The desired method to match the cooling capacity to load and weather conditions is to adjust the air flow by the

use of modulating controls (variable speed drives).
Alternatively, multi speed fan motors or fan cycling can be applied, but fans operating on a common heat exchange

section should always be operated simultaneously.
It is not recommended to cycle the spray pump as a means of controlling the unit capacity.
Whenever two speed motors are used for capacity control, a time delay of at least 15 seconds is required when

switching form high to low speed. Sudden switch over might damage the drive system or the motor.

When operating with VFD drives above nominal frequency be aware of the potential risk for motor overload

or mechanical damages.

It is recommended to provide sinus filters on the VFD to prevent bearing damage on fan motors.

CAUTION

Refer to fan motor nameplate data when programming a VFD.

Spray pumps should be switched off when the fan(s) are idle. Operation with pump but without fan(s) does not

provide cooling capacity of any significance but could lead to occasional water splash out at the air intake. For this

reason this operation mode should be avoided. Spray pump should be switched off with a time delay of

maximum

30 seconds after switching off the fan(s) and should be activated

maximum

30 seconds prior to the anticipated

start of the fan(s).
The purpose of a low level cut out switch for pump protection is to protect the pump from running dry in case of

make-up failure or extreme water loss. The status of the alarm can be checked prior to pump start-up, but should

not be considered during the first minute after start-up, since activation of the pump can cause a water level drop,

that might trigger the alarm. Normal make-up will stabilize the water level after a short period of time.
In case the low level alarm signals, that there is no longer enough water in the cold water sump to guarantee a

proper operation, the pump should be stopped (after a time delay of 60 seconds) and only manually restarted after it

has been verified that the water in the sump is at or near the overflow level.

In case the low level pump alarm is used to stop the pump, appropriate control logic should be incorporated

to prevent hunting of the pump motor. Once the spray pump is stopped, the water in suspension will drain

back to the tank and raise the water-level above the alarm level, which will reset the alarm immediately. A manual

reset of the alarm after solving the root cause of the low level alarm is recommended. Frequent start/stop or

hunting will damage the motor.

Protection against coil freezing

The best protection is the use of glycol or other anti freeze solutions in appropriate concentrations. The use of such

solutions influences the thermal performance of the closed circuit cooling tower and this should be taken into

account, when selecting the model(s). The table below indicates the freeze protection range for various ethylene

glycol concentrations (% by volume).

W W W . B A L T I M O R E A I R C O I L . E U

17

4 Cold Weather Operations

4 Cold Weather Operations

Содержание VFL 241-H

Страница 1: ...VFL Closed Circuit Cooling Towers OPERATING AND MAINTENANCE INSTRUCTIONS MVFLv19EN...

Страница 2: ...nized Codes of Practice such as EUROVENT 9 5 6 ACOP HSC L8 Guide des bonnes pratiques Legionella et tours a ror frig rantes etc Water sampling test results and corrective actions should be recorded in...

Страница 3: ...epends on applied code of practice Notes 1 Water treatment and auxiliary equipment integrated in the cooling system may require additions to the table above Contact suppliers for recommended actions a...

Страница 4: ...14 Passivation 14 Overflow connection 15 4 Cold Weather Operations 16 About cold weather operation 16 Protection against sump water freezing 16 Capacity control 16 Protection against coil freezing 17...

Страница 5: ...W B A L T I M O R E A I R C O I L E U 5 CONSTRUCTION DETAILS 1 Casing 2 Water distribution section 3 High efficiency drift eliminators 4 Forward curved centrifugal fan 5 Fan shaft and bearing 6 Fan mo...

Страница 6: ...for an ambient temperature range from 25 C to 40 C Design pressure max 10 bar Fluid inlet temperature max 82 C Fluid outlet temperature min 10 C Fluids circulated through the inside of the coils must...

Страница 7: ...stem volume per year If the annual make up of the closed system is greater than 15 yearly or if highly corrosive water such as water with very low hardness or alkalinity is used it is recommended to c...

Страница 8: ...ith extra care to prevent accidents CAUTION Do not cover units with PVC eliminators with a plastic tarpaulin Temperature increase due to sun radiation could deform the eliminators AUTHORIZED PERSONNEL...

Страница 9: ...ent of refrigerants if applicable oil and other parts must be done with respect to the environment whilst protecting workers from potential risks related to exposure to harmful substances National and...

Страница 10: ...event of any such defect BAC will repair or provide a replacement For more details please refer to the Limitation of Warranties applicable to and in effect at the time of the sale purchase of these p...

Страница 11: ...thereafter Moreover there must be an ongoing programme of monitoring in place to ensure the water treatment system is maintaining the water quality within the control guidelines Check and adjustments...

Страница 12: ...owed provided the sum of chlorides sulfates parameters does not exceed 650 mg l for Baltibond SST304L Baltiplus protection pH 6 5 to 9 0 pH during initial passivation Below 8 2 Total hardness as CaCO3...

