baltur GI MIST 1000 DSPNM-D Скачать руководство пользователя страница 17

E

N

G

L

I

S

H

16 / 34

0006080766

-  ignite  the  burner,  adjust  the  quantity  of  gas  and  air 

for  the  pilot  flame  and  check  for  proper  ignition 

 several times.

- when adjustment is over restore the original connections.
UV CELL 

Detection of the pilot flame is effected by a UV cell: the 

following information should be born in mind. Even slight 

greasiness will compromise passage of the UV rays through 

the UV photocell bulb, thus preventing the sensitive device 

inside it receiving the quantity of radiation needed for correct 

operation. If the bulb is smeared with light oil, heavy oil, 

etc. it must be cleaned thoroughly. Note that even gentle 

contact with fingers can leave a slight film of grease which 

is sufficient to compromise proper UV photocell operation.

 

The UV cell does not “see” daylight or the light emitted by a 

common bulb. A sensitivity check can be carried out using 

a flame (lighter, candle) or the spark generated between the 

electrodes of a common ignition transformer. To ensure proper 

operation the UV cell current must be sufficiently stable and 

must not drop below the minimum required by the specific con

-

trol box. It may be necessary to try different positions in order 

to find the best one: do this by shifting (axial or rotary shift) the 

body that contains the photocell with respect to the attachment 

strap. The check is effected by connecting a micro-ammeter 

(with suitable scale), in series, to one of the two UV photocell 

connection wires; it is, of course, necessary to observe polarity 

( + and - ). The cell current needed to ensure proper control 

box operation is given on the wiring diagram.

17) When the burner is working at “minimum” adjust the air to

the quantity needed to ensure good combustion. Turn the

adjuster screws in or out at the point of contact with the lever

that transmits combustion air regulation damper movement.

The quantity of air at “minimum” should be a little scarce so

as to ensure perfect ignition even under the most demanding

circumstances.

18) After adjusting the air for the “minimum” turn the modulation

switches to position “MAN” and to position “MAX”.

19) The modulation motor starts moving: wait for the disk (on

which the adjuster screws are fitted) to sweep through an

angle of about 12° (this corresponds to the space taken up by

three screws) and then stop modulation by turning the switch

back to position “0”. Run a visual check on the flame and, if

necessary, regulate combustion air as described in point 17.

Then check combustion using the appropriate instruments

and, if necessary, correct the adjustment previously made

by way of visual check. The above-described operation must

be repeated by proceeding progressively (by advancing the

disk about 12° at a time) and, each time, modifying, where

necessary, the fuel-air ratio throughout the entire modulation

range. It is necessary to make sure that fuel feed progression

occurs gradually and that maximum fuel flow occurs at the

end of the modulation range. This condition is necessary for

attainment of smooth, gradual modulation. If necessary modify

the position of the fuel control screws to obtain that specified

above.  Note  that  maximum  flow  is  attained  when  return

pressure is about 2 - 3 bar less than delivery pressure (gene-

rally 20 - 22 bar). A correct air-fuel ratio should give a carbon

dioxide (CO

2

) value that increases as fuel flow increases: as 

a rough guide, it should be at least 10% at minimum flow and 

reach an optimum of about 13 % at maximum flow.  

 

It is inadvisable to exceed a CO

2

 figure of 13% so as to prevent 

operation with a rather limited excess of air, possibly leading to 

a significant increase in smoke number owing to unavoidable 

causes (changes in atmospheric pressure, small dust depo-

sits in the fan air ducts etc.). The resulting smoke (i.e. fume) 

number is closely linked to the type of fuel used (latest regu-

lations indicate n° 6 on the Bacharach scale as a maximum).  

it is advisable, if possible, to keep the smoke number below 

n° 6 on the Bacharach scale even if the CO

2

 value could, as a 

consequence, be slightly lower. Reduced opacity (i.e. a lower 

smoke number) soils the boiler less and the average efficiency 

of the latter is normally higher even if CO

2

 levels are slightly 

lower. Remember that to achieve proper adjustment system 

water must be up to normal working temperature and that the 

burner must have been working for at least fifteen minutes. In 

the absence of proper instrumentation use fume colour as a 

guide. We recommend that adjustment be effected so as to 

obtain a light orange flame; avoid red flames with smoke and 

white flames with an exaggerated excess of air.

20) The purpose of the air pressure switch is to place the control

box in lock-out (safety mode) if air pressure is incorrect. The

pressure switch must be adjusted so that it trips by closing the

N.O. (Normally Open) contact when air pressure in the burner

reaches a sufficient value. The pressure switch connection

circuit features self-control so it is necessary that the N.C.

