FXV3/CXVT Rigging & Assembly Instructions
–
Unit Rigging & Assembly
Page | 10
3. Unit Rigging & Assembly
Rigging
NOTICE:
For weight information, refer to the submittal drawing package.
NOTICE:
All single-cell and multi-cell units must be rigged one section at a time.
: Failure to use appropriate lifting equipment can result in a dropped load, causing severe injury,
death, and/or property damage. Lifts must be performed by qualified riggers following BAC published Rigging
Instructions, and generally accepted lifting practices. The use of a supplemental safety sling may also be required if the
lift circumstances warrant its use, as determined by the rigging contractor.
Refer to
section’s
required minimum spreader bar length W1
and the recommended minimum
vertical dimension “H”.
Model Number
Lower Section
Plenum Section
Coil Section
H
W1
H
W1
H
W1
FXV3-1224-xxx
20’
12’
20'
12’
16’
12’
FXV3-1426-xxx
20'
14’
22'
14’
16’
14’
CXVT-x-1224-x, XECXVT-1224-x,
CXVT-x-2424-x, XECXVT-2424-x
20’
12’
20'
12’
16’
12’
CXVT-x-1426-x, XECXVT-1426-x,
CXVT-x-2826-x, XECXVT-2826-x
20'
14’
22'
14’
16’
14’
Table 1. Minimum Vertical Dimension and Spreader Bar Length for FXV3 and CXVT Units
FXV3 Model
Number
Nominal
Box Size
Coil Module
Height
FXV3-1224-20x-xx
12’
x 24’
Short
FXV3-1224-24x-xx
12’ x 24’
Short
FXV3-1224-28x-xx
12’ x 24’
Tall
FXV3-1224-30x-xx
12’ x 24’
Tall
FXV3-1224-32x-xx
12’ x 24’
Tall
FXV3-1224-36x-xx
12’ x 24’
Tall
FXV3-1426-20x-xx
14’
x 26’
Short
FXV3-1426-24x-xx
14’ x 26’
Short
FXV3-1426-28x-xx
14’ x 26’
Tall
FXV3-1426-30x-xx
14’ x 26’
Tall
FXV3-1426-32x-xx
14’ x 26’
Tall
FXV3-1426-36x-xx
14’ x 26’
Tall
Table 2. FXV3 Nominal Box Size & Coil Module Height by Model Number