AIR REGULATION ON THE COMBUSTION HEAD
The combustion head has a regulation device that allows the air
passage between the disc and the combustion head to be opened or
closed. Closing the passage, you can obtain high pressure upstream
of the disc even at low flow rate. The high speed and turbulence of
the air provides for its greater penetration into the fuel and therefore
an excellent mixture and flame stability. High air pressure upstream
of the disc may be necessary to prevent flame fluctuations, this is
particularly essential when the burner works on the combustion
chamber that is pressurised and/or at a high thermal load.
CAUTION / WARNING
Check that the combustion head is centred with respect to the
disk. An imperfect centring could cause a poor combustion and
overheating of the head with its subsequent rapid deterioration.
CAUTION / WARNING
The above adjustments are indicative only; position the
combustion head according to the characteristics of the
combustion chamber.
Model
X
Index value (4)
TBG 85 MC
5 ÷ 36
1 ÷ 4,5
TBG 120 MC
17 ÷ 54
1 ÷ 5
TBG 150 MC
17 ÷ 36
1 ÷ 3,2
TBG 210 MC
14 ÷ 51
1 ÷ 5
TBG 260 MC
14 ÷ 51
1 ÷ 5
TBG 360 MC
12 ÷ 49
1 ÷ 5
• Loosen the screw (1)
• Turn screw (2) to position the combustion head (3), referring to
index (4)
• Adjust the distance (x) between the minimum and maximum
according to the indications in the table
STARTING UP AND REGULATION
• Check that thee voltage on the mains meets the manufacturer
requirements and that all electrical connections made at the
installation site are performed properly as illustrated in our wiring
diagram.
• Check that the discharge of combustion products through the boiler
gate and flue gate take places freely.
• Check that there is water in the boiler and that the gate valves of
the system are open.
Check that all gate valves fitted on the fuel piping are open as well as
any other shut-off component.
INSTRUCTIONS FOR MANUAL BURNER OPERATION.
Combustion may be checked throughout the entire burner operating
range by controlling the equipment manually.
After disconnecting the boiler connector -3 that brings the signals
from the thermostat line, insert the connector -4 provided with the
burner back in its place.
Use the +/- button to increase or decrease the gas and air flow rate.
After completing the check, reconnect the boiler connector -3 to
restore automatic operation.