There are several different forms of communications networks. Maple Systems’

OITs utilize the multidrop format. The host controller, located at one of the network

ends, is connected to the OITs via a continuous com-link. Each OIT is connected to

the network by locally tapping into the com-link with short stub cables. The end of

the com-link must be properly terminated to reduce noise pickup and interference.

The total length of the com-link, from the host controller to the network cable

terminator, can be up to 4,000 feet.

If you decide to use 3-wire RS-422/485, the following limitations apply:

• The host controller must disable or tri-state its RS-485 transmitter when it is not

sending data to the OITs on the network. To simplify programming, the host

should disable or tri-state its RS-485 receiver whenever transmitting.

• The ability to stay logged on to a particular OIT by sending the command terminator

instead of the line terminator is not available in this mode. Therefore, each command

sent from the host controller should end with the appropriate line terminator.

• If the host controller sends a command that requires a response from the OIT, the

host controller must wait for a response from the OIT before sending another

command. Otherwise, a situation can occur in which the OIT and the host

controller attempt to transmit at the same time cuasing unpredictable results.

• The ASCII strings sent by the OIT’s function keys should not include any

control characters which the other OITs on the network could misinterpret, such

as the line terminator or command terminator.

INSTALLATION MANUAL

11

1010-0046A, REV 00

HOST

Less than

4000'

TO OIT

Less than 12"

Shielded Cable

OIT #1

OIT #100

TERMINA

TOR

TERMINA

TOR

To More

OITs

OIT #2

From Host or

Previous OIT

See

Detail A & B

Detail B

5 Wire Termination

Detail A

5 Wire Termination

To More

OITs

From Host or

Previous OIT

CHASSI

S

GND

RXD+/

TXD+

RXD-

/T

XD-

SI

G

GND

SI

G

GND

CHASSI

S

GND

RXD-

SI

G

GND

TXD+

TXD-

TO OIT

CHASSI

S

GND

TXD+

TXD-

RXD+

RXD-

SI

G

GND

SI

G

GND

RXD+

Drain

Wires

2 Pair Twisted

Shielded Cable

24 Gage Wire

3 Pair Twisted

Shielded Cable

24 Gage Wire

Drain

Wires

Содержание MAP450D

Страница 1: ...C D F E P N V W INSTALLATION MANUAL 1010 0046A REV 00 Secure online ordering 24 7 365 from European Headquarters Westlink Commercial Park Oranmore Co Galway Ireland www bb europe com Phone 353 91 7924...

Страница 2: ...ense is granted by implication or otherwise under any patent or patent rights of Maple Systems Inc Maple Systems retains the right to revise or change its products and documentation at any time withou...

Страница 3: ...circuitry inside is exposed to possible damage by electrostatic discharge during handling Minimize the possibility of electrostatic discharge by Discharging personal static by grounding yourself prio...

Страница 4: ...to a Host Controller 7 2 1 RS 232 Interactive Block modes 9 2 2 RS 422 485 Interactive Block modes 9 2 3 RS 422 485 Network mode 10 2 4 Set Jumper for 3 Wire RS 422 485 13 3 Mounting the MAP450D 14 3...

Страница 5: ...e braid should be installed from the hinged control panel to the rest of the enclosure 1 2 Power Supply Selection The power supply used to power the OIT should have an output between 12 and 30 VDC The...

Страница 6: ...hes 20 cm of separation between the OIT cables and other power wiring If voltages greater than 120 VAC are used in the system greater separation is required IftheOITcablesmust come nearAC wiring make...

Страница 7: ...k tubing from the end of the OIT operating cable 4 Slide the ferrite coil over the OIT operating cable This usually requires rotating the ferrite coil back and forth while simultaneously pulling on th...

Страница 8: ...nst the inside wall of the OIT enclosure with the protruding OIT operating cable kept short 9 Tighten the cable strain relief nut 10 Re install the four screws into the back of the OIT enclosure 11 Ro...

Страница 9: ...configuration has both transmit and receive on the same pair of wires plus a signal common The 5 wire configuration has differential signal pairs for transmit and receive plus a signal common In both...

Страница 10: ...t the same time 3 wire RS 422 485 only supports half duplex communications which means that the host controller cannot transmit and receive data at the same time Although 3 wire RS 422 485 installatio...

Страница 11: ...e in this mode Therefore each command sent from the host controller should end with the appropriate line terminator If the host controller sends a command that requires a response from the OIT the hos...

Страница 12: ...Network Grounding To communicate properly serious attention must be paid to the grounding scheme of the devices connected to the com link Improper grounding improper termination and faulty shielding o...

Страница 13: ...entials and currents Connecting the signal ground to chassis or earth ground can damage the devices connected to the com link 2 4 Set Jumper for 3 Wire RS 422 485 This step is required only if the OIT...

Страница 14: ...utout required for proper panel installation The panel cutout should be cleaned and deburred before the OIT is installed 14 MAP450D 1010 0046A REV 00 The OIT is mounted using four 6 32UNC screws sandw...

Страница 15: ...to a mounting plate using the four pre tapped holes in the rear cover The OIT enclosure and cable strain relief provide the environmental seal to NEMA 4 and NEMA 12 standards Figure 11 shows the minim...

Страница 16: ...r cover has two legs set at a five degree angle to give the display and keypad a sloped front while sitting on a bench Four rubber feet are attached to the legs to prevent slippage as well as damage t...

Страница 17: ...e 4 1 Connecting the MAP450D to a PC First remove the operating cable from the terminal block pins Next connect an RS 232 serial communications cable Maple Systems P N 7431 0048 to the proper COM port...

Страница 18: ...y industrial environment Power Requirements Input Voltage 12 to 30 VDC Power Usage 2 5 watts typical Display Display Type MAP450D 003 Liquid Crystal Display LCD 5 x 7 dot matrix with cursor Display Ty...

Страница 19: ...0 127 0 90 23 depth behind the front of a panel 8 12 206 6 32UNC x 0 50 12 7 screw 4 places SS 6 32UNC x 0 30 7 6 deep threads for Pedestal Mounting only REAR VIEW FRONT VIEW SIDE VIEW Free Standing P...

Страница 20: ...mmunity and emissions 5 Local setup mode is entered by pressing and holding the Clear key instead of the S key while the Initializing prompt is on the display Local setup mode can also be entered afte...

Отзывы: