28

Defective flame with sparks

Flame badly shaped with smoke and
soot

Defective pulsating escaping flame
or receding from the combustion ori-
fice

Corrosion inside the boiler

Soot at the chimney exit

1) Atomizing pressure too low
2) Too much combustion air
3) Inefficient nozzle, either fouled up

or worn out

4) Water in the fuel

1) Insufficient combustion air flow
2) Inefficient nozzle, either fouled up

or worn out

3) Combustion chamber unsuitably

designed or too small

4) Delivery nozzle inadequate in re-

spect to the combustion chamber
size

5) Refractory lining unsuitable or ex-

cessive

6) Boiler or chimney ducts clogged
7) Low atomizing pressure

1) Excessive draught (only when there

is a suction fan in the chimney)

2) Inefficient nozzle, either fouled up or

worn out

3) Water in the fuel

4) Dirty disk
5) Excessive combustion air flow
6) Air passage between disk and blast

tube

1) Boiler operating temperature too

low (below the dew point)

2) High sulphur content in the fuel
3) Smoke temperature too low (below

180  °C)

1) Excessive cooling (below 180°C) of

smoke before exit outflow, for an out-
side chimney not adequately heat in-

1) Re-set it at the required rating
2) Reduce combustion air flow
3) Clean it or replace it

4) Remove it from the tank using a

suitable pump (never use the
burner pump for this job)

1) Increase combustion air flow
2) Clean or replace it

3) Reduce the nozzle delivery rate to

suit the combustion chamber ca-
pacity or replace the boiler

4) Increase nozzle delivery rate by re-

placing it

5) Modify it or make it lighter accord-

ing to boiler manufacturer’s in-
structions

6) Clean them
7) Rectify and re-set at the required

value

1) Adjust the suction fan speed by

changing the pulley diameter

2) Clean or replace it

3) Remove it from the tank with a suit-

able pump (never use the burner
pump for this job)

4) Clean it
5) Reduce combustion air flow
6) Rectify the position of the blast tube

1) Increase the operating temperature

2) Change grade of fuel
3) Increase the nozzle delivery rate by

replacing it

1) Improve insulation and close any

gap letting cold air in

Содержание BT 180 DSG

Страница 1: ...tarting the burner and service it The system electric feeding must be disconnected before starting working on it If the works are not carried out correctly it is possible to cause dangerous accidents...

Страница 2: ...la BALTUR misma y con los accesorios de linea gas certificados CE suministrables a pedido NOTA la presente declaraci n no tiene validez respecto a la Norma CE o UNI para los quemadores de gas y para...

Страница 3: ...Air regulation on the combustion head Regulating the distance between the disck and the nozzle 12 Using of the burner Maintenance Description of operation of two flame burners 13 Hydraulic diagram 14...

Страница 4: ...ODEL MATERIALE A CORREDO MODELLO BT 180 DSG BT 250 DSG BT 300 DSG BT 350 DSG INSULATING GASKET N 1 N 1 N 2 N 2 GUARNIZIONE ISOLANTE STUD BOLTS N 4 M16 N 4 M16 N 4 M18 N 4 M18 PRIGIONIERI HEXAGONAL NUT...

Страница 5: ...NSIONS A A1 A2 B B1 B2 C D E F H I L M N BT 180 DSG 820 400 420 760 580 180 930 265 260 225 940 395 280 M16 275 BT 250 DSG 840 420 420 760 580 180 930 265 260 225 940 395 280 M16 275 BT 300 DSG 840 42...

Страница 6: ...sso ries The unit is equipped with a cylindrical combustion head it is advisable to fasten the boiler s iron plate first and then the burner When the boiler door is not fitted with heat insulation it...

Страница 7: ...ction pipe 7 Return pipe 10 Bottom valve N B For any missing devices in the piping follow existing regulations H Total meters meters meters i 16 mm i 18 mm 0 5 21 34 1 18 29 1 5 15 24 2 11 5 19 2 5 8...

Страница 8: ...SUPPLY FROM THE TANK TOP 1 Tank 3 Wire net filter 4 Pump 6 Suction pipe 7 Return pipe 8 Automatic fuel interception device at burner shut off 9 One way valve 10 Bottom valve P 3 5 m max SUCTION TYPE F...

Страница 9: ...ich intercepts the flow of oil through the 1st flame pressure regulator The 1st flame pressure regulator is excluded in this way and the pressure increase until it reaches the value at which the press...

Страница 10: ...aining either lubrification oil or fuel oil do not use low viscosity products such as light oil crude oil petrol kerosene etc 5 Now press on the mobile part of the motor s relay in order to start up t...

Страница 11: ...h 4 The control box will start functioning and will connect the burner component devices according to its pre established programme The unit starts up in this way as described in the Chapter Descripti...

Страница 12: ...uel an optimum mixture and good flame stability It might be necessary to have high air pressure upstream the disk in order to avoid flame pulsation s and it is considered practically indispensable whe...

Страница 13: ...ks at full rating it will remain in this position until it reaches the pressure or temperature limit pre set on the control device pressure switch or thermostat The control device trips disconnecting...

Страница 14: ...di metro 150 altura 400 tienen que instalarse lo m s cerca posible del quemador a una cota superior de aproximadamente 0 5 m con respecto a la bomba del mismo Tubi flessibili Flexible pipes Tubos fle...

Страница 15: ...15 GENERAL DIAGRAM AIR REGULATION N 8608 3...

Страница 16: ...16 INDICATIVE DIAGRAM SHIWING THE NOZZLE POSITION ELECTRODES FLAME DISK AND REGULATION OF THE D HEAD DISK DISTANCE IN HINGED LIGHT OIL TWO STAGES DSG BURNERS N 0002930070...

Страница 17: ...Regolazione aria per la 1 fiamma Air damper control handweel 1st flame air regula tion 3 Dado di bloccaggio Lock nut 4 Vite regolazione aria per la 2 fiamma Air control screw for 2nd flame 5 Tappo di...

Страница 18: ...18 POMPA BALTUR MODELLO BT BALTUR PUMP MODEL BT BOMBA BALTUR MODELO BT N 0002900580...

Страница 19: ...28 84 29 73 30 59 31 43 32 25 33 04 6 00 6 50 20 67 22 10 23 44 23 70 25 91 27 06 28 17 29 23 30 26 31 25 32 21 33 14 34 05 34 94 35 80 6 50 7 00 22 26 23 79 25 24 26 60 27 90 29 14 30 33 31 48 32 58...

Страница 20: ...o que Ud desee y la rueda se desplazar respecto a la escala de referencia El ndice de la rueda roja indica el ngulo de rotaci n establecido para cada leva en la correspondiente escala de referencia 1...

Страница 21: ...E air regulation 2nd stage cam ST2 Disconnect temporarily the cable connected to buckle N 3 the same which was previously disconnected from buckle N 9 and connect it temporarily to the buckle N 7 Oper...

Страница 22: ...meleLKS300 tif 0 Close air shutter cam with burner in stop position ST1 Air regulation cam 1 flame ST2 Air regulation cam 2nd flame MV2 2nd Flame valve connection cam must be adjusted in a position be...

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ...2 Air infiltration in the pipes 3 Dirty filter 4 Excessive distance between the tank and the burner or a lot of acci dental leakage s elbows curves choking etc 5 Deteriorated flexible pipes 1 Thermost...

Страница 28: ...t 2 High sulphur content in the fuel 3 Smoke temperature too low below 180 C 1 Excessive cooling below 180 C of smoke before exit outflow for an out side chimney not adequately heat in 1 Re set it at...

Страница 29: ...eserves the right to change specification without notice BALTUR S p A Via Ferrarese 10 44042 CENTO Ferrara ITALIA Tel 051 684 37 11 Fax 051 685 75 27 28 International Tel 39 051 684 37 11 Fax 39 051 6...

Отзывы: