Installation
14
V 1.20
3.2.2 ACOPOSinverter X64
Terminal
Function
Electrical characteristics
R2A
R2C
NO contact of programmable relay r2
•
Minimum switching capacity: 10 mA at 5 V (DC power)
•
Max. switching capacity at resistive load (cos ϕ = 1 and L/R = 0 ms): 2 A at 250 V (AC
power) and 30 V (DC power)
•
Max. switching capacity at inductive load (cos ϕ = 0.4 and L/R = 7 ms): 1.5 A at 250 V
(AC power) and 30 V (DC power)
•
Sampling time: 8 ms
•
Service life: 100,000 switching operations at maximum switching capacity
+24 V
Power supply for X2X interface
MANDATORY
•
24 VDC (min. 18 V, max. 30 V)
•
Power: 1.6 W at 24 VDC
GND
Common
GND for 24 VDC power supply
DO1
Digital output
•
Switching voltage: 18 to 30 VDC
•
Diagnostic status: Output monitoring with 100 μs delay
•
Leakage current when the power is switched off: 3 μA
•
Residual voltage: <0.3 V at 0.5 A nominal current
•
Short-circuit peak current: <35 A
•
Switch-on after overload or short-circuit shutdown: <20 μs
•
Switching delay:
–
0 → 1: <100 μs
–
1 → 0: <300 μs
•
Switching frequency at resistive load: Max. 100 Hz
•
Output circuit: Source
X2X data point
LI1
LI2
Logic inputs
•
Power supply 24 V (max. 30 V)
•
Impedance: 12.1 kΩ
•
State 0 if <5 V, state 1 if >15 V (voltage difference between LI- and CLI)
•
Sampling time: 4 ms
Ground terminal
Recommended wire cross section 1.5 mm² (16 AWG).
The ground terminal must be connected to the EMC plate.