FLAME SENSOR
The flame detecting UV photocell must be able to trigger upon system
operation if the flame turns off (this check must be carried out after at
least one minute from the ignition).
The photocell current value required for a correct operation of the equi
-
pment is indicated in the wiring diagram.
Even the slightest greasiness will compromise the passage of rays
through the photocell bulb, thus preventing the sensitive internal ele
-
ment from receiving the quantity of radiation necessary for it to work
properly. If the bulb is fouled with diesel, fuel oil, etc... it must be pro
-
perly cleaned.
CAUTION / WARNINGS
Even simply touching the bulb with fingers may leave a slight
greasiness which could compromise photocell operation.
The UV photocell does not detect daylight or the light from a common
lamp.
Sensitivity can be checked with a flame (lighter) or with the electric
discharge between the electrodes of a common ignition transformer.
To ensure a proper operation, the UV photocell current value must be
sufficiently stable and not go below the minimum value required for the
equipment.
It may be necessary to tentatively find the best position by sliding (axial
or rotational movement) the casing that contains the photocell with re
-
spect to the fastening clamp.
This can be checked by connecting a micro-ammeter, with a suitable
scale, in series to one of the two UV photocell connection cables. Ob
-
viously the + and - polarity must be respected.
The burner should be capable of locking out and remain in that con
-
dition when, during the ignition sequence in the time pre-set by the
control box, the flame does not regularly appear.
The lock-out condition leads to an immediate fuel shut-off, the system
stops and the lock warning light comes on.
To check the photocell and lock-out efficiency, proceed as follows:
1 Start the burner
2 After at least one minute from ignition remove the UV photocell
from its seat, and simulate a flame failure. The burner flame must
turn off, the equipment will immediately shut down in "lock-out"
condition.
3 The equipment can only be reset manually by pressing the reset
button. The shut-down efficiency test must be performed at least
twice.
Check the efficiency of the thermostats or boiler pressure switches
(they should shut down the burner when triggered).
1
2 10
4
5
7
8
6
9
3
1)
Main switch ON - OFF
2)
Thermostatic line switch
3) Display
4)
Appliance shut-down indicator light
5)
Power LED
6)
Fan motor lock
7)
Gas operation light
8)
Liquid fuel operation indicator light
9)
Pump motor lock
10) Fuel switch (gas/liquid fuel)
18 / 46
0006160318_202106
ENGLISH
Содержание TBML 1200 ME
Страница 2: ......
Страница 36: ...SCHEMI ELETTRICI TBML 1200ME 1600ME 2000ME BT 335 34 46 0006160318_202106 ITALIANO...
Страница 37: ...TBML 1200ME 1600ME 2000ME BT 335 35 46 0006160318_202106 ITALIANO...
Страница 38: ...TBML 1200ME 1600ME 2000ME BT 335 36 46 0006160318_202106 ITALIANO...
Страница 39: ...TBML 1200ME 1600ME 2000ME BT 335 37 46 0006160318_202106 ITALIANO...
Страница 40: ...BA I1 I2 I3 I4 TBML 1200ME 1600ME 2000ME BT 335 38 46 0006160318_202106 ITALIANO...
Страница 42: ...SCHEMI ELETTRICI TBML 1200 1600 2000 ME 40 46 0006160318_202106 ITALIANO...
Страница 43: ...TBML 1200 1600 2000 ME 41 46 0006160318_202106 ITALIANO...
Страница 44: ...TBML 1200 1600 2000 ME 42 46 0006160318_202106 ITALIANO...
Страница 45: ...TBML 1200 1600 2000 ME 43 46 0006160318_202106 ITALIANO...
Страница 46: ...TBML 1200 1600 2000 ME I1 I2 I3 I4 BA 44 46 0006160318_202106 ITALIANO...
Страница 48: ...46 46 0006160318_202106 ITALIANO...
Страница 82: ...WIRING DIAGRAMS TBML 1200ME 1600ME 2000ME BT 335 34 46 0006160318_202106 ENGLISH...
Страница 83: ...TBML 1200ME 1600ME 2000ME BT 335 35 46 0006160318_202106 ENGLISH...
Страница 84: ...TBML 1200ME 1600ME 2000ME BT 335 36 46 0006160318_202106 ENGLISH...
Страница 85: ...TBML 1200ME 1600ME 2000ME BT 335 37 46 0006160318_202106 ENGLISH...
Страница 86: ...BA I1 I2 I3 I4 TBML 1200ME 1600ME 2000ME BT 335 38 46 0006160318_202106 ENGLISH...
Страница 88: ...WIRING DIAGRAMS TBML 1200 1600 2000 ME 40 46 0006160318_202106 ENGLISH...
Страница 89: ...TBML 1200 1600 2000 ME 41 46 0006160318_202106 ENGLISH...
Страница 90: ...TBML 1200 1600 2000 ME 42 46 0006160318_202106 ENGLISH...
Страница 91: ...TBML 1200 1600 2000 ME 43 46 0006160318_202106 ENGLISH...
Страница 92: ...TBML 1200 1600 2000 ME I1 I2 I3 I4 BA 44 46 0006160318_202106 ENGLISH...
Страница 94: ...46 46 0006160318_202106 ENGLISH...
Страница 95: ......