CAUTION
Sump heaters can be hot.
BELT TENSIONING
Belt tensioning can be adjusted by changing the position of the fan motor(s) by rotating the motor base adjustment
screw, which extends through the bottom frame angle.
Check belt tension as follows:
1. Shut off fan(s).
2. Rotate the fan sheave half a turn to evenly distribute the tension in the belt before measuring.
3. Check belt tension by verifying both following conditions.
-
The deflection amounts 10 mm / m free belt length (see figure below).
-
The deflection force required is between the minimum and maximum values given in the table below.
CAUTION
Fan has to be blocked while replacing belts.
Fan belt check and adjustment
1.
Fan sheave
2.
Belt
3.
Motor sheave
4.
10 mm/m deflection = proper belt tension
5.
Straight edge
CAUTION
Over-tensioning of belts can lead to component damage.
W W W . B A L T I M O R E A I R C O I L . E U
23
5 Maintenance Procedure
5 Maintenance Procedure
Содержание VFL 241-H
Страница 1: ...VFL Closed Circuit Cooling Towers OPERATING AND MAINTENANCE INSTRUCTIONS MVFLv19EN...
Страница 34: ...W W W B A L T I M O R E A I R C O I L E U 34...
Страница 35: ...W W W B A L T I M O R E A I R C O I L E U...
Страница 36: ...W W W B A L T I M O R E A I R C O I L E U...
Страница 37: ...W W W B A L T I M O R E A I R C O I L E U...