E-Stop Safety Modules with Adjustable Delay – 

Models ES-TN-14H5/-14H6

Initial Checkout and Troubleshooting Procedure 

 NOTE:   If more than one E-Stop switch is series-connected to one E-Stop Safety 

Module, this checkout procedure must be run individually for each switch.

1.   Remove power from the machine being guarded and from the E-Stop Safety Module.
2.   Activate the E-stop buttons (open their contacts).
3.  Remove the E-Stop Safety Module front cover, (see Figure 5).
4.   Check for correct settings on the DIP switches S1-S4 and S1.1-S4.1 (see  

Figure 6). The related pairs of switches (S1/S1.1, S2/S2.1, S3/S3.1, and S4/S4.1) 

must match at all times, as must the two Delay Time selector switches (T1/T2).

5.   After switches are set to the proper position for the application, replace the E-Stop 

Safety Module front cover.

6.   Make sure that jumpers, if required, are installed:  

 

 

1-channel monitoring:

  X5-X6 

 

1-channel E-stop:

 S21-S22 

No monitoring:

 

X3-X4, X5-X6 

Auto reset:

 

X1-X2

7.    Turn the power ON to the E-Stop Safety Module. All LEDs will turn ON for a period 

of about 0.5 seconds, after which time all but the power LED will turn OFF for about 

0.5 seconds; then the normal status indicator function will be displayed. If any LEDs 

do not cycle ON, then OFF after power is ON, disconnect power and check all wiring; 

return to step 5 after correcting the problem. If the problem cannot be corrected, 

return the Module to the factory for repair (see step 12 and page 16).

8.    E-Stop LED will be OFF if the E-stop contacts are not closed. Out and Timed-Out 

LEDs must be OFF; Monitor LED must be ON (monitor inputs are closed). The Reset 

LED must be OFF if configured for Manual Reset, and ON if configured for Automatic 

Reset.

9.    Arm the E-stop button.  

If the Module is set for Auto Reset,

 output contacts 13-14, 23-24, 33-34, 43-44, 57-

58, 67-68, 77-78, and 87-88 should close immediately, and contacts 91-92 and 01-

02 should open immediately. E-Stop, Out, and Timed-Out LEDs must all come ON. 

If the Module is set for Manual Reset,

 the E-Stop LED will come ON.  

After the E-Stop button is armed and the Reset LED starts flashing, reset the Module 

by closing and opening the reset input. (The Reset button should remain closed 

longer than 100 ms, but not longer than 2.5 seconds. The Reset LED will begin 

to flash again if the button is held in too long.) After Reset is opened, the Out and 

Timed-Out LEDs must come ON immediately. All normally open output contacts are 

closed now, and all normally closed output contacts are open. The Reset LED will 

be steady ON as long as the reset input is closed; it will go OFF if the reset input is 

opened and the four relays are ON.

10.   Activate the E-Stop switch (open its contacts); the E-Stop LED must go OFF. Out LED 

must go OFF. Contacts 13-14, 23-24, 33-34, 43-44, 57-58, 67-68, 77-78, and 87-88 

must open immediately; contacts 91-92 and 01-02 will close immediately. Contacts 

57-58, 67-68, 77-78, and 87-88 open after the selected delay time; contact 01-02 

closes after the selected delay time. Timed-Out LED will go OFF after the delay time is 

over.

11.  (Optional) Close the Cancel Delay input to immediately terminate the delay.
12.   If the complete Safety Module must be replaced, the modular terminal strips may 

easily be removed for quick installation into another module. To remove the terminal 

strips, first replace the Safety Module front cover. Then insert the blade of a small 

screwdriver into one of the four depressions in the Safety Module front cover and 

pry them loose; see Figure 7.

Figure 7.   To remove the Module’s terminal 

strips, insert a small screwdriver 

blade into each of the four slots 

at the top and bottom of the front 

cover.

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Содержание E-Stop ES-TN-14H5

Страница 1: ...mediate output switching channels functional stop Category 0 and four delayed output switching channels functional stop Category 1 Delay time is adjustable from 0 20 seconds or 0 200 seconds depending on model One auxiliary non safety normally closed immediate output and one auxiliary non safety normally closed delayed output for status monitoring WARNING This Emergency Stop Safety Module is not a...

Страница 2: ...articular application are satisfied Extreme care is urged that all legal requirements have been met and that all installation and maintenance instructions contained in this manual are followed U S Standards Applicable to Use of Emergency Stop Safety Modules ANSI B11 Standards for Machine Tools Safety Requirements for the Construction Care and Use Available from Safety Director AMT The Association ...

Страница 3: ...high mass or momentum would cause the machine to run on To stop such machines quickly and safely electro mechanical or electrical brake systems like DC injection brakes or reverse current via the machine s actuators are commonly used The outputs of E stop Safety Modules ES TN 1H5 and 1H6 are two redundant normally open immediate safety contacts each of which is a series of two forced guided relay ...

