4.31.5.8.5.1 Preparation interval
Name:
PreparationInterval01 to PreparationInterval02
This register defines the time interval in which the measured value is checked before being passed on.
Data type
Value
UINT
0 to 65535 (x 0.1 ms)
Information:
This register must be defined if the replacement value strategy "Retain last valid value" was selected
4.31.5.8.5.2 Static replacement value for upper limit
Name:
ReplaceUpper01 to ReplaceUpper02
This register is used to defined a replacement value that is output in place of the invalid measured value if the
upper limit is violated.
Data type
Value
DINT
-2147483648 to 2147483647
Information:
This register must be defined if the replacement value strategy "Replace with static value" was selected
4.31.5.8.5.3 Static replacement value for lower limit
Name:
ReplaceLower01 to ReplaceLower02
This register is used to defined a replacement value that is output in place of the invalid measured value if the
lower limit is violated.
Data type
Value
DINT
-2,147,483,648 to 2,147,483,647
Information:
This register must be defined if the replacement value strategy "Replace with static value" was selected
4.31.5.8.6 Configuring the user-defined limit values
This module provides the user the option to specify user-defined limits. If the valid measurement range is reduced
in this way, the behavior of the replacement value strategy is more likely to be applied.
Valid measurement range
The valid range is derived from the properties of the sensor being used or the hardware and firmware of the
respective B&R module. These values cannot be changed by the user.
Valid range of values
The range of values is always within the valid measurement range. The range of values can be adapted to the
requirements of the application by specifying the upper and lower limit value.
4.31.5.8.6.1 Upper limit value
Name:
UpperLimit01 to UpperLimit02
This register specifies the upper limit value. The values entered should be within the valid measurement range.
Data type
Value
DINT
-2,147,483,648 to 2,147,483,647