IONIZATION PROBE/ELECTRODE ADJUSTMENT DIAGRAM
No. 0002935021
Legend:
1- Ionisation electrode
2- Ignition electrode
3- Flame disk
4- Mixer
5- Gas delivery pipe
IONISATION CURRENT MEASUREMENT
To measure the ionisation current, remove the jumper between
terminals 30-31 on the printed circuit with the burner off (see
diagram). Connect to the terminals a microammeter having a
suitable scale to have the burner restart. Once the flame has
appeared it will be possible to measure the ionisation current, the
minimum value of which ensuring the operation of the equipment
is shown in the specific wiring diagram. At the end of the
measurement, connect the jumper that has been disconnected.