4.26.3.10.5.3 Configuring the input filter
Name:
ConfigOutput03
This register is used to define the filter level and input ramp limitation of the input filter.
Data type
Value
USINT
See bit structure.
Bit structure:
Bit
Description
Value
Information
000
Filter switched off
001
Filter level 2
010
Filter level 4
011
Filter level 8
100
Filter level 16
101
Filter level 32
110
Filter level 64
0 - 2
Defines the filter level
111
Filter level 128
3
Reserved
0
000
The input value is used without limitation
001
Limit value = 0x3FFF (16383)
010
Limit value = 0x1FFF (8191)
011
Limit value = 0x0FFF (4095)
100
Limit value = 0x07FF (2047)
101
Limit value = 0x03FF (1023)
110
Limit value = 0x01FF (511)
4 - 6
Defines the input ramp limitation
111
Limit value = 0x00FF (255)
7
Reserved
0
4.26.3.10.5.4 Lower limit for the analog value
Name:
ConfigOutput05
This register can be used to configure the lower limit for analog values. If the analog value goes below the limit
value, it is frozen at this value and the corresponding error status bit is set.
Information:
•
The default value of -32768 corresponds to the minimum default value of -10 VDC.
•
For current measurements, this value should be set to 0.
•
When configured as 4 to 20 mA, this value can be set to -8192 (corresponds to 0 mA) in order
to display values <4 mA.
Data type
Value
INT
-32,768 to 32,767
4.26.3.10.5.5 Upper limit for the analog value
Name:
ConfigOutput06
This register can be used to configure the upper limit for analog values. If the analog value goes above the limit
value, it is frozen at this value and the corresponding error status bit is set.
Information:
•
The default value of 32767 corresponds to the maximum default value of 20 mA or +10 VDC.
Data type
Value
INT
-32,768 to 32,767