ELECTRICAL SUPPLY

•  The equipment is electrically safe only when it is correctly connected to an efficient ground connection carried out in accordance with current safety 

regulations. It is necessary to check this essential safety requirement. If in doubt, call for a careful electrical check by a qualified technicians, since 
the manufacturer will not be liable for any damage caused by a poor ground connection. 

•  Have qualified technicians check that the wiring is suitable for the maximum power absorption of the equipment, as indicated in the technical plate, 

making sure in particular that the diameter of cables is sufficient for the equipment’s power absorption. 

•  Adapters, multiple plugs and extension cables may not be used for the equipment’s power supply. 
•  An ominpolar switch in accordance with current safety regulations is required for the mains supply connection. 
•  The electrical supply to the burner must have neutral to ground connection. If the ionisation current has control with neutral not to ground it is essential 

to make a connection between terminal 2 (neutral) and the ground for the RC circuit. 

•  The use of any components that use electricity means that certain fundamental rules have to followed, including the following: 
  - do not touch the equipment with parts of the body that are wet or damp or with damp feet 
  - do not pull on electrical cables 
  - do not leave the equipment exposed to atmospheric agents (such as rain or sun etc.) unless there is express provision for this. 
  - do not allow the equipment to be used by children or inexpert persons. 
•  The power supply cable for the equipment not must be replaced by the user. If the cable gets damaged, switch off the equipment, and call only on 

qualified technicians for its replacement. 

•  If you decide not to use the equipment for a while it is advisable to switch off the electrical power supply to all components in the system that use 

electricity (pumps, burner, etc.).

GAS, LIGHT OIL, OR OTHER FUEL SUPPLIES 

General warning notes 
•  Installation of the burner must be carried out by qualified technicians and in compliance with current law and regulations, since incorrect installation 

may cause damage to person, animals or things, for which damage the manufacturer shall not can be held responsible. 

•  Before installation it is advisable to carry out careful internal cleaning of all tubing for the fuel feed system to remove any residues that could jeopardise 

the  proper working of the burner. 

•  For first start up of the equipment have qualified technicians carry out the following checks:
•  If you decide not to use the burner for a while, close the tap or taps that supply the fuel. 
Special warning notes when using gas 
•  Have qualified technicians check the following:
  a) that the feed line and the train comply with current law and regulations.
  b) that all the gas connections are properly sealed.
•  Do not use the gas pipes to ground electrical equipment. 
•  Do not leave the equipment on when it is not in use and always close the gas tap.
•  If the user of is away for some time, close the main gas feed tap to the burner.
•  If you smell gas:
  a) do not use any electrical switches, the telephone or any other object that could produce a spark;
  b) immediately open doors and windows to create a current of air that will purify the room;
  c) close the gas taps;
  d) ask for the help of qualified technicians. 

•  Do not block ventilation openings in the room where there is gas equipment or dangerous situations may arise with the build up of toxic and explosive 

mixtures.

FLUES FOR HIGH EFFICIENCY BOILERS AND SIMILAR 

It should be pointed out that high efficiency boilers and similar discharge  combustion products (fumes) at relatively low temperatures into the flue. In 
the above situation, traditional flues (in terms of their diameter and heat insulation) may be suitable because the significant cooling of the combustion 
products in these permits temperatures to fall even below the condensation point. In a flue that works with condensation there is soot at the point the 
exhaust reaches the atmosphere when burning light oil or heavy oil or the presence of condensate water along the flue itself when gas is being burnt 
(methane, LPG, etc.). Flues connected to high efficiency boilers and similar must therefore be of a size (section and heat insulation) for the specific use 
to avoid such problems as those described above.

WARNING NOTES FOR THE USER HOW TO USE THE BURNER SAFELY

Содержание TBL 45P

Страница 1: ...br l rler i in kullan m k lavuzu Instruction for burners model Instrucci nes para quemadores modelos Mode d emploi brule r TBL45P TBL60P 0006081349_200802 TR GB SP FR TBL45PDACA TBL60PDACA...

Страница 2: ......

Страница 3: ...e se corre el riesgo de que se produzcan accidentes peligrosos Avant de commencer utilise le br leur lire attentivement les recommandations de la notice RECOMMANDATIONS A L ATTENTION DE L UTILISATEUR...

Страница 4: ...n accordance with the European Standards EN 676 gas and dual fuel gas side EN 267 light oil and dual fuel oil side EN 60335 1 2001 A1 2004 A11 2004 A2 2006 EN 60335 2 102 2006 EN 50165 1997 A1 2001 EN...

Страница 5: ...or if the owner moves and leaves the equipment make sure that the booklet always goes with the equipment so it can be consulted by the new owner and or installer For all equipment with optionals or k...

Страница 6: ...rrent law and regulations since incorrect installation may cause damage to person animals or things for which damage the manufacturer shall not can be held responsible Before installation it is advisa...

Страница 7: ...CTION RATING IP 40 IP 44 versione DACA FLAME DETECTOR PHOTORESISTACE NOISE dBA 73 75 WEIGHT kg 38 40 Fuel max viscosity light oil 5 5 cst 20 C 1 5 E 20 C FLOW RATE MAX kg h 37 9 50 6 MIN kg h 13 5 21...

