Water quality guidelines for adiabatic
pre-cooler frame
Baltiplus 800™ coating
Temperature
< 20 ºC
PH
6.5 – 9
Hardness as (CaCO
3
)
50 – 500 mg/l
Alkaline as (CaCO
3
)
< 500 mg/l
Total dissolved solids
< 1500 mg/l
Chlorides
< 200 mg/l
Sulfates
< 250 mg/l
Conductivity
1800 µS/cm
Bacteria Rate (CFU/ml, KBE/ml)
< 1000
Minimum supply water quality
For Ozone water treatment application, stainless steel 316L execution is required.
Model
Number of fans
Minimum pre-cooler water flow
per unit
DFCV-EC9122-*
4 fans
14 l/min
DFCV-EC9123-*
6 fans
22 l/min
DFCV-EC9124-*
8 fans
28 l/min
DFCV-EC9125-*
10 fans
36 l/min
DFCV-EC9126-*
12 fans
44 l/min
DFCV-EC9127-*
14 fans
50 l/min
Recommended adiabatic pre-cooler water flow rates
If any of the following happens:
•
at ambient conditions exceeding the given maximum ambient conditions,
•
with supply water quality data exceeding one or more of the concentration limits of above table "Minimum
supply water quality",
•
if the supply water has a Practical Scaling Index below 5.5,
Then:
•
the water flow needs to be increased to higher levels to avoid rapid fouling and scaling of the pre-cooler
medium. Contact your local BAC-Balticare representative for support.