• 2952 Enable Default Communication Timeout. A “communication timeout" refers to the communication between any

Modbus master host and the DXM baseboard. Set this register to 1 to enable the default condition when the host

has not communicated with the DXM baseboard for the period of time defined by the Communication Default IO

Timeout.

• 2953 Communication Default I/O Timeout (100 ms/Count). This parameter defines the host timeout period in 100

millisecond increments. If a host does not communicate within this timeout period, the device outputs are set to the

default values.

• 2954 Enable Default on Power Up. Setting this parameter to 1 sends the device outputs to their default condition

when the DXM baseboard is powered up. Set to 0 to disable this feature.

Default Output State. The Default Output State parameter represents the default condition of the analog output. When an

error condition exists, the outputs are set to this 16-bit user-defined output state. To define the error conditions for device

outputs, refer to the MultiHop default output parameters 2950-2954.
Enable Register Full Scale. Set to 1 to enable a linear range from 0 to 65535 for specified input range. For a 4 to 20 mA

output, a value of 0 represents 4 mA and 65535 represents 20 mA. Set this parameter to 0 to store readings in unit-specific

data. For example, the register data representing a 15.53 mA reading is 15530. For units of current (0 to 20 mA outputs),

values are stored as µA (micro Amps) and voltage values are stored as mV (millivolts).
Hold Last State Enable. Set the Hold Last State to 1 to set the output to its last known value before the error occurred. Set

this parameter to 0 to disable the Hold Last State and use the Default Output State setting during an error condition.
Maximum Analog Value. The Maximum Analog Value register stores the maximum allowed analog value. The specific units

of measure apply to the register value. For example, the register may contain 20000, for 20 mA, or for a voltage output the

register may contain 8000, for 8 volts.
Minimum Analog Value. The Minimum Analog Value register stores the minimum allowed analog value. The specific units of

measure apply to register value. For example, the register may contain 4000, for 4 mA, or for a voltage output the register

may contain 2000, for 2 volts.

4.5.5 Universal Inputs

The universal inputs can be programmed to accept different types of inputs: discrete NPN/PNP, 0 to 20 mA analog, 0 to 10

V analog, 10k thermistor, potentiometer sense, bridge, and NPN raw fast. Use the DXM Configuration Tool tool to write to

the appropriate Modbus registers in the I/O board to configure the input type.
The universal inputs are treated as analog inputs. When the universal inputs are defined as mA, V, or temperature, use

Modbus registers to configure the operational characteristics of the inputs. These parameters are temperature conversion

type, enable full scale, threshold and hysteresis. See the Modbus register section for the parameter definitions.
When a universal input is configured as an NPN or PNP input type, it can be enabled to be a synchronous counter. Enable

the counter function by setting Modbus register 'Enable Rising' or 'Enable Falling' to 1. See 

Modbus Registers

 for the

universal input register definitions.

Pin

Univ. Input

Description

Pin 47

Universal Input 1

Program the universal inputs to accept input types NPN, PNP, 10k thermistor, 0 to 10 V, 0 to
20 mA, or potentiometer. The default setting is 8: NPN raw fast. To set the input type, write the
following values to the Input Type Modbus registers.

0 = NPN
1 = PNP
2 = 0 to 20 mA
3 = 0 to 10 V dc
4 = 10k Thermistor
5 = Potentiometer Sense (DXM150 only)
6 = Not used
7 = Bridge
8 = NPN Raw Fast (default)

Pin 46

Universal Input 2

Pin 43

Universal Input 3

Pin 42

Universal Input 4

Pin 40

Universal Input 5

Pin 39

Universal Input 6

Pin 38

Universal Input 7

Pin 37

Universal Input 8

Thermistor Input. A thermistor input must use a 10k thermistor between ground and the universal input. The thermistor must

be a 10k NTC (Banner model number BWA-THERMISTOR-002) or equivalent. Select the temperature conversion of degrees

C (default) or degrees F by writing to the Modbus registers defined in 

I/O Base Board

.

Potentiometer Sense (DXM150 only). A potentiometer input is created from two inputs: a voltage source (pin 45) that

supplies a voltage to the potentiometer and an input sense (Potentiometer Sense) to read the resistance. Follow 

Example:

Change Universal Input 8 to Read a Potentiometer Input 

on page 18 to configure the DXM150 Controller for a

potentiometer input.
Potentiometer Input (DXM100 only). A potentiometer input is created from three inputs: a voltage source (pin 30) that

supplies 5 V to the potentiometer and two inputs set to voltage inputs to read the voltage across the potentiometer. See the

DXM technical note for setting up a potentiometer.

 

 

DXM150-Sx Wireless Modbus Slave

 

www.bannerengineering.com - Tel: +1.763.544.3164

17

Содержание DXM150-S2

Страница 1: ...DXM150 Sx Wireless Modbus Slave Instruction Manual Original Instructions 195455 Rev B 13 July 2018 Banner Engineering Corp All rights reserved 195455...

