Banner DXM150-S2 Скачать руководство пользователя страница 26

5.2.2 Connecting a Battery to the 

DXM Modbus Slave

When attaching a battery to the DXM Modbus Slave as a backup battery or as a solar battery, verify the charging algorithm

is set properly. The factory default setting for the battery charging algorithm assumes you are using 12 to 30 V dc to

recharge the battery.
The charging algorithm is designed to work with a sealed lead acid (SLA) battery only.

• When using 12 to 30 V dc, connect the 12 to 30 V dc + to pin 2 and connect the ground to pin 3.
• When using main dc power with a back up battery (default configuration), connect the incoming main power pin 2

(+) and to pin 3 (-). Connect the 12 V sealed lead acid battery to pin 4 (+) and pin 5 (-). The incoming main power

must be 15 to 30 V dc to charge the battery.

• When using a solar panel, connect the solar panel output to pin 2 and connect the ground to pin 3. Connect the 12

V dc SLA battery to pin 4 (+) and pin 5 (-). To change the charging algorithm, refer to 

Supplying Power from a Solar

Panel

 on page 10.

The battery charging algorithm defaults to a battery backup configuration. To charge the battery from a solar panel, change

the battery charging algorithm.

1. From the DXM Modbus Slave LCD menu navigate to Setting Config > I/O Board > Charger.
2. Select Solar for solar panel configurations or DC for battery backup configurations.

Modbus Slave ID

Modbus Register

Description

11 *

6071

Battery backup charging algorithm.

0 = Battery is recharged from a solar panel
1 = Battery is recharged from 12 to 30 V dc (default)

* The Modbus Slave ID for the base board is set at the factory and may be changed using the base board DIP switch

settings.

5.3 Working with Solar Power

A reliable solar system requires careful planning and monitoring to size the components correctly. The recommendations

provided are for the DXM Modbus Slave system as an autonomous system.
Adding extra components increases the power requirements and likely requires increasing the solar system components.

Depending upon the geographical location, the size of the solar panel and battery may vary.

5.3.1 Setting the 

DXM Modbus Slave

 for Solar Power

By default, the DXM Modbus Slave is set from the factory to charge a backup battery from a line power source. Use the

LCD menu on the front of the DXM Modbus Slave to change the charging algorithm to solar power.
Go to System Config > I/O Board > Charger. Use the up/down arrows to select Solar.
For DXM devices without an LCD, adjust the I/O board Modbus register 6071. Set the register to 0 to select battery

charging from a solar panel, and set to 1 to select battery charging from incoming 12 to 30 V dc supply.
Here are a few DXM configuration tips to help minimize the power consumption (may not apply to all models).

• If Ethernet is not being used, save up to 25% of the consumed power by disabling Ethernet. Set DIP switch 1 to the

ON position on the processor board then reboot.

• Instead of powering external devices all the time, take advantage of the switched power mechanisms to turn off

devices when possible.

• Minimize the number of cellular transactions and the amount of data pushed across the cellular modem.

5.3.2 Solar Components

The components of a solar system include the battery and the solar panel.

Battery

The DXM solar controller is designed to use a 12 V lead acid battery. The characteristics of a solar system require the

battery to be of a certain type. There are basically two types of lead acid batteries:

• SLI batteries (Starting Lights Ignition) designed for quick bursts of energy, like starting engines
• Deep Cycle batteries - greater long-term energy delivery. This is the best choice for a solar battery.

Since a solar system charges and discharges daily, a deep cycle battery is the best choice. There are different versions of a

lead acid battery: wet cell (flooded), gel cell, and an AGM (absorbed glass mat).

DXM150-Sx Wireless Modbus Slave

 

 

26

www.bannerengineering.com - Tel: +1.763.544.3164

 

Содержание DXM150-S2

Страница 1: ...DXM150 Sx Wireless Modbus Slave Instruction Manual Original Instructions 195455 Rev B 13 July 2018 Banner Engineering Corp All rights reserved 195455...

Страница 2: ...odbus Slave ID on the I O Base Board 21 4 6 1 DXM150 Sx Wireless Modbus Slave Models 21 4 6 2 Setting the DXM I O Board Modbus Slave ID using Modbus Registers 21 4 6 3 I O Board Jumpers 21 5 I O Base...

Страница 3: ...ite Information 40 9 2 3 Feature Requests 40 9 2 4 Potential DXM Issues 40 9 2 5 DXM Security 41 9 3 Contact Us 41 10 Warnings 43 10 1 Banner Engineering Corp Limited Warranty 43 DXM150 Sx Wireless Mo...