Страница 8: ...15 200 245 M12 145 TBL 60P 505 260 245 455 325 130 840 140 350 150 152 260 225 300 M12 160 TBL 60P DACA 535 260 275 455 325 130 880 140 350 150 152 260 225 300 M12 160 1 Combustion head 2 Gasket 3 Bur...

Страница 9: ...Un lock switch button N 0002935350 REV 26 11 07 N 0002935510 REV 07 02 08 13 Equipment 14 Ignition transformer 15 Motor contactor only for three phase power supply 16 Thermal relay only for three pha...

Страница 10: ...ipes For unavoidable joints we recommend the use of biconic fittings The annexed tables show the indicative diagrams for the different types of systems depending on the position of the tank in respect...

Страница 11: ...One way valve 10 Bottom valve SUCTION TYPE FEEDING SYSTEM N B For any missing devices in the piping follow existing regulations H Difference in level between level in the tank and the pump axis L Max...

Страница 12: ...ion pipes should be sized to cope with the delivery rate of the auxiliary pump Always avoid to electrically connect the auxiliary pump directly to the remote control switch of the burner motor HYDRAUL...

Страница 13: ...y insert the two 7 and 4 pole plugs in the sockets located below the electrical panel base as shown in figure 1 2 In the case of models with three phase power supply unscrew the 2 screws 1 and pull ba...

Страница 14: ...e see figure 2 In the case of a three phase burner connect the power supply cables 4 to the contactor fix the ground cable 5 and tighten its cable holder 3 Reposition the cable float plate as in figur...

Страница 15: ...ned by the position in which the the hydraulic control jack is set see 0002935420 If the air adjustment servo motor is used see 0002935210 If the flame appears normally with the safety time set by the...

Страница 16: ...ure that a Feedinglineconnectionstothermostatsorpressureswitchesare made exactly according to electric diagram of the control box b Check if there is fuel in the tank and water in the boiler c All the...

Страница 17: ...emove the photo cell from its seat and pull it out and simulate flame failure by covering the photo cell use a rag to close the window in the photocell support The burner flame should go to lock out c...

Страница 18: ...the air damper that regulates the aspiration flow from the burner fan This must of course be the case when the burner is working at maximum desired supply In practice you have to start the adjustment...

Страница 19: ...ll burner and remove pawl 5 with screw 6 that regulates the position of the mixer assembly figure 2 Important Before carrying out the above procedure store in memory the exact position of the mobile p...

Страница 20: ...air damper G Air intake H Support eyelet Adjustment of 1st flame air damper position 1 To increase air supply capacity turn ring nut C1 anticlockwise use counter wrench on body A of the jack to preve...

Страница 21: ...sition indicator To modify the regulation of the cams utilized operate the respective rings I II III The index of the ring indicate on the respective reference scale the rotation angle taken up for ea...

Страница 22: ...16 52 3 00 3 50 11 13 11 90 12 62 13 30 13 95 14 57 15 17 15 74 16 29 16 83 17 34 17 85 18 34 18 81 19 28 3 50 4 00 12 72 13 60 14 42 15 20 15 94 16 65 17 33 17 99 18 62 19 23 19 82 20 40 20 95 21 50...

Страница 23: ...low 1 Pipe diameter too small 2 Air infiltration in the pipes 3 Dirty filter 4 Excessive distance between the tank and the burner or a lot of accidental leakage s elbows curves choking etc 5 Deteriora...

Страница 24: ...el 3 Smoke temperature too low below 180 C 1 Excessive cooling below 180 C of smoke before exit outflow for an outside chimney not adequately heat insulated or cold air infiltration REMEDY 1 Re set it...

Страница 25: ...2 STAGE THERMOSTAT I THERMOSTAT 2 STUFE I TERMOSTATO 2 ETAPA TA ATE LEME TRANSFORMAT R TRASFORMATEUR D ALLUMAGE IGNITION TRASFORMER ZUNDUNGSTRASFORMATOR TRANSFORMADOR TC KAZAN TERMOSTATI THERMOSTAT CH...

Страница 26: ...SET PUSH BUTTON ENTSPERRKNOPF PULSADOR DE DESBLOQUEO SG ANAANAHTAR INTERRUTTORE GENERAL GENERAL SWITCH ALLGEMEINER SCHALTER INTERRUPTOR GENERAL T2 TERMOSTAT 2 A AMA THERMOSTAT 2 ETAGE 2ND STAGE THERMO...

Страница 27: ...OR DE DESBLOQUEO T2 TERMOSTAT 2 A AMA I THERMOSTAT 2 ETAGE 12 STAGE THERMOSTAT I THERMOSTAT 2 STUFE I TERMOSTATO 2 ETAPATA ATE LEME TRANSFORMAT R TRASFORMATEUR D ALLUMAGE IGNITION TRASFORMER ZUNDUNGST...

Страница 28: ...LTER INTERRUPTOR ENC APAG S2 D ME A IK BOUTON DE DEBLOCAGE RE SET PUSH BUTTON ENTSPERRKNOPF PULSADOR DE DESBLOQUEO SG ANAANAHTAR INTERRUTTORE GENERAL GENERAL SWITCH ALLGEMEINER SCHALTER INTERRUPTOR GE...

Страница 29: ...a por lo tanto se reserva cualquier posibilitad de modificati n de datos t cnicos y otras anotaciones Ce manuel rev t caract re purement indicatif La maison se reserve la possibilit de modifier des do...

Отзывы: