19
FEED PLANT
PUMP AS 47
N°0002900530
Rev. 20/02/97
H
METERS
Total lenght
l. meters
Ø i. 10 mm
Ø i. 12 mm
0,5
27
51
1
23
43
1,5
19
35
2
15
27
2,5
10
20
3
7
13
3,5
--
6
H
= Measurement between minimum
oil level and pump axis
L
= Max. legth of suction line, including
vertical lifts
For each bend of valve deduct
0,25 m.
N.B. For any missing devices in the
pipping, conform to existing regulations.
Max. pressure on suction and return = 1,5 bar
H
METERS
Total lenght
l. meters
Ø i. 10 mm
1
30
2
35
3
40
4
45
Max. pressure on suction and return = 1,5 bar
Quote P = 3,5 m (max)
H
METERS
Total lenght
l. meters
Ø i. 10 mm
1
30
2
35
3
40
4
45
1
Oil tank
6
Suction line
2
Feed line
7
Return line
3
Filter
8
Fire valve
4
Burner
9
Non return valve
5
Degasifier
GRAVITY FEED FROM THE BOTTOM OF OIL TANK
1
Oil tank
6
Suction line
3
Filter
7
Return line
4
Burner
10
Foot valve
SUCTION FEED
1
Oil tank
7
Return line
3
Filter
8
Fire valve
4
Burner
9
Non return valve
6
Suction line
10
Foot valve
GRAVITY FEED OVER THE TOP OF OIL TANK
Содержание SPARK 18W
Страница 9: ...9 N 0002921495 Rev 13 09 02 CAMPO DI LAVORO WORKING FIELD RANGO DE TRABAJO...