Banner E-Stop ES-TN-14H5 Скачать руководство пользователя страница 9

E-Stop Safety Modules with Adjustable Delay – 

Models ES-TN-14H5/-14H6

WARNING . . .

 

Reset 

Routine Required

ANSI B11 and NFPA 79 

standards require that a reset routine 

be performed after returning the E-stop 

switch to its closed-contact position 

(arming the E-stop switch). When 

Automatic Reset is used, an alternate 

means must be established to require a 

reset routine, after the E-stop switch is 

armed. 

Allowing the machine to restart 

as soon as the E-stop switch is armed 

creates an unsafe condition which could 

result in serious injury or death.

!

WARNING . . .

  

Auto Power-Up and 

Momentary Power Loss

If Auto Power-Up is selected, a 

momentary loss of power could cause 

the outputs to energize, even without a 

manual reset, when the power resumes. 

Be sure that this Auto Power-Up situation 

does not cause the machine to restart, or 

an unsafe condition may occur that could 

result in serious injury or death.

!

Configuration

Automatic Reset Mode

The E-Stop Safety Module may be configured for Automatic Reset via two independent 

DIP switches, located inside the Module housing, under the front cover (see Figures 5 

and 6) and by replacing the Reset switch with a jumper wire in the X1-X2 reset input 

circuit (see Figure 2). 
The E-Stop Safety Module will reset (and the outputs energize) as soon as the E-Stop 

switch returns to its closed-contact position (S11-S12 and S21-S22 closed), feedback 

inputs are closed (X3-X4 and X5-X6), and no fault exists. Automatic Reset will not 

occur if Manual Power-up is selected and the E-stop switch is already closed when 

power is applied.
Automatic reset mode is useful for some automated processes. 

However, if Automatic 

Reset is used, it is necessary to provide a means of preventing resumption of 

hazardous machine motion, until an alternate reset procedure is performed.

 The 

alternate procedure must include a Reset switch, located outside the area of dangerous 

motion, which is positioned so that any area of dangerous motion may be observed by 

the switch operator during the reset procedure.
NOTE:  The minimum amount of time required for the Module to be in a STOP or 

OFF condition is 100 ms. This “recovery time” (OFF-state) is required for the 

internal circuitry of the Safety Module to normalize, allowing a reliable reset 

to occur. A lockout will occur if the Module is cycled too quickly. To clear 

the lockout, the Module must be re-cycled, meeting the minimum OFF time 

requirement.

Auto Power-Up

If the Module is programmed for Auto Power-Up (see Figures 6 and 7), K1-K4 relays 

will close as soon as power is connected to A1-A2 – if the E-stop inputs S11-S12 and 

S21-S22 are closed, the appropriate jumpers are installed and feedback contacts X3-X4 

and X5-X6 are closed, whether the Module is programmed for Auto or Manual Reset.
Auto Reset may be used only if the machine being controlled will not initiate dangerous 

motion if power is applied to or interrupted from the module. In addition, an alternate 

Reset routine must be required (see WARNING at left).
The next time the E-stop is cycled when the Module is set to Manual Reset, the Reset 

button at X1-X2 must go from open to closed and back to open in order to reset the 

unit and energize the four internal relays. 
NOTE:  Auto Power-Up in combination with Manual Reset energizes the output contacts 

automatically only one time after applying power to the Module. Cycling the  

E-stop button while power is applied 

will not reset the unit. 

Manual Power-Up

If the DIP switches are set to Manual Power-Up and Manual Reset, the unit will reset 

only after power is applied and the Reset button is pushed and released. If Manual 

Power-Up and Auto Reset is selected, the E-stop button must be cycled (opened and 

closed) if it is closed after power up (but simply closed if it is open after power-up).

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Содержание E-Stop ES-TN-14H5

Страница 1: ...mediate output switching channels functional stop Category 0 and four delayed output switching channels functional stop Category 1 Delay time is adjustable from 0 20 seconds or 0 200 seconds depending on model One auxiliary non safety normally closed immediate output and one auxiliary non safety normally closed delayed output for status monitoring WARNING This Emergency Stop Safety Module is not a...

Страница 2: ...articular application are satisfied Extreme care is urged that all legal requirements have been met and that all installation and maintenance instructions contained in this manual are followed U S Standards Applicable to Use of Emergency Stop Safety Modules ANSI B11 Standards for Machine Tools Safety Requirements for the Construction Care and Use Available from Safety Director AMT The Association ...

Страница 3: ...high mass or momentum would cause the machine to run on To stop such machines quickly and safely electro mechanical or electrical brake systems like DC injection brakes or reverse current via the machine s actuators are commonly used The outputs of E stop Safety Modules ES TN 1H5 and 1H6 are two redundant normally open immediate safety contacts each of which is a series of two forced guided relay ...

