12
english
Output
gradient
Linear
transducer
Unit
Min.
value
Null
value
Indication for
adjustment
Indication
for teach-in
End
value
Max.
value
Error
value
Rising
BTL7-A…
V
−0.5
0
2.0
4.0
10.0
10.5
10.5
BTL7-E…
mA
3.6
4.0
6.0
12.0
20.0
20.4
3.6
Falling
BTL7-A…
V
10.5
10.0
2.0
4.0
0
−0.5
−0.5
BTL7-E…
mA
20.4
20.0
6.0
12.0
4.0
3.6
3.6
Tab. 6-1: Value table for teach-in
6.1
Programming inputs
Programming inputs La and Lb must be used in order to
make settings. A programming input at 20 to 28 V
corresponds to activation (high active).
The Balluff BTL7-A-CB02-… adjusting box can be used for
this (see Accessories on page 21).
Automatic deactivation!
If no signals are transmitted via the
programming inputs for approx. 10 min,
programming mode is automatically ended.
6.2
Calibration procedure notes
Prerequisites
– Programming inputs are connected.
– The transducer is connected to the system controller.
– Voltage or current values from the transducer can be
read (using a multimeter, the system control or the
adjusting box).
Fig. 6-1:
YE
GY
RD
PK
GN
BU
BN
WH
YE
GY
PK
RD
GN
BU
BN
WH
Linear transducer
Calibration box
Supply
8-port
luster terminal
Adapter cable with
connector (luster terminal)
6-pin
8-pin
Connecting the BTL7-A-CB02-K calibration box to the
BTL7-…-SA262 cable version
6
Calibration procedure
Values for null and end point
– Any desired position of the magnet can be used as the
null or end point. However, the null and end points may
not be reversed.
– The absolute null and end points must lie within the
minimum or maximum limits of what can be output
(see value table).
The last set values are always saved, regardless
of whether the setting was ended using the
programming inputs or automatically after
10 min have expired.
Value table for teach-in
The following examples refer to transducers
with 0 to 10 V or 4 to 20 mA output.
The PK conductor of the transducer must
be connected to the RD conductor of the
calibration box!
BTL7-A/E1 _ 0-M _ _ _ _ -K(8)-SA262-K _ _ /F _ _
Micropulse Transducer - Rod Style
Содержание MICROPULSE BTL7-A/E1 0-M Series
Страница 1: ...Betriebsanleitung deutsch BTL7 A E1_0 M_ _ _ _ K 8 SA262 K_ _ F_ _...
Страница 2: ...www balluff com...
Страница 25: ...User s Guide english BTL7 A E1_0 M_ _ _ _ K 8 SA262 K_ _ F_ _...
Страница 26: ...www balluff com...
Страница 49: ...Manual de instrucciones espa ol BTL7 A E1_0 M_ _ _ _ K 8 SA262 K_ _ F_ _...
Страница 50: ...www balluff com...
Страница 73: ...Notice d utilisation fran ais BTL7 A E1_0 M_ _ _ _ K 8 SA262 K_ _ F_ _...
Страница 74: ...www balluff com...
Страница 97: ...Manuale d uso italiano BTL7 A E1_0 M_ _ _ _ K 8 SA262 K_ _