(Normally Closed) contact (with fan at standstill and therefore

no air pressure in burner) actually brings about this condition. If

it does not the control box is not switched on (the burner stays

off). More precisely, note that if the contact designed to be clo-

sed when working fails to close (air pressure too low) then the

control box goes through its cycle but the ignition transformer

does not come on, the pilot flame gas valves stay closed and

the burner thus shuts down in “lock-out”. To check that the air

pressure switch is working properly it is necessary, with the

burner at minimum flow rate

 to increase the adjustment value

until it trips: immediate burner “lock-out” must follow. Reset

the burner by pressing the appropriate button and adjust the

pressure switch to a value sufficient to detect the air pressure

during pre-ventilation.

21) The gas pressure switches (minimum and maximum) are desig-

ned to stop the burner working when gas pressure is outside the

set range. Given the specific function of the pressure switches it

is evident that the minimum pressure control switch must utilise

the closed contact when the pressure switch detects a pressure

higher than that to which it is set. It is also evident that the ma-

ximum pressure switch must utilise the closed contact when it

detects a pressure lower than that to which it is set. Adjustment

of minimum and maximum gas pressure switches must there-

fore be effected during burner testing as a function of actual

pressure at each individual installation. The pressure switches

are electrically connected in series; consequently, if any one of

the pressure switches trips (i.e. opening of the circuit) when the

burner is working (flame lit) the burner shuts down immediately.

When testing the burner it is extremely important to check

that pressure switches are working properly. Proper pressure

Содержание GI MIST 1000 DSPNM-D

Страница 1: ...68 02 04 Краснодар 861 203 40 90 Красноярск 391 204 63 61 Курск 4712 77 13 04 Липецк 4742 52 20 81 Магнитогорск 3519 55 03 13 Москва 495 268 04 70 Мурманск 8152 59 64 93 Набережные Челны 8552 20 53 41 Нижний Новгород 831 429 08 12 Новокузнецк 3843 20 46 81 Новосибирск 383 227 86 73 Орел 4862 44 53 42 Оренбург 3532 37 68 04 Пенза 8412 22 31 16 Пермь 342 205 81 47 Ростов на Дону 863 308 18 15 Рязань...

Страница 2: ...n integral and essential part of the product The works on the burner and on the esystem have to be carried out only by competent people Read carefully the instructions before starting the burner and service it The system electric feeding must be disconnected before starting working on it If the works are not carried out correctly it is possible to cause dangerous accidents E N G L I S H ...

Страница 3: ...If the equipment is sold or transferred to another owner or if the owner moves and leaves the equipment make sure that the booklet always goes with the equipment so it can be consulted by the new owner and or installer For all equipment with optionals or kits including electrical only origi nal accessories must be used BURNERS This equipment must be used only for its expressly stated use applied t...

Страница 4: ...out by qualified technicians and in compliance with current law and regulations since incorrect installation may cause damage to person animals or things for which damage the manufacturer shall not can be held responsible Before installation it is advisable to carry out careful internal cleaning of all tubing for the fuel feed system to remove any residues that could jeopardise the proper working ...

Страница 5: ...the modulation kit Ability to operate with any type of combustion chamber Air gas mixing at combustion head and high pressure mechani cal atomisation of fuel using nozzle Ability to obtain optimal combustion values by regulating com bustion air and combustion head Maintenance facilitated by the fact that the mixing unit and the atomisation unit can be removed without having to remove the burner fr...

Страница 6: ...A1 A2 B B1 B2 B3 B4 B5 B6 C D E Ø GI mist 1000 DSPNM D 1465 800 665 1257 855 402 450 575 175 163 2350 440 480 Mod F Ø G G1 L Ø M N Ø P Q R S GI mist 1000 DSPNM D 685 DN80 Rp1 2 630 M16 495 740 1910 1575 795 N 0002670552 OVERALL DIMENSIONS ...

Страница 7: ...DSPGN LIGHT OIL version DSPG HEAVY OIL rated viscosity max 50 E at 50 C version DSPN D GAS Methane HEAVY OIL rated viscosity max 5 E at 50 C version GI Mist DSPNM GAS Methane LIGHT OIL version GI Mist DSPGM Note that the GI Mist 1000 DSPGM and GI Mist 1000 DSPNM burners have been designed for operation with methane gas or with liquid fuel The GI 1000 burner is a modulating burner with a modulation...

Страница 8: ...y to fit insulation protection between the iron plate and the heater that is at least 10 mm thick Check that combustion head pene trates the combustion chamber by the measure requested by the manufacturer of the boiler CONNECTING THE BURNER TO THE GAS SUP PLY PIPE After you have secured the burner to the boiler remember that the burner head must penetrate the combustion chamber to the extent presc...

Страница 9: ...are used Piping must be sized as a function of both its length and the flow rate of the employed pump Our instructions regard only that which is necessary for proper operation HYDRAULIC DIAGRAM OPERATING FOR ONE OR MORE BURNERS WITH MAX NOMINAL VISCOSITY 5 E AT 50 C N 0002901180 1 Main tank 2 Filter 3 Circulation pumps 4 By pass normally closed 5 Pressure regulator adjustable from 0 5 to 2 bar 6 P...

Страница 10: ...AGRAM FOR ONE OR MORE MODULATING BURNERS OPERATING WITH HEAVY OIL 50 E AT 50 C WITH AUXILIARY HEATER N 0002901200 1 Main tank 2 Steam or hot water heating oil to keep a sufficienttemperature for the slide in the pipe line also during the pause 3 Filter 4 Circulation pumps 5 Steam or hot water coil to heat oil 6 Auxiliary heater 7 resistance 8 Thermometer 9 Degasifier Ø 100 mm H 300 mm 10 By pass n...

Страница 11: ...ure gauge 0 40 bar 12 Electrics pre heaters 13 MINIMUM PRE HEAT THERMOSTAT 14 PRE HEAT MAXIMUM THERMOSTAT 15 AIR GAS VENT VALVE NORMALLY CLOSED OPEN SLIGHTLY ONLY IN CASE OF GAS DISCHARGE 16 Self cleanig filter 0 3 mm 17 Pressure gauge 0 40 bar 18 THERMOSTAT PT100 AND THERMOMETER 19 PRE HEATER SAFETY VALVE SET AT 32 BAR 20 REDUCTION UNIT OR PILOT PRESSURE STABILISER 21 GAS MINIMUM AND MAXIMUM PRES...

Страница 12: ...upport so that it can be positioned to avoid the above described interference Just 2 5 seconds after the ignition of the pilot flame the control box powers the magnet which via a series of lever mechanisms moves the two nozzle fuel flow delivery and return interception rods The moving of these rods causes closure of the by pass inside the atomising unit consequently the in pump pressure is brought...

Страница 13: ...PUMP 20 22 BAR 3 PRESSURE GAUGE O 40 BAR 4 ATOMIZER BODY 5 RETURN NOZZLE WITHOUT PIN 6 RODS WITH CLOSING PINS 7 BY PASS HOLES 8 CLOSING SPRINGS 9 OPENING ELECTROMAGNETS 10 RETURN PRESSURE CONTROL MIN 10 12 BAR MAX 18 20 BAR 11 MODULATION SERVOMOTOR 12 AIR FUEL REGULATION CONTROL DISK 13 AIR LOCKS 14 FLEXIBLE TUBE 15 IGNITION PILOT 16 MAIN GAS VALVE FOR IGNITION FLAME WITH FLOW CON TROL PILOT FLAME...

Страница 14: ...RY CIRCUIT 1 Valve body 2 Adjusting screw support plug 3 Adjusting screw stop nut 4 Adjusting screw 5 Spring centering bush N 0002932080 6 Spring 7 Shutter 8 Pressure gauge connection 9 Fuel inlet 10 Fuel outlet 1 2 5 4 3 1 Valve body 2 Adjusting screw tap 3 Pressure gauge 0 40 bar 4 To the pump return 5 From the atomizing group return ...

Страница 15: ... Fuel outlet Fuel return holes Fuel inlet Fuel return N B For the nozzle to operate properly its return section must never be completely closed This is achievedby regulating when the burner is started up for the first time In practice when the nozzle is operating at the maximum flow rate the difference in pressure between the delivery pump pressure and return pressure at hte returnpressure regulat...

Страница 16: ...ssure gauge endof scale approx 3bar to the on pump vacuum meter coupling seat in order to check the pressure at which fuel arrives at the burner pump Apply a pressure gauge end of scale approx 30 bar to the on pump pressure gauge coupling seat in order to check the working pressure of the pump itself Apply a pressure gauge end of scale approx 30 bar to the return pressure regulator coupling to che...

