Commissioning • Installation
48
Power Panel T30 User's manual V1.42 - Translation of the original documentation
Grounding in the control cabinet
Control cabinet
Grounding rail
Ground connection
≥4 mm²
Figure: Grounding in the control cabinet
Important!
The ground connection of the device must be low impedance and connected to ground (e.g. grounding
rail in the control cabinet) using a short path.
Securing the conductor lines to the grounding plate
1
Ground conductor
The connection to ground potential must be as short as possible and sufficiently strong (≥4 mm²) over the
intended spade terminal (Faston 6.3 mm).
2
Unshielded lines
All unshielded lines must be relieved of tension by using a cable tie to tie them to the grounding plate.
Power Panel T30 - 4.3" variant
Power Panel T30 - 7.0" variant
1)
①
②
②
①
1 Ground conductor
2 Unshielded lines
1)
Note:
The image is valid for the 5.7" and 10.1" display variants.