must still be equipped with an anti rotation device 5 Tighten the small alignment screw 1 to 1 5 N m 6 Open a...

Страница 11: ...The NC contacts marked with this symbol will open 3 Turn the release element back to its original position locked before restarting normal operation 4 Screw in the lock screw 0 5 N m and seal in place...

Страница 12: ...the mounting screw position 2 While holding the lever in the counterclockwise direction insert the key in the small slot near the lower mounting screw You should feel some resistance 3 Turn the lever...

Страница 13: ...tuator is present this contact signifies the closed position and the locking status of the guard so it can be checked by the monitoring device of the safety circuit per ISO 14119 When using the lockin...

Страница 14: ...ule 2 channel E stop Module 2 channel Gate Monitor Module etc Single gate or guard Solenoid Monitor Contact Solenoid Monitor Contact Locking for personnel protection Refer to the installation instruct...

Страница 15: ...ISO 13849 1 of a machine stop circuit In addition normally closed N C safety contacts from each of the two safety switches should be connected to the two separate inputs of a two channel safety monito...

Страница 16: ...trained to perform a specified checkout procedure 1 Inspect for breakage of the switch body or actuator 2 Verify good alignment and full engagement of the actuator 3 Confirmation that the safety switc...

Страница 17: ...ion Glass fiber reinformed polyamide thermoplastic UL94 V0 enclosure and cover Glass fiber reinformed polyamide thermoplastic UL94 V0 and zinc diecast actuating device Maximum Approach Speed Vmax 0 5...

Страница 18: ...Figure 11 SI QM SMFA 2 dimensions 1 2 Figure 12 SI QM SMFA 3 dimensions SI GL42 Series Locking Style Safety Interlock Switch 18 www bannerengineering com Tel 1 888 373 6767...

Страница 19: ...Figure 13 SI QM SSA 2 dimensions Figure 14 SI QM SSA 2RA dimensions SI GL42 Series Locking Style Safety Interlock Switch www bannerengineering com Tel 1 888 373 6767 19...

Страница 20: ...k Switch SI LS100 Safety Interlock Switch SI QS90 Safety Interlock Switch RP LS42 Rope Pull Switch 5 3 Cable Glands Model Size For Cable Diameter Dimensions Used With SI QS CGM20 M20 1 5 Plastic 5 0 t...

Страница 21: ...dels Expandable Models Description SC26 2 XS26 2 26 convertible I O and 2 Redundant Solid State Safety Outputs SC26 2d XS26 2d 26 convertible I O and 2 Redundant Solid State Safety Outputs with Displa...

Страница 22: ...ct THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED INCLUDING WITHOUT LIMITATION ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE AN...

Отзывы: