ENGLISH
FAN-CONTROL ADJUSTMENT
position of potentiometers
IONISATION CURRENT
The minimum current needed to run the equipment is 1.5 µA. The
burner provides a significantly higher current and therefore does not
normally require any checks at all. Should however, the ionisation
current need to be measured, a microammeter must be connected
in series to the ionisation electrode lead.