Страница 17: ...es as fuel flow increases as a rough guide it should be at least 10 at minimum flow and reach an optimum of about 13 at maximum flow It is inadvisable to exceed a CO2 figure of 13 so as to prevent operation with a rather limited excess of air possibly leading to a significant increase in smoke number owing to unavoidable causes changes in atmospheric pressure small dust depo sits in the fan air du...

Страница 18: ... the flow regulator valve The main flame of the burner is now ignited at the mi nimum setting The pilot circuit cuts out after the main valves open The modulator servo motor cuts in after the main valves open and on a consent signal from the modulating thermostat or pressurestat assuming they are set a temperature or pressure value in excess of the temperature or pressure in the boiler the servo m...

Страница 19: ...LING AIR GAS SUPPLY 3 VALVE SEAL CONTROL DEVICE AND PRESSURE SWITCH LDU 4 MAIN GAS FLAME VALVE 5 MINIMUM GAS PRESSURE SWITCH AND MAXIMUM PILOT RAMP 6 GAS SUPPLY MODULATING CONTROL BUTTERFLY VALVE 7 GAS PRESSURE CONTROL WITH BUILT IN FILTER 8 VIBRATION PROOF JOINT 9 BALL COCK 10 GAS FILTER 11 DISC WITH ADJUSTMENT SCREWS FOR OPENING AND CLOSING AIR SUPPLY TO HEAD 12 FLAME SAFETY GAS IGNITION PILOT V...

Страница 20: ...e pressure is sufficient and the pressurestat fails to respond neither the ignition transformer nor the pilot flame gas valves will operate so the burner will shut down in lockout Note that lockouts during this first ignition sequence should be considered normal since the fuel supply line will still contain air which must be purged before a stable flame can be obtained Press the reset button to re...

Страница 21: ...e the pressurestat regulation value with the burner operating at minimum output until such a time as the pressurestat cuts in the burner must immediately shut down in lockout Reset the burner by pressing the reset button and return the pressure stat setting to a value that enables it to detect the air pressure created during the pre purge stage 19 The gas pressurestats minimum and maximum pressure...

Страница 22: ...elocity and turbulence ensure that the air penetrates the gas more thoroughly giving an optimum fuel air mixture and a stable flame With gas burners it can be essential to have high air pressure on the diffusor inlet side if pulsation of the fla me is to be prevented especially where the burner operates in a high pressure combustion chamber or in high thermal load conditions Accordingly the head m...

Страница 23: ...ening and closing The VE4000B1 valves are Class A solenoid valves normally closed They may be used as ON OFF valves in the supply trains with Natural Gas Manufactured Gas or GPL on burners or combustion plants They are provided with M I and CE Approval for EN 161 ADJUSTMENT For models VE 4000B1 see fig 1 Adjustment to the flow Remove the cover from the upper section of the coil Insert a hexagonal ...

Страница 24: ...which compresses the closure return spring with the rod and plate The valve remains in the open position while the pump and magnetic valve remain powered When the unit receives the signal to close or if power supply is cut off the pump shuts down the magnetic valve opens decompressing the chamber above the piston The plate is closed both by the return spring and by gas pressure The flow rate for t...

Страница 25: ...e with pressure regulator Using the valve with pressure regulator the valve s out let pressure acts as a comparative value on a membrane assisted by a spring The resistance of the spring can be adju sted an constitutes the prescribed value set pressure value The membrane acts by means of an oscillating system on a by pass ball valve between the upper chamber and the servo control If the comparativ...

Страница 26: ...ndards The following LFL1 features exceed the standards offering a high level of additional safety The flame detector test and false flame test start immediately after the tolerated post combustion time If the valves remain open or do not close completely after adjustment stops a lock out stop is triggered at the end of the tolerated post combustion period The tests will end only at the end of the...

Страница 27: ...ion contact for air damper MIN position M Motor fan or burner NTC NTC resistor QRA UV probe R Thermostat or pressure probe RV Fuel valve with continuous regulation S Fuse SA Air damper servomotor SB Safety limiter temperature pressure etc SM Programmer synchronous motor v In the case of servomotor auxiliary contact for consensus for fuel valve depending on air damper position V Flame signal amplif...

Страница 28: ...12 t5 Time between end of t4 and consensus at power regulator or at valve on terminal 20 18 t6 Post ventilation time with M2 3 t7 Time between consensus for start up and voltage at terminal 7 start delay for fan motor M2 72 t8 Start up duration without t11 and t12 3 t9 Second safety time for burners that use pilot burners 12 t10 Time from start up to beginning of air pressure control without air d...