Страница 4: ... Automatic Reset mode is useful for some automated processes However when Automatic Reset is used an alternate means must be established to require a Reset routine after the E stop switch is returned to its closed contact position see WARNING on page 9 This E Stop Safety Module complies with the following design standards ISO 13850 Emergency Stop Equipment Functional Aspects Principles for Design ...

Страница 5: ...eration should be used to reduce the possibility of a failure of the switch to open A short circuit failure results in loss of switching function This can occur from a short across the switch contacts a short across the wires connected to the switch somewhere between the switch and the E Stop Safety Module or a short to a secondary source of power To reduce these possibilities physically separate ...

Страница 6: ... EN418 NOTE As the normally open immediate and delayed output contacts come from physically separate relays a fault could cause only one set of contacts either the immediate or the delayed to close after a manual or auto reset This possibility must be considered in the design of the machine control circuit Connection of E Stop Switch Connect the poles of the E Stop switch as shown in Figure 3 The ...

Страница 7: ...uppressors to fail as a short circuit If installed directly across the output contacts of the Safety Module a short circuited suppressor will create an unsafe condition which could result in serious injury or death Figure 3 E Stop Safety Modules ES TN 14H5 and 14H6 hookups See page 11 for DIP switch configuration The Safety Module can not be reset until the delay output times out and switches or u...

Страница 8: ...closed monitor contact from one MSC element controlled by one of the immediate output contacts from the Module is wired in series to one normally closed monitor contact from one MSC element controlled by one of the delayed output contacts from the Module to input X3 X4 The same configuration one immediate N C series connected to one delayed N C is wired to X5 X6 Figure 2 In operation if one of the...

Страница 9: ... include a Reset switch located outside the area of dangerous motion which is positioned so that any area of dangerous motion may be observed by the switch operator during the reset procedure NOTE The minimum amount of time required for the Module to be in a STOP or OFF condition is 100 ms This recovery time OFF state is required for the internal circuitry of the Safety Module to normalize allowin...

Страница 10: ...th inputs X3 X4 and X5 X6 for closed state before a reset can occur After the unit is reset and during RUN mode both inputs will be checked for matching state In other words if one input opens the other input must open within 200 milliseconds If both pairs of output contacts both immediate and delayed are used and MSCs from all four contacts are controlled Figure 3 both an immediate MSC and a dela...

Страница 11: ... Manual power up 1 Auto power up 2 1 Channel E Stop S4 S4 1 0 2 Channel E stop 1 1 Channel E stop Delay Time Seconds T1 T2 0 0 Seconds See table below Switch Position 0 1 2 3 4 5 6 7 8 9 ES TN 1H5 0 0 5 1 2 4 6 8 10 15 20 Seconds ES TN 1H6 0 5 10 20 30 50 70 100 150 200 Seconds Figure 6 Module DIP switches and selectors set to factory settings DIP AND SELECTOR SWITCH SETTINGS REMOVE COVER FACTORY ...

Страница 12: ...output contacts 13 14 23 24 33 34 43 44 57 58 67 68 77 78 and 87 88 should close immediately and contacts 91 92 and 01 02 should open immediately E Stop Out and Timed Out LEDs must all come ON If the Module is set for Manual Reset the E Stop LED will come ON After the E Stop button is armed and the Reset LED starts flashing reset the Module by closing and opening the reset input The Reset button s...

Страница 13: ... below will flash to indicate the area where the fault has been detected See Fault Indication Table for probable cause Flashing Internal Fault See page 16 for repair E Stop green ON E Stop inputs are closed S11 S12 and S21 S22 OFF E Stop inputs are open Flashing Fault LED OFF If the module is configured for Manual Power up and Auto Reset the E Stop button must be cycled opened then closed to enter...

Страница 14: ...uring reset b In 2 Channel Monitoring inputs are not in the same state within 200 milliseconds of each other after the N O outputs close c In 1 Channel Monitoring the X3 X4 input was not closed during reset d In 1 Channel Monitoring the jumper on X5 X6 is missing POWER FAULT E STOP RESET MONITOR OUT TIMED OUT ON FLASHING ON or OFF ON or OFF ON or OFF OFF OFF Internal Fault a Internal relay failure...

Страница 15: ... 0 5 1 2 4 6 8 10 15 20 seconds K3 K4 ES TN 14H6 0 5 10 20 30 50 70 100 150 200 seconds Delayed Output Timing Tolerance Set time 100 ms or 2 whichever is greater ON Time Delay 100 ms Time from the E stop contacts to close Auto Reset or the Reset button to open Manual Reset and the safety outputs to close Input Requirements E stop switch must have a normally closed contact capable of switching 20 m...

Страница 16: ...ary to return an E Stop Safety Module to the factory please do the following 1 Contact the Banner Factory Application Engineering Group at the address or at the numbers listed below They will attempt to troubleshoot the system from your description of the problem If they conclude that a component is defective they will issue an RMA Return Merchandise Authorization number for your paperwork and giv...

Отзывы: