Device description
Power Panel C50 User's manual V1.10
35
4.8.3 POWERLINK interface (IF1)
Figure
Pinout
Terminal
Ethernet
1
RXD
Receive data
2
RXD\
Receive data\
3
TXD
Transmit data
4
Termination
5
Termination
6
TXD\
Transmit data\
7
Termination
8
Termination
Diagnostic LEDs
(POWERLINK mode)
LED
Color
Status
Description
Link/Activity
On
Link established to a POWERLINK network.
Blinking
Link established to a POWERLINK network
and POWERLINK activity taking place on the
bus.
LNK/ACT
Green
Off
No link established to a POWERLINK network.
Transfer rate
SPEED
Green Off
Not used.
Diagnostic LEDs
(Ethernet mode)
LED
Color
Status
Description
Link/Activity
On
Link established to an Ethernet network.
Blinking
Link established to an Ethernet network and
Ethernet activity taking place on the bus.
LNK/ACT
Green
Off
No link established to an Ethernet network.
Transfer rate
8
1
Front (touch screen)
LNK/ACT
SPEED
Back
SPEED
Green Off
Not used.
Information:
For all POWERLINK and Ethernet connections, only connections within a building are permitted, taking
into account maximum lengths.
POWERLINK V2 mode
By default, the POWERLINK interface is operated as a managing node (MN). In the managing node, the node
number is set to a fixed value of 240.
If the POWERLINK node is operated as a controlled node (CN), a node number from 1 to 239 can be set in the
POWERLINK configuration in Automation Studio.
Ethernet mode
In this mode, the interface is operated as an Ethernet interface. The INA2000 station number is set using the B&R
Automation Studio software.
Information:
If interface IF1 is operated in Ethernet mode, then this interface receives its own IP address and works
independently of Ethernet interface IF2.
Содержание Power Panel C50
Страница 2: ...1557771373112 1 10 2020 05 07...
Страница 75: ...Publishing information Power Panel C50 User s manual V1 10 75...