Страница 2: ...odbus Slave ID on the I O Base Board 21 4 6 1 DXM150 Sx Wireless Modbus Slave Models 21 4 6 2 Setting the DXM I O Board Modbus Slave ID using Modbus Registers 21 4 6 3 I O Board Jumpers 21 5 I O Base...

Страница 3: ...ite Information 40 9 2 3 Feature Requests 40 9 2 4 Potential DXM Issues 40 9 2 5 DXM Security 41 9 3 Contact Us 41 10 Warnings 43 10 1 Banner Engineering Corp Limited Warranty 43 DXM150 Sx Wireless Mo...

Страница 4: ...l Overview The DXM Configuration Tool configures the DXM Modbus Slave by creating an XML file that is transferred to the DXM Modbus Slave using a USB or Ethernet connection The DXM Modbus Slave can al...

Страница 5: ...rovides connections for all inputs outputs and power The base board also contains a 12 V solar controller that accepts connections to a solar panel and SLA battery The battery connection can also be u...

Страница 6: ...in the model number DXMxxx xxR1 DX80 Performance 900MHz DXMxxx xxR3 DX80 Performance 2 4GHz DXMxxx xxR8 DX80 Performance 900MHz Australia The settings outlined below are specific for the DXM Modbus S...

Страница 7: ...col for routing packets In Modbus mode a routing table is stored in each parent device to optimize the radio traffic This allows for point to point communication in a multiple data radio network and a...

Страница 8: ...adio datasheet refer to the MultiHop Quick Start Guide p n 152653 or Instruction Manual p n 151317 The ISM radio board s Modbus ID is assigned from the master radio during binding using the master rad...

Страница 9: ...d 40 Universal Input 5 9 Not used 25 NMOS Output 5 41 Ground 10 Not used 26 No connection 42 Universal Input 4 11 Not used 27 NMOS Output 6 43 Universal Input 3 12 Not used 28 NMOS Output 7 44 Ground...

Страница 10: ...4008 and 4028 contain a value of 2 To select voltage 0 10 V for output Aout1 set jumper 1 in the voltage position V and set Modbus register 4008 on the I O board SID 200 to 3 To select voltage 0 10 V...

Страница 11: ...ure inputs define one of the universal inputs as a temperature input Modbus Slave ID Modbus Register Description 11 6081 Battery voltage mV 6082 Battery charging current mA 6083 Incoming supply voltag...

Страница 12: ...p to 25 of the consumed power by disabling Ethernet Set DIP switch 1 to the ON position on the processor board then reboot Instead of powering external devices all the time take advantage of the switc...

Страница 13: ...all amounts of snow in the corners of the panel Because all cells are connected in a series string the weakest cell will bring down the other cells power level Good quality solar panels will not degra...

Страница 14: ...loudy First Day Figure 3 Battery Voltage mV Cloudy First Day 4 4 Connecting the Communication Pins The base board communications connection for external Modbus device uses the primary RS 485 RS 485 Th...

Страница 15: ...gram an input to capture the edge transition counts follow Example Configure Input 1 as a Synchronous Counter on page 18 The counters are synchronous because the inputs are sampled at a 10 ms clock ra...

Страница 16: ...ters for Analog Output 2 start at 4021 through 4028 Parameter Registers for Analog Outputs 4xxxx OUT 1 OUT 2 Parameters 4001 4021 Maximum Analog Value 4002 4022 Minimum Analog Value 4003 4023 Enable R...

Страница 17: ...programmed to accept different types of inputs discrete NPN PNP 0 to 20 mA analog 0 to 10 V analog 10k thermistor potentiometer sense bridge and NPN raw fast Use the DXM Configuration Tool tool to wr...

Страница 18: ...ge 6 Change the Source Register selection to I O Board Registers 7 Write a 3 to Modbus register 3326 on Modbus Slave ID 11 I O board 8 Cycle power to the device 9 Using the Register View tab read regi...

Страница 19: ...put 1 4 Universal input 2 5 Universal input 3 6 Universal input 4 7 Universal input 5 8 Universal input 6 9 Universal input 7 10 Universal input 8 Base Board Output Connection Modbus Register Descript...

Страница 20: ...r point or reporting threshold ON point for a sensor input Setting a threshold establishes an ON point Hysteresis defines how far below the threshold the analog input is required to be before the inpu...

Страница 21: ...ary dial location K and DIP Switch location J set the Modbus Slave IDs DIP Switches J Location K Rotary Dials Position 0 through 9 1 2 0 1 2 3 4 5 6 7 8 9 OFF OFF x 3 11 12 13 14 15 16 17 18 19 ON OFF...

Страница 22: ...tput characteristics for AO2 pin 32 and AO1 pin 33 Defines current 0 20 mA or voltage 0 10 V for analog output 1 and 2 By default current 0 20 mA is selected using jumpers 1 and 2 and registers 4008 a...