Страница 4: ...l Overview The DXM Configuration Tool configures the DXM Modbus Slave by creating an XML file that is transferred to the DXM Modbus Slave using a USB or Ethernet connection The DXM Modbus Slave can al...

Страница 5: ...rovides connections for all inputs outputs and power The base board also contains a 12 V solar controller that accepts connections to a solar panel and SLA battery The battery connection can also be u...

Страница 6: ...in the model number DXMxxx xxR1 DX80 Performance 900MHz DXMxxx xxR3 DX80 Performance 2 4GHz DXMxxx xxR8 DX80 Performance 900MHz Australia The settings outlined below are specific for the DXM Modbus S...

Страница 7: ...col for routing packets In Modbus mode a routing table is stored in each parent device to optimize the radio traffic This allows for point to point communication in a multiple data radio network and a...

Страница 8: ...adio datasheet refer to the MultiHop Quick Start Guide p n 152653 or Instruction Manual p n 151317 The ISM radio board s Modbus ID is assigned from the master radio during binding using the master rad...

Страница 9: ...d 40 Universal Input 5 9 Not used 25 NMOS Output 5 41 Ground 10 Not used 26 No connection 42 Universal Input 4 11 Not used 27 NMOS Output 6 43 Universal Input 3 12 Not used 28 NMOS Output 7 44 Ground...

Страница 10: ...4008 and 4028 contain a value of 2 To select voltage 0 10 V for output Aout1 set jumper 1 in the voltage position V and set Modbus register 4008 on the I O board SID 200 to 3 To select voltage 0 10 V...

Страница 11: ...ure inputs define one of the universal inputs as a temperature input Modbus Slave ID Modbus Register Description 11 6081 Battery voltage mV 6082 Battery charging current mA 6083 Incoming supply voltag...

Страница 12: ...p to 25 of the consumed power by disabling Ethernet Set DIP switch 1 to the ON position on the processor board then reboot Instead of powering external devices all the time take advantage of the switc...

Страница 13: ...all amounts of snow in the corners of the panel Because all cells are connected in a series string the weakest cell will bring down the other cells power level Good quality solar panels will not degra...

Страница 14: ...loudy First Day Figure 3 Battery Voltage mV Cloudy First Day 4 4 Connecting the Communication Pins The base board communications connection for external Modbus device uses the primary RS 485 RS 485 Th...

Страница 15: ...gram an input to capture the edge transition counts follow Example Configure Input 1 as a Synchronous Counter on page 18 The counters are synchronous because the inputs are sampled at a 10 ms clock ra...

Страница 16: ...ters for Analog Output 2 start at 4021 through 4028 Parameter Registers for Analog Outputs 4xxxx OUT 1 OUT 2 Parameters 4001 4021 Maximum Analog Value 4002 4022 Minimum Analog Value 4003 4023 Enable R...

Страница 17: ...programmed to accept different types of inputs discrete NPN PNP 0 to 20 mA analog 0 to 10 V analog 10k thermistor potentiometer sense bridge and NPN raw fast Use the DXM Configuration Tool tool to wr...

Страница 18: ...ge 6 Change the Source Register selection to I O Board Registers 7 Write a 3 to Modbus register 3326 on Modbus Slave ID 11 I O board 8 Cycle power to the device 9 Using the Register View tab read regi...

Страница 19: ...put 1 4 Universal input 2 5 Universal input 3 6 Universal input 4 7 Universal input 5 8 Universal input 6 9 Universal input 7 10 Universal input 8 Base Board Output Connection Modbus Register Descript...

Страница 20: ...r point or reporting threshold ON point for a sensor input Setting a threshold establishes an ON point Hysteresis defines how far below the threshold the analog input is required to be before the inpu...

Страница 21: ...ary dial location K and DIP Switch location J set the Modbus Slave IDs DIP Switches J Location K Rotary Dials Position 0 through 9 1 2 0 1 2 3 4 5 6 7 8 9 OFF OFF x 3 11 12 13 14 15 16 17 18 19 ON OFF...

Страница 22: ...tput characteristics for AO2 pin 32 and AO1 pin 33 Defines current 0 20 mA or voltage 0 10 V for analog output 1 and 2 By default current 0 20 mA is selected using jumpers 1 and 2 and registers 4008 a...

Страница 23: ...put 4 PNP NPN 38 Universal Input 7 7 Primary RS 485 23 PWR Out OR 39 Universal Input 6 8 Ground 24 Ground 40 Universal Input 5 9 RS 232 Tx CAN 25 Ground 41 Ground 10 RS 232 Rx CAN 26 PWR OUT OR 42 Uni...

