1TT –TIMER + TERMOREGOLATORE - Reference Manual - Pag. 3 di 7
Manual modes (pulse generator)
The instrument has two
manual
modes that exclude the control algorithms and run the control elements at constant
power:
•
Manual mode always on (also with temperature probe);
•
Manual mode only when there is an error with the temperature probe.
Select manual mode (always on) by selecting the parameter
MAN
=
1
(the
MPE
parameter is ignored).
To select manual mode only when there is an error with the temperature probe by selecting the parameter
MAN = 0
and
MPE = 1
.
In both cases the percentage of activation control output is set via the OUT parameter (percentage of the cycle time
normally used).
Table (summary):
MAN
MPE
Manual mode always on
1
Manual mode in case of error of probe
0
1
Versions with front display