Страница 13: ...ation of sulphates is allowed provided the sum of chlorides sulphates parameters does not exceed 650 mg l for SST304L and 1500 mg l for SST316L For Ozone water treatment application Stainless steel 31...

Страница 14: ...which may cause corrosion Preferably the water treatment chemicals should be fed into the cooling system at the discharge of the recirculation pump The chemicals should not be fed in concentrated for...

Страница 15: ...secondary approach is to conduct a chemical passivation using inorganic phosphate or film forming passivation agents Consult your water treatment specialist for specific recommendation Overflow connec...

Страница 16: ...from wet to dry operation as the sump water is protected at all times For dry operation applications ensure that make up water line is shut off and make up valve completely drained Thermostats for el...

Страница 17: ...ct the pump from running dry in case of make up failure or extreme water loss The status of the alarm can be checked prior to pump start up but should not be considered during the first minute after s...

Страница 18: ...If the process load is extremely light or shut off it may be necessary to apply an auxiliary heat load during freezing conditions Consult your local BAC Balticare representative for advice if these c...

Страница 19: ...M VFL 484 M 23 0 27 2 30 5 30 5 33 8 13 8 14 5 15 2 15 2 15 9 VFL 721 L VFL 721 M VFL 721 O VFL 722 N VFL 722 O VFL 723 L VFL 723 O VFL 724 O 7 9 40 1 40 1 40 1 46 4 46 4 51 5 51 5 56 6 17 8 17 8 17 8...

Страница 20: ...r the basin has been flushed the strainers should be removed cleaned and replaced before refilling the basin with fresh water CAUTION Do not use acid to clean the strainers Remote Basin The water leve...

Страница 21: ...height from sump bottom to water level and compare with face value from table 4 Check valve for leakage and replace valve if necessary 5 Check that float arm can move freely and that float ball floats...

Страница 22: ...ine ensure that the valve is unobstructed and that blow down water can drain freely Measure the blow down flow rate by recording the time needed to fill a given volume For automatic blow down using co...

Страница 23: ...ing 3 Check belt tension by verifying both following conditions The deflection amounts 10 mm m free belt length see figure below The deflection force required is between the minimum and maximum values...

Страница 24: ...nsioned re tighten the locking nuts on the motor base adjusting screws There should be no chirp or squeal when the fan motor is started DRIVE ALIGNMENT Proper drive alignment ensures maximum belt life...

Страница 25: ...nd pumps must rotate in the correct direction which is indicated by arrows on the equipment Check proper functioning as follows 1 Stop fan s and pump s 2 Turn the fan by hand to ensure rotation withou...

Страница 26: ...of mechanical components or operational problems e g unwanted ice formation If this occurs a thorough inspection of the entire unit followed by immediate corrective action is needed If required consul...

Страница 27: ...ly in parallel to it Selecting a coil cleaner is important since the cleaner must neutralise and remove deposits on the surface of the coil BAC does not recommend the use of alkaline and acidic coil c...

Страница 28: ...art fan s and pump s Nozzle spray distribution type FAN SHAFT The exposed areas of the fan shaft are coated with a soft seal for added corrosion protection It is recommended that the coating be inspec...

Страница 29: ...correctly Lubrication FAN SHAFT BEARINGS The fan shaft is supported by ball bearings see figure below Under normal operating conditions the bearings should be greased every 2000 operating hours or at...

Страница 30: ...C Total Fina Elf Multis 3 20 C to 120 C Grease products ADJUSTABLE MOTOR BASE The motor base adjusting screw see figure below should be coated every six months using a good quality corrosion inhibiti...

Страница 31: ...ocal or national guidance also recommends disinfection prior to initial start up after a prolonged shut down after routine cleaning operations or when significant alterations have been made to the coo...

Страница 32: ...parts are used Prolonged outdoor stay Should the unit s be stored outside prior to installation and or start up for approximately one month shelf life or longer or stored in severe climates it is imp...

Страница 33: ...ecomaf 2002 30p Guide des Bonnes Pratiques Legionella et Tours A ror frig rantes Minist res de l Emploi et de la Solidarit Minist re de l Economie des Finances et de l Industrie Minist re de l Environ...

Страница 34: ...W W W B A L T I M O R E A I R C O I L E U 34...

Страница 35: ...W W W B A L T I M O R E A I R C O I L E U...

Страница 36: ...W W W B A L T I M O R E A I R C O I L E U...

Страница 37: ...W W W B A L T I M O R E A I R C O I L E U...

Страница 38: ...AGE EVAPORATIVE CONDENSERS HYBRID PRODUCTS PARTS EQUIPMENTS SERVICES www BaltimoreAircoil eu info BaltimoreAircoil eu Please refer to our website for local contact details Industriepark Zone A B 2220...

Отзывы: