Commissioning
42
Power Panel C50 User's manual V1.10
5.1.3 Installation instructions
The Power Panel must be installed using the retaining clips included in delivery.
In order to guarantee sufficient air circulation, allow the specified amount of space above, below, to the side and
behind the Power Panel. The minimum specified spacing is indicated in the following schematic diagrams. This
applies to all Power Panel variants.
>40 mm
>40 mm
Air outlet
>60 mm
>60 mm
>45 mm
Air intake
Information:
In worst-case operation, the specified spacing for air circulation applies at the maximum specified
ambient temperature (see "Temperature specifications" in chapter "Technical data") in compliance
with the permissible mounting orientations (see
"Mounting orientations" on page 43
).
If the specified spacing for air circulation cannot be observed, either a corresponding derating must
be taken into account (see
"Derating the ambient temperature" on page 18
) or the internal housing
temperature must be monitored by the user (see
"Temperature monitoring" on page 57
).