• A power line filter installed at the AC input to the OIT power supply is highly

recommended as a safeguard against conducted RF noise, which is often present

on factory power lines. The wires connecting the output of the power line filter

to the power supply should be kept as short as possible to minimize any

additional noise pickup. The case of the power line filter should be connected to

a quiet earth ground. The power line filter should have a current rating of at least

three amps with common mode and differential mode attenuation.

• The power supply that provides power to the OIT should not be used to power

switching relays or solenoids unless noise filter caps are connected to each relay.

1.3. OIT Cable Routing

• Always route the OIT operating cable away from any AC voltage or host

controller wires.

• Never bundle the OIT cables together with 120 VAC power wires or with relay

wiring.

• Try to keep at least 8 inches (20 cm) of separation between the OIT cables and

other power wiring. If voltages greater than 120 VAC are used in the system,

greater separation is required.

• If the OIT cables must come near AC wiring, make sure they cross at 90 degrees.
• Running AC power wires in a separate grounded conduit is the preferred method

for electrical noise reduction.

• Keep the lengths of the OIT cables as short as possible. Do not coil excess cable

and place it next to AC powered equipment.

1.4. Other Steps to Improve Noise Immunity

• Always install the OIT’s rear cover. This provides a shield against electrical

noise which can be generated in the control panel by relays, motors, power lines,

and/or high frequency equipment. Ensure that all rear cover mounting screws

are properly secured.

• Any equipment used in the enclosure that operates at high frequency or high

current levels can be covered with a grounded metal shield.

6

MAP450D

1010-0046A, REV 00

AC

AC

GND

N

L

WHITE

BLACK

N

L

G

AC

LINE FILTER

GREEN

WHITE TO

110VAC NEUTRAL

BLACK TO

110VAC LOAD(HOT)

TO EARTH

"QUIET" GROUND

POWER SUPPLY

GROUND

KEEP SHORT

Figure 2 Power Line Filter Connection

Содержание MAP450D

Страница 1: ...C D F E P N V W INSTALLATION MANUAL 1010 0046A REV 00 Secure online ordering 24 7 365 from European Headquarters Westlink Commercial Park Oranmore Co Galway Ireland www bb europe com Phone 353 91 7924...

Страница 2: ...ense is granted by implication or otherwise under any patent or patent rights of Maple Systems Inc Maple Systems retains the right to revise or change its products and documentation at any time withou...

Страница 3: ...circuitry inside is exposed to possible damage by electrostatic discharge during handling Minimize the possibility of electrostatic discharge by Discharging personal static by grounding yourself prio...

Страница 4: ...to a Host Controller 7 2 1 RS 232 Interactive Block modes 9 2 2 RS 422 485 Interactive Block modes 9 2 3 RS 422 485 Network mode 10 2 4 Set Jumper for 3 Wire RS 422 485 13 3 Mounting the MAP450D 14 3...

Страница 5: ...e braid should be installed from the hinged control panel to the rest of the enclosure 1 2 Power Supply Selection The power supply used to power the OIT should have an output between 12 and 30 VDC The...

Страница 6: ...hes 20 cm of separation between the OIT cables and other power wiring If voltages greater than 120 VAC are used in the system greater separation is required IftheOITcablesmust come nearAC wiring make...

Страница 7: ...k tubing from the end of the OIT operating cable 4 Slide the ferrite coil over the OIT operating cable This usually requires rotating the ferrite coil back and forth while simultaneously pulling on th...

Страница 8: ...nst the inside wall of the OIT enclosure with the protruding OIT operating cable kept short 9 Tighten the cable strain relief nut 10 Re install the four screws into the back of the OIT enclosure 11 Ro...

Страница 9: ...configuration has both transmit and receive on the same pair of wires plus a signal common The 5 wire configuration has differential signal pairs for transmit and receive plus a signal common In both...

Страница 10: ...t the same time 3 wire RS 422 485 only supports half duplex communications which means that the host controller cannot transmit and receive data at the same time Although 3 wire RS 422 485 installatio...

Страница 11: ...e in this mode Therefore each command sent from the host controller should end with the appropriate line terminator If the host controller sends a command that requires a response from the OIT the hos...

Страница 12: ...Network Grounding To communicate properly serious attention must be paid to the grounding scheme of the devices connected to the com link Improper grounding improper termination and faulty shielding o...

Страница 13: ...entials and currents Connecting the signal ground to chassis or earth ground can damage the devices connected to the com link 2 4 Set Jumper for 3 Wire RS 422 485 This step is required only if the OIT...

Страница 14: ...utout required for proper panel installation The panel cutout should be cleaned and deburred before the OIT is installed 14 MAP450D 1010 0046A REV 00 The OIT is mounted using four 6 32UNC screws sandw...

Страница 15: ...to a mounting plate using the four pre tapped holes in the rear cover The OIT enclosure and cable strain relief provide the environmental seal to NEMA 4 and NEMA 12 standards Figure 11 shows the minim...

Страница 16: ...r cover has two legs set at a five degree angle to give the display and keypad a sloped front while sitting on a bench Four rubber feet are attached to the legs to prevent slippage as well as damage t...

Страница 17: ...e 4 1 Connecting the MAP450D to a PC First remove the operating cable from the terminal block pins Next connect an RS 232 serial communications cable Maple Systems P N 7431 0048 to the proper COM port...

Страница 18: ...y industrial environment Power Requirements Input Voltage 12 to 30 VDC Power Usage 2 5 watts typical Display Display Type MAP450D 003 Liquid Crystal Display LCD 5 x 7 dot matrix with cursor Display Ty...

Страница 19: ...0 127 0 90 23 depth behind the front of a panel 8 12 206 6 32UNC x 0 50 12 7 screw 4 places SS 6 32UNC x 0 30 7 6 deep threads for Pedestal Mounting only REAR VIEW FRONT VIEW SIDE VIEW Free Standing P...

Страница 20: ...mmunity and emissions 5 Local setup mode is entered by pressing and holding the Clear key instead of the S key while the Initializing prompt is on the display Local setup mode can also be entered afte...

Отзывы: