32 / 34
0006080766
1) Press
▲
key and the
flashing figure will change, press key
again until obtaining
3
. Press
◄ to confirm the flashing
3
that
becomes fixed. It is now possible to edit the figure further to
the left that begins to flash. Press ▲
key in order to change
the figure now flashing to 3 and then ◄ in order to confirm this
value and move to the figure further to the left. This operation
must be repeated until obtaining the
number
3
four times
=
3333
. Press
►
key to confirm the
PASS
word. We are now
in a position to configure or reconfigure the controller.
For one electric preheater you need to set n°
1045
.
For two or more preheaters you need to set n°
1046
.
2) At this point go through the procedure illustrated in point 1 to
set n°
1045
or n°
1046
.
3) We can now set parameters (control values) as detailed in the
previous table.
4) Press
F
key, repeatedly if necessary, until the wording
SP
appears. Press
► key and the figure furthest to the right will
start to flash. Next proceed as per point 1 in order to enter the
required value (130 °C). Having set the desired temperature,
press
► to confirm and the temperature setting will appear at
the bottom of the display.
5) It is now necessary to set value
SP.2
. Press
F
key repeatedly
until wording
Par
appears. Press
► key to confirm and the
wording
SP.2
will appear. Proceed as per point 1 in order to
set value given in the table for
SP.2 =
110 °C.
6) Press
F
key and the wording Pb will appear. Proceed as per
point 1 in order to set table value = 6. Press ► to confirm
this value and the wording t.i will appear.
7) Proceed as previously described in order to set value t.i = 4 as
per table. Press ► to confirm this value and move to t.d.
8) Proceed as previously described in order to set value t.d. = 0.8
as per table. Press ► to confirm this value and move to t.c.
9) Proceed as previously described in order to set value t.c. = 10
as per table. Press ► to confirm this value and move to Yh.
10) Proceed as previously described in order to set value Yh = 100
as per table. Confirm this value by pressing ► and the display
will return to Pb.
11) Press F key in order to move to Hy2. Proceed as per point 1
and set value Hy2 = 1. Press ► key to confirm and remain at
Hy2.
12) Press F key in order to move to SPL 1. Proceed as before and
set SPL 1 = 100 °C. Press ► to confirm and move to SPL h.
Set SPL h = 250 °C in the usual manner. Press ► to confirm
and move to SLOP.
13) Proceed as before in order to set SLOP = 0 and confirm with
► key. The controller is now configured and capable of fun
-
ctioning using set values. Should it be necessary to modify
any temperature setting, proceed as previously described at
specific points 4 for SP and 5 for SP2.
!
The controller is supplied with the instructions given by the ma-
nufacturer ASCON that contain the respective “flow diagram”.
14) Proceed as follows if wishing to check the default configuration
set by us (1045 or 1046):
Press
F
key repeatedly until the wording ConF appears.
Press ► key once and the configuration set will appear (1045
or 1046 - Conf.). From this position, if wishing to alter the
configuration press ► once and the wording 9999 - PASS
will appear (9 furthest to the right flashing). It is necessary
to enter the PASSword (= 3333) as described at point 1.
It is now possible to change the configuration if desired by
following the instructions of point 1.