Страница 23: ...put 4 PNP NPN 38 Universal Input 7 7 Primary RS 485 23 PWR Out OR 39 Universal Input 6 8 Ground 24 Ground 40 Universal Input 5 9 RS 232 Tx CAN 25 Ground 41 Ground 10 RS 232 Rx CAN 26 PWR OUT OR 42 Uni...

Страница 24: ...t the jumpers to use pins 9 and 10 as a CAN serial port or a generic RS 232 serial port Both jumpers must be set to the same operation CAN or RS232 The default setting is CAN serial port G3 Analog out...

Страница 25: ...ry is recharged from a solar panel 1 Battery is recharged from 12 to 30 V dc default The following power operating characteristics are stored in Modbus registers Battery voltage If no battery is prese...

Страница 26: ...mponents increases the power requirements and likely requires increasing the solar system components Depending upon the geographical location the size of the solar panel and battery may vary 5 3 1 Set...

Страница 27: ...eristics Use the 5 watt panel for light duty operation and use the 20 watt panel when you require greater charging capabilities Solar Panel Voltage Current Typical DXM Configurations 5 Watt 17 V 0 29...

Страница 28: ...chart shows three days of charging Figure 6 Solar Panel Voltage mV Cloudy First Day Figure 7 Battery Voltage mV Cloudy First Day 5 4 Connecting the Communication Pins The base board communications con...

Страница 29: ...0 to 10 V 0 to 20 mA or potentiometer The default setting is 8 NPN raw fast To set the input type write the following values to the Input Type Modbus registers 0 NPN 1 PNP 2 0 to 20 mA 3 0 to 10 V dc...

Страница 30: ...to a 0 to 10 V dc Output 1 Connect the DXM Modbus Slave to the PC 2 Launch the DXM Configuration Tool software 3 Connect to the DXM Modbus Slave by selecting the Device Connection Settings menu option...

Страница 31: ...configured as either 0 to 20 mA outputs default or 0 to 10 V outputs To change the analog output type change the hardware jumper position and write to the Modbus register that defines the analog outp...

Страница 32: ...AC input type 0 to 12 to 30 V dc Input to output isolation of 2 5 kV IN xA IN xB Pin 15 Input 1B Pin 16 Input 2A Pin 17 Input 2B Synchronous Counters An isolated input can be programmed to count the i...

Страница 33: ...3033 Enable rising edge counter 3034 Enable falling edge counter 3035 High register for counter 3036 Low register for counter Universal Input Parameter Modbus Registers Universal Inputs 1 2 3 4 5 6 7...

Страница 34: ...iometer The default setting is 8 NPN raw fast To set the input type write the following values to the Input Type Modbus registers 0 NPN 1 PNP 2 0 to 20 mA 3 0 to 10 V dc 4 10k Thermistor 5 Potentiomet...

Страница 35: ...IDs DIP Switches J Location K Rotary Dials Position 0 through 9 1 2 0 1 2 3 4 5 6 7 8 9 OFF OFF x 6 11 12 13 14 15 16 17 18 19 ON OFF 20 21 22 23 24 25 26 27 28 29 OFF ON 30 31 32 33 34 35 36 37 38 3...

Страница 36: ...is based in 100 millisecond units Once written the timer starts to count down to zero After the timer expires the restore factory defaults are applied if register 4152 1 If register 4152 is zero the I...

Страница 37: ...2 Write a 10 to Modbus register 4151 Modbus Register Values Description 4151 0 255 Reset restore trigger This timer is based in 100 millisecond units Once written the timer starts to count down to zer...

Страница 38: ...ons 94 6 mm 3 72 85 mm 3 35 35 mm 1 38 59 5 mm 2 34 156 mm 6 14 All measurements are listed in millimeters inches unless noted otherwise DXM150 Sx Wireless Modbus Slave 38 www bannerengineering com Te...

Страница 39: ...Medium Range Omni Antennas BWA 9O5 C Antenna Rubber Swivel 900 MHz 5 dBi RP SMA Male Connector BWA 2O5 C Antenna Rubber Swivel 2 4 GHz 5 dBi RP SMA Male Connector Long Range Omni Antennas BWA 9O8 AS...

Страница 40: ...best operation for the DXM Modbus Slave stay connected with Banner Engineering Corp to hear about the latest updates through the Banner website Create a login today to stay informed of all Banner pro...

Страница 41: ...one 90 216 688 8282 Website www bannerengineering com Email turkey bannerengineering com tr India Address Banner Engineering India Pune Head Quarters Office No 1001 10th Floor Sai Capital Opp ICC Sena...

Страница 42: ...411 Website www bannerengineering com Email mail bannerengineering co jp Taiwan Address Banner Engineering Taiwan 8F 2 No 308 Section 1 Neihu Road Taipei 114 Taiwan Phone 886 0 2 8751 9966 Website www...

Страница 43: ...or liability for misuse abuse or the improper application or installation of the Banner product THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED INCLU...

Отзывы: