Programming guidelines
284
ACOPOSinverter P84 User's Manual 2.10
2.8.11.34 Evacuation function
The evacuation function is for elevator applications. It is only available for inverters 8I84T400075.01P-1 to
8I84T407500.01P-1.
If a lift is stuck between 2 floors due to a power failure, it must be possible to evacuate its occupants within a
reasonable period of time.
For this function, a back-up power supply must be connected to the inverter.
This power supply is provided with a lower voltage and allows the operating only outside the nominal values at
reduced speed, but with full torque.
The function requires:
•
A logic input to control the evacuation function
•
A reduction of the monitoring threshold for voltage
•
A suitable reference value for the low speed
After a power failure, the inverter can be restarted without switching into the fault mode
[UNDERVOLT. FAULT]
(USF)
if the logic input is at 1 at the same time.
Caution!
•
This input is not permitted to be at 1 if the inverter is connected to the power network. To
guarantee this and to avoid short circuits, changeover contactors must be used.
•
Set this input to 0 before connecting the emergency power supply.
Failure to observe these instructions can result in damage to property.
[EMERGENCY POWER SUPPLY] (rFt-)
Code
Name/Description
Setting range
Factory settings
rFt-
[EMERGENCY POWER SUPPLY]
Function is only available for the inverters 8I84T400075.01P-1 to 8I84T407500.01P-1.
rFt
[Emergency power supply]
[No]
(nO)
nO
[No]
(nO)
: Function not assigned
LI1
[LI1]
(LI1)
to
[LI6]
(LI6)
-
The emergency power supply is blocked in state 1 of the input or of the associated bit.
LI6
The emergency power supply is triggered in state 0 of the input or of the associated bit.
rSU
[Emergency power supply volt.]
220 to 230 V
220 V
Permissible minimum value of the AC voltage of the emergency power supply.
The parameter is accessible if
[emergency power supply]
(rFt)
is not equal to
[No]
(nO)
.
8I84T4*****.01P-1: Range from 220 to 320 V, Factory setting 220 V.
rSP
[Emergency power supply freq.]
5 Hz
Frequency reference of the mode "Emergency power supply"
The parameter is accessible if
[emergency power supply]
(rFt)
is not equal to
[No]
(nO)
.
The adjustment range is determined by the parameters
[low frequency]
(LSP)
,
[rated motor frequency.]
(FrS)
and, as described above,
[Mot. rated voltage]
(UnS)
and
[Emergency power supply volt.]
(rSU)
.
•
If
LSP
< (
Frs
x
rSU
/
UnS
):
rSP
min. =
LSP
,
rSP
max. = (
Frs
x
rSU
/
UnS
)
•
If
LSP
≥ (
Frs
x
rSU
/
UnS
):
rSP
= (
Frs
x
rSU
/
UnS
)
Parameter that can be modified during operation or when stopped.
Содержание ACOPOSinverter P84
Страница 2: ......
Страница 384: ...Accessories 384 ACOPOSinverter P84 User s Manual 2 10 8I0FT180 300 1 A Nm lb in 8I0FT180 300 1 25 221 3...
Страница 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Страница 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Страница 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Страница 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Страница 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Страница 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...