Страница 4: ... Automatic Reset mode is useful for some automated processes However when Automatic Reset is used an alternate means must be established to require a Reset routine after the E stop switch is returned to its closed contact position see WARNING on page 9 This E Stop Safety Module complies with the following design standards ISO 13850 Emergency Stop Equipment Functional Aspects Principles for Design ...

Страница 5: ...eration should be used to reduce the possibility of a failure of the switch to open A short circuit failure results in loss of switching function This can occur from a short across the switch contacts a short across the wires connected to the switch somewhere between the switch and the E Stop Safety Module or a short to a secondary source of power To reduce these possibilities physically separate ...

Страница 6: ... EN418 NOTE As the normally open immediate and delayed output contacts come from physically separate relays a fault could cause only one set of contacts either the immediate or the delayed to close after a manual or auto reset This possibility must be considered in the design of the machine control circuit Connection of E Stop Switch Connect the poles of the E Stop switch as shown in Figure 3 The ...

Страница 7: ...uppressors to fail as a short circuit If installed directly across the output contacts of the Safety Module a short circuited suppressor will create an unsafe condition which could result in serious injury or death Figure 3 E Stop Safety Modules ES TN 14H5 and 14H6 hookups See page 11 for DIP switch configuration The Safety Module can not be reset until the delay output times out and switches or u...

Страница 8: ...closed monitor contact from one MSC element controlled by one of the immediate output contacts from the Module is wired in series to one normally closed monitor contact from one MSC element controlled by one of the delayed output contacts from the Module to input X3 X4 The same configuration one immediate N C series connected to one delayed N C is wired to X5 X6 Figure 2 In operation if one of the...

Страница 9: ... include a Reset switch located outside the area of dangerous motion which is positioned so that any area of dangerous motion may be observed by the switch operator during the reset procedure NOTE The minimum amount of time required for the Module to be in a STOP or OFF condition is 100 ms This recovery time OFF state is required for the internal circuitry of the Safety Module to normalize allowin...

Страница 10: ...th inputs X3 X4 and X5 X6 for closed state before a reset can occur After the unit is reset and during RUN mode both inputs will be checked for matching state In other words if one input opens the other input must open within 200 milliseconds If both pairs of output contacts both immediate and delayed are used and MSCs from all four contacts are controlled Figure 3 both an immediate MSC and a dela...

Страница 11: ... Manual power up 1 Auto power up 2 1 Channel E Stop S4 S4 1 0 2 Channel E stop 1 1 Channel E stop Delay Time Seconds T1 T2 0 0 Seconds See table below Switch Position 0 1 2 3 4 5 6 7 8 9 ES TN 1H5 0 0 5 1 2 4 6 8 10 15 20 Seconds ES TN 1H6 0 5 10 20 30 50 70 100 150 200 Seconds Figure 6 Module DIP switches and selectors set to factory settings DIP AND SELECTOR SWITCH SETTINGS REMOVE COVER FACTORY ...

Страница 12: ...output contacts 13 14 23 24 33 34 43 44 57 58 67 68 77 78 and 87 88 should close immediately and contacts 91 92 and 01 02 should open immediately E Stop Out and Timed Out LEDs must all come ON If the Module is set for Manual Reset the E Stop LED will come ON After the E Stop button is armed and the Reset LED starts flashing reset the Module by closing and opening the reset input The Reset button s...

Страница 13: ... below will flash to indicate the area where the fault has been detected See Fault Indication Table for probable cause Flashing Internal Fault See page 16 for repair E Stop green ON E Stop inputs are closed S11 S12 and S21 S22 OFF E Stop inputs are open Flashing Fault LED OFF If the module is configured for Manual Power up and Auto Reset the E Stop button must be cycled opened then closed to enter...

Страница 14: ...uring reset b In 2 Channel Monitoring inputs are not in the same state within 200 milliseconds of each other after the N O outputs close c In 1 Channel Monitoring the X3 X4 input was not closed during reset d In 1 Channel Monitoring the jumper on X5 X6 is missing POWER FAULT E STOP RESET MONITOR OUT TIMED OUT ON FLASHING ON or OFF ON or OFF ON or OFF OFF OFF Internal Fault a Internal relay failure...

Страница 15: ... 0 5 1 2 4 6 8 10 15 20 seconds K3 K4 ES TN 14H6 0 5 10 20 30 50 70 100 150 200 seconds Delayed Output Timing Tolerance Set time 100 ms or 2 whichever is greater ON Time Delay 100 ms Time from the E stop contacts to close Auto Reset or the Reset button to open Manual Reset and the safety outputs to close Input Requirements E stop switch must have a normally closed contact capable of switching 20 m...

Страница 16: ...ary to return an E Stop Safety Module to the factory please do the following 1 Contact the Banner Factory Application Engineering Group at the address or at the numbers listed below They will attempt to troubleshoot the system from your description of the problem If they conclude that a component is defective they will issue an RMA Return Merchandise Authorization number for your paperwork and giv...

Отзывы: