Banner E-Stop ES-TN-14H5 Скачать руководство пользователя страница 1

E-Stop Safety Modules with Adjustable Delay

®

Models 

ES-TN-14H5

 with 0-20 second delay, 

ES-TN-14H6

 with 0-200 second delay

Features

•   Selectable Auto-Reset or monitored Manual Reset.

•  Auto or manual power-up

•  One- or two-channel feedback monitoring

•   Monitors one dual-channel or one single-channel normally closed E-stop switch 

circuit for a contact failure or wiring fault (safety category 2 or 4,  

per ISO13849-1 [EN954-1]; see pages 5-7).

•  4 amp safety output contacts

•  Removable terminal blocks

•   Input monitoring circuit has diverse-redundant microprocessors

•   Designed for use in functional stop Category 0 and 1 applications (per ISO/EN 

60204-1 and NFPA79)

•   Four immediate output switching channels (functional stop Category 0) and four 

delayed output switching channels (functional stop Category 1). Delay time is 

adjustable from 0-20 seconds or 0-200 seconds, depending on model. 

•   One auxiliary non-safety, normally closed immediate output and one auxiliary 

non-safety normally closed delayed output for status monitoring.

WARNING . . .

  

This Emergency Stop 

Safety Module is not 

a point-of-operation 

guarding device, as 

defined by OSHA regulations.

 It 

is necessary to install point-of-

operation guarding devices, such 

as safety light screens and/or hard 

guards, to protect personnel from 

hazardous machinery. 

Failure to 

install point-of-operation guards 

on hazardous machinery can 

result in a dangerous condition 

which could lead to serious 

injury or death.

!

Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]

Содержание E-Stop ES-TN-14H5

Страница 1: ...mediate output switching channels functional stop Category 0 and four delayed output switching channels functional stop Category 1 Delay time is adjustable from 0 20 seconds or 0 200 seconds depending on model One auxiliary non safety normally closed immediate output and one auxiliary non safety normally closed delayed output for status monitoring WARNING This Emergency Stop Safety Module is not a...

Страница 2: ...articular application are satisfied Extreme care is urged that all legal requirements have been met and that all installation and maintenance instructions contained in this manual are followed U S Standards Applicable to Use of Emergency Stop Safety Modules ANSI B11 Standards for Machine Tools Safety Requirements for the Construction Care and Use Available from Safety Director AMT The Association ...

Страница 3: ...high mass or momentum would cause the machine to run on To stop such machines quickly and safely electro mechanical or electrical brake systems like DC injection brakes or reverse current via the machine s actuators are commonly used The outputs of E stop Safety Modules ES TN 1H5 and 1H6 are two redundant normally open immediate safety contacts each of which is a series of two forced guided relay ...

Страница 4: ... Automatic Reset mode is useful for some automated processes However when Automatic Reset is used an alternate means must be established to require a Reset routine after the E stop switch is returned to its closed contact position see WARNING on page 9 This E Stop Safety Module complies with the following design standards ISO 13850 Emergency Stop Equipment Functional Aspects Principles for Design ...

Страница 5: ...eration should be used to reduce the possibility of a failure of the switch to open A short circuit failure results in loss of switching function This can occur from a short across the switch contacts a short across the wires connected to the switch somewhere between the switch and the E Stop Safety Module or a short to a secondary source of power To reduce these possibilities physically separate ...

Страница 6: ... EN418 NOTE As the normally open immediate and delayed output contacts come from physically separate relays a fault could cause only one set of contacts either the immediate or the delayed to close after a manual or auto reset This possibility must be considered in the design of the machine control circuit Connection of E Stop Switch Connect the poles of the E Stop switch as shown in Figure 3 The ...

Страница 7: ...uppressors to fail as a short circuit If installed directly across the output contacts of the Safety Module a short circuited suppressor will create an unsafe condition which could result in serious injury or death Figure 3 E Stop Safety Modules ES TN 14H5 and 14H6 hookups See page 11 for DIP switch configuration The Safety Module can not be reset until the delay output times out and switches or u...

Страница 8: ...closed monitor contact from one MSC element controlled by one of the immediate output contacts from the Module is wired in series to one normally closed monitor contact from one MSC element controlled by one of the delayed output contacts from the Module to input X3 X4 The same configuration one immediate N C series connected to one delayed N C is wired to X5 X6 Figure 2 In operation if one of the...

Страница 9: ... include a Reset switch located outside the area of dangerous motion which is positioned so that any area of dangerous motion may be observed by the switch operator during the reset procedure NOTE The minimum amount of time required for the Module to be in a STOP or OFF condition is 100 ms This recovery time OFF state is required for the internal circuitry of the Safety Module to normalize allowin...

Страница 10: ...th inputs X3 X4 and X5 X6 for closed state before a reset can occur After the unit is reset and during RUN mode both inputs will be checked for matching state In other words if one input opens the other input must open within 200 milliseconds If both pairs of output contacts both immediate and delayed are used and MSCs from all four contacts are controlled Figure 3 both an immediate MSC and a dela...

Страница 11: ... Manual power up 1 Auto power up 2 1 Channel E Stop S4 S4 1 0 2 Channel E stop 1 1 Channel E stop Delay Time Seconds T1 T2 0 0 Seconds See table below Switch Position 0 1 2 3 4 5 6 7 8 9 ES TN 1H5 0 0 5 1 2 4 6 8 10 15 20 Seconds ES TN 1H6 0 5 10 20 30 50 70 100 150 200 Seconds Figure 6 Module DIP switches and selectors set to factory settings DIP AND SELECTOR SWITCH SETTINGS REMOVE COVER FACTORY ...

Страница 12: ...output contacts 13 14 23 24 33 34 43 44 57 58 67 68 77 78 and 87 88 should close immediately and contacts 91 92 and 01 02 should open immediately E Stop Out and Timed Out LEDs must all come ON If the Module is set for Manual Reset the E Stop LED will come ON After the E Stop button is armed and the Reset LED starts flashing reset the Module by closing and opening the reset input The Reset button s...

Страница 13: ... below will flash to indicate the area where the fault has been detected See Fault Indication Table for probable cause Flashing Internal Fault See page 16 for repair E Stop green ON E Stop inputs are closed S11 S12 and S21 S22 OFF E Stop inputs are open Flashing Fault LED OFF If the module is configured for Manual Power up and Auto Reset the E Stop button must be cycled opened then closed to enter...

Страница 14: ...uring reset b In 2 Channel Monitoring inputs are not in the same state within 200 milliseconds of each other after the N O outputs close c In 1 Channel Monitoring the X3 X4 input was not closed during reset d In 1 Channel Monitoring the jumper on X5 X6 is missing POWER FAULT E STOP RESET MONITOR OUT TIMED OUT ON FLASHING ON or OFF ON or OFF ON or OFF OFF OFF Internal Fault a Internal relay failure...

Страница 15: ... 0 5 1 2 4 6 8 10 15 20 seconds K3 K4 ES TN 14H6 0 5 10 20 30 50 70 100 150 200 seconds Delayed Output Timing Tolerance Set time 100 ms or 2 whichever is greater ON Time Delay 100 ms Time from the E stop contacts to close Auto Reset or the Reset button to open Manual Reset and the safety outputs to close Input Requirements E stop switch must have a normally closed contact capable of switching 20 m...

Страница 16: ...ary to return an E Stop Safety Module to the factory please do the following 1 Contact the Banner Factory Application Engineering Group at the address or at the numbers listed below They will attempt to troubleshoot the system from your description of the problem If they conclude that a component is defective they will issue an RMA Return Merchandise Authorization number for your paperwork and giv...