MAINTENANCE PROCEDURE
Checks and adjustments
ADIABATIC PRE-COOLER WATER FLOW
A minimum water flow must be distributed over the adiabatic pre-cooler as per minimum water flow rates. (See
table below "Minimum recommended adiabatic pre-cooler water flow rates").
The water flow will depend on the supply water pressure, and can be set by adjusting the adjustment screw on the
water flow valve on the flow meter (See figure below). Read off the water flow at the underside of the float.
Water flow adjustment screw
DFCV-AD-EC