Страница 24: ...t the jumpers to use pins 9 and 10 as a CAN serial port or a generic RS 232 serial port Both jumpers must be set to the same operation CAN or RS232 The default setting is CAN serial port G3 Analog out...

Страница 25: ...ry is recharged from a solar panel 1 Battery is recharged from 12 to 30 V dc default The following power operating characteristics are stored in Modbus registers Battery voltage If no battery is prese...

Страница 26: ...mponents increases the power requirements and likely requires increasing the solar system components Depending upon the geographical location the size of the solar panel and battery may vary 5 3 1 Set...

Страница 27: ...eristics Use the 5 watt panel for light duty operation and use the 20 watt panel when you require greater charging capabilities Solar Panel Voltage Current Typical DXM Configurations 5 Watt 17 V 0 29...

Страница 28: ...chart shows three days of charging Figure 6 Solar Panel Voltage mV Cloudy First Day Figure 7 Battery Voltage mV Cloudy First Day 5 4 Connecting the Communication Pins The base board communications con...

Страница 29: ...0 to 10 V 0 to 20 mA or potentiometer The default setting is 8 NPN raw fast To set the input type write the following values to the Input Type Modbus registers 0 NPN 1 PNP 2 0 to 20 mA 3 0 to 10 V dc...

Страница 30: ...to a 0 to 10 V dc Output 1 Connect the DXM Modbus Slave to the PC 2 Launch the DXM Configuration Tool software 3 Connect to the DXM Modbus Slave by selecting the Device Connection Settings menu option...

Страница 31: ...configured as either 0 to 20 mA outputs default or 0 to 10 V outputs To change the analog output type change the hardware jumper position and write to the Modbus register that defines the analog outp...

Страница 32: ...AC input type 0 to 12 to 30 V dc Input to output isolation of 2 5 kV IN xA IN xB Pin 15 Input 1B Pin 16 Input 2A Pin 17 Input 2B Synchronous Counters An isolated input can be programmed to count the i...

Страница 33: ...3033 Enable rising edge counter 3034 Enable falling edge counter 3035 High register for counter 3036 Low register for counter Universal Input Parameter Modbus Registers Universal Inputs 1 2 3 4 5 6 7...

Страница 34: ...iometer The default setting is 8 NPN raw fast To set the input type write the following values to the Input Type Modbus registers 0 NPN 1 PNP 2 0 to 20 mA 3 0 to 10 V dc 4 10k Thermistor 5 Potentiomet...

Страница 35: ...IDs DIP Switches J Location K Rotary Dials Position 0 through 9 1 2 0 1 2 3 4 5 6 7 8 9 OFF OFF x 6 11 12 13 14 15 16 17 18 19 ON OFF 20 21 22 23 24 25 26 27 28 29 OFF ON 30 31 32 33 34 35 36 37 38 3...

Страница 36: ...is based in 100 millisecond units Once written the timer starts to count down to zero After the timer expires the restore factory defaults are applied if register 4152 1 If register 4152 is zero the I...

Страница 37: ...2 Write a 10 to Modbus register 4151 Modbus Register Values Description 4151 0 255 Reset restore trigger This timer is based in 100 millisecond units Once written the timer starts to count down to zer...

Страница 38: ...ons 94 6 mm 3 72 85 mm 3 35 35 mm 1 38 59 5 mm 2 34 156 mm 6 14 All measurements are listed in millimeters inches unless noted otherwise DXM150 Sx Wireless Modbus Slave 38 www bannerengineering com Te...

Страница 39: ...Medium Range Omni Antennas BWA 9O5 C Antenna Rubber Swivel 900 MHz 5 dBi RP SMA Male Connector BWA 2O5 C Antenna Rubber Swivel 2 4 GHz 5 dBi RP SMA Male Connector Long Range Omni Antennas BWA 9O8 AS...

Страница 40: ...best operation for the DXM Modbus Slave stay connected with Banner Engineering Corp to hear about the latest updates through the Banner website Create a login today to stay informed of all Banner pro...

Страница 41: ...one 90 216 688 8282 Website www bannerengineering com Email turkey bannerengineering com tr India Address Banner Engineering India Pune Head Quarters Office No 1001 10th Floor Sai Capital Opp ICC Sena...

Страница 42: ...411 Website www bannerengineering com Email mail bannerengineering co jp Taiwan Address Banner Engineering Taiwan 8F 2 No 308 Section 1 Neihu Road Taipei 114 Taiwan Phone 886 0 2 8751 9966 Website www...

Страница 43: ...or liability for misuse abuse or the improper application or installation of the Banner product THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED INCLU...

Отзывы: