ENGLISH
6 / 54
0006081544_201907
TECHNICAL SPECIFICATIONS
MODEL
TBML 200 MC
TBML 260 MC
TBML 360 MC
Maximum natural gas thermal power
kW
2000
2600
3600
Minimum natural gas thermal power
kW
450
500
700
¹) natural gas emissions
mg/kWh
Class 2
Class 1
Class 2
Natural gas operation
Two-stage progressive /
modulating burner
Two-stage progressive /
modulating burner
Two-stage progressive /
modulating burner
Maximum natural gas thermal rate
Stm³/h
211,6
275
380,9
Minimum natural gas thermal rate
Stm³/h
47,6
52,9
74,1
Natural gas minimum pressure
hPa (mbar)
25,5
45
63
Natural gas maximum pressure
hPa (mbar)
360
360
360
Maximum propane thermal power
kW
1930
2600
3600
Minimum propane thermal power
kW
450
500
700
Maximum propane thermal rate
Stm³/h
78,9
106,4
147,3
Minimum propane thermal rate
Stm³/h
18,4
20,5
28,6
Propane minimum pressure
hPa (mbar)
20,9
45
80
Propane maximum pressure
hPa (mbar)
360
360
360
²) propane emissions
mg/kWh
Class 1
Class 2
Class 2
Maximum diesel fuel thermal rate
kg/h
168,6
219,2
303,5
Minimum diesel fuel thermal rate
kg/h
59
75,9
75,9
Maximum diesel fuel thermal power
kW
2000
2600
3600
Minimum diesel fuel thermal power
kW
700
900
1000
³) diesel emissions
mg/kWh
Class 2
Class 2
Class 2
Diesel viscosity
5.5 cst / 20°C - 1.5° E
/ 20° C
5.5 cst / 20°C - 1.5° E
/ 20°C
5.5 cst / 20°C - 1.5° E
/ 20°C
Diesel operation
Two-stage
Two-stage
Two-stage
50hz fan motor
kW
3
5,5
7
60hz fan motor
kW
3,5
7,5
9
50 hz ignition transformer
26 kV - 48 mA - 230V
26 kV - 48 mA - 230V
26 kV - 48 mA - 230V
60 hz ignition transformer
26 kV - 48mA - 230 V
26 kV - 48mA - 230 V
26 kV - 48mA - 230 V
50hz voltage
3N ~ 400 V ± 10%
3N ~ 400 V ± 10%
3N ~ 400 V ± 10%
60hz voltage
3N ~ 380 V ± 10%
3N ~ 380 V ± 10%
3N ~ 380 V ± 10%
50hz electrical power*
kW
3.4
6.5
8
60hz electrical power*
kW
3,9
8,7
10
Protection rating
IP 40
IP 40
IP 40
Control box
LME 73...
LME 73...
LME 73...
Flame detection
UV photocell
UV photocell
UV photocell
operating ambient air temperature
°C
-15 ÷ +40
-15 ÷ +40
-15 ÷ +40
Sound pressure**
dBA
86
87
88
Sound power***
dBA
95
98
98
Weight with packaging
kg
108
115
170
Weight without packaging
kg
88
95
113
Propane / natural gas CO emissions ≤ 100 mg/kWh
Calorific power below reference conditions 15° C, 1013 hPa (mbar):
Natural gas: Hi = 9,45 kWh/Stm³ = 34,02 MJ/Stm³
Diesel fuel: Hi = 11.86 kWh/kg = 42.70 Mj/kg
Propane: Hi = 24,44 kWh/Stm³ = 88,00 MJ/Stm³
For different types of gases and pressure values, contact our sales departments.
Minimum gas pressure, depending on the type of gas train used for obtaining max. flow rate with null pressure in the combustion
chamber.
* Total absorption at start-up with ignition transformer on.
Содержание TBML 200 MC
Страница 2: ......
Страница 48: ...ITALIANO 46 54 0006081544_201907 SCHEMI ELETTRICI ...
Страница 49: ...ITALIANO 47 54 0006081544_201907 ...
Страница 50: ...ITALIANO 48 54 0006081544_201907 ...
Страница 52: ...ITALIANO 50 54 0006081544_201907 ...
Страница 53: ...ITALIANO 51 54 0006081544_201907 ...
Страница 54: ...ITALIANO 52 54 0006081544_201907 ...
Страница 56: ...ITALIANO 54 54 0006081544_201907 ...
Страница 102: ...ENGLISH 46 54 0006081544_201907 WIRING DIAGRAMS ...
Страница 103: ...ENGLISH 47 54 0006081544_201907 ...
Страница 104: ...ENGLISH 48 54 0006081544_201907 ...
Страница 106: ...ENGLISH 50 54 0006081544_201907 ...
Страница 107: ...ENGLISH 51 54 0006081544_201907 ...
Страница 108: ...ENGLISH 52 54 0006081544_201907 ...
Страница 110: ...ENGLISH 54 54 0006081544_201907 ...
Страница 111: ......