Страница 29: ...ment Electromagnetic discharges must be checked on the application plan Control program in the event of stopping indicating position of stop As a rule in the event of any kind of stop the fuel flow is cut off immediately At the same time the programmer remains immobi le as does the switch position indicator The symbol visible on the indicator reading disk indicates the type of fault No start up be...

Страница 30: ...ling operation During the second verification stage this pressure must remain constant Should it drop this means that the burner on the furnace side has a blow by fault when closing Therefore the DW pressure switch operates and the tightness control equipment prevents burner start up and stops in blocked state red pilot lamp lit If second stage verification is positive the LDU 11 equipment closes ...

Страница 31: ...XI programmer cam contacts Control programme t4 5s Putting control circuit under atmospheric pressure t6 7 5s Time between start up and energizing of main AR relay t1 22 5s 1st verification stage at atmospheric pressure t3 5s Putting control circuit gas under pressure t2 27 5s 2nd verification stage at gas pressure t5 67 5s Total time of tightness control up to burner operation consent t20 22 5s R...

Страница 32: ...Y1 PID control approximately 130 C In the second preheater the temperature of the fuel is increased to 130 C Configuration for two or more electric preheaters C 1 D 0 E 4 F 6 Indicative parameters SP 130 0 C t d 0 8 minutes S P L 1 100 C SP 2 110 0 C t c 10 seconds S P L h 250 C P b 6 Yh 100 SLOP 0 t i 4 minutes Hy 2 1 To all intents and purposes this configuration is suitable for most users but w...

Страница 33: ...ill appear 7 Proceed as previously described in order to set value t i 4 as per table Press to confirm this value and move to t d 8 Proceed as previously described in order to set value t d 0 8 as per table Press to confirm this value and move to t c 9 Proceed as previously described in order to set value t c 10 as per table Press to confirm this value and move to Yh 10 Proceed as previously descr...

Страница 34: ...E ATOMIZING GROUP AND FLAME DISK N 0002933430 1 Take out the burner cover 2 Disconnect the atomising group and head tie rods 3 Disconnect the heating element connector 4 Disconnect the ignition electrode cable 5 Unscrew the Woss coupling nut to take out the pilot tube ...

Страница 35: ...7 Take out the hinge upper screw and open the burner 8 Take out the blocking screw of the atomising group 9 Take out the atomising group to dismount the nozzle 10 Take out the four fixing screws of the group holder 11 Take out the group holder and flame disks ...

Страница 36: ...75 84 0006080766 ...

Страница 37: ...76 84 0006080766 ...

Страница 38: ...77 84 0006080766 ...

Страница 39: ...78 84 0006080766 ...

Страница 40: ...79 84 0006080766 ...

Страница 41: ...80 84 0006080766 ...

Страница 42: ...81 84 0006080766 ...

Страница 43: ... GIALLO GREEN YELLOW VERT JAUNE VERDE AMA RILLO BU BLU BLUE BLEU AZUL BN BRUNO BROWN MARRON MARRÓN BK NERO BLACK NOIR NEGRO BK CONNETTORE NERO CON SOVRASTAMPA BLACK WIRE WITH INPRINT CONDUCTEUR NOIR AVEC SURIMPRES SION CONDUCTOR NEGRO CON IMPRESIÓN ...

Страница 44: ...RESSOSTATO ARIA AIR PRESSURE SWITCH Pm PRESSOSTATO DI MINIMA GAS MIN PRESSURE SWITCH PmP PRESSOSTATO DI MINIMA RAMPA PILOTA PILOT TRAIN MINIMUM PRESSURE SWITCH PMP PRESSOSTATO DI MASSIMA RAMPA PILOTA PILOT TRAIN MAXIMUM PRESSURE SWITCH Q1 SEZIONATORE GENERALE BLOCCO PORTA MAIN DOOR LOCK SWITCH RP RF RG RESISTENZE POMPA FILTRO GRUPPO GROUP FILTER PUMP RESISTANCES RS1 RS2 RESISTENZE RESISTANCES S1 I...

Страница 45: ...μένων και οποιονδήποτε άλλων πληροφοριών κατά την αποκλειστική του κρίση Baltur S p A По вопросам продаж и поддержки обращайтесь Архангельск 8182 63 90 72 Астана 7 7172 727 132 Белгород 4722 40 23 64 Брянск 4832 59 03 52 Владивосток 423 249 28 31 Волгоград 844 278 03 48 Вологда 8172 26 41 59 Воронеж 473 204 51 73 Екатеринбург 343 384 55 89 Иваново 4932 77 34 06 Ижевск 3412 26 03 58 Казань 843 206 ...

Отзывы: