HYDRAULIC CONNECTIONS (LIGHT OIL)
The connection pipes between tank and burner must be completely tight.
We suggest to use copper or steel pipes of an adequate diameter (see list and diagram).
At the rigid pipes ands it must be fitted the fuel’s detection gates.
Filters, flex pipes and relative connection couplings are supplied along with burner.
Pump is equipped with suitable connecting points (see drawing) for detection instruments (pressure gauge and
vacuummeter).
Pressure drop in suction must not exceed 4 m. W.C. = to 30 cm.Hg. for a proper and silent operation.
Probable max. pressure on suction and on the return 1,5 bar.
HYDRAULIC DIAGRAM
N° BT 8502
DETAILS OF SUNTEC AN 47C 7342 PUMP
2
- Pressure outlet (manometer connection point and
air purge (Ø1/8”)
3
- Pressure adjustment (12 bar)
4.1
- Return with by-pass pin inside retour interieur
goujon by-pass)
5
- Suction
6
- Nozzle outlet
7
- Vacuumeter connection point (Ø 1/8”)
Foot valve
Light oil electrovalve
Nozzle
Pump (12 bar pressure)
Return
Suction
N° 0002901030
Содержание COMIST 18
Страница 8: ...8 Metano Natural gas Gasolio Light oil CAMPO DI LAVORO WORKING FIELD N 0002920161 G P L L P G ...
Страница 25: ...25 GAS BURNERS CONTROLS LGB for small to medium capacity burners with or without a fan intermittent operation ...
Страница 26: ...26 GAS BURNERS CONTROLS LGB for small to medium capacity burners with or without a fan intermittent operation ...
Страница 28: ...28 GENERAL DIAGRAM FOR TWO STAGE L P G PRESSURE REDUCTION FOR BURNER OR BOILER N BT 8721 2GB Rev 21 03 90 ...
Страница 29: ...29 SCHEMA DISPOSIZIONE DISCO ELETTRODI DISK ELECTRODES RELATIVE POSITION DIAGRAM COMIST 18 N BT 9260 ...
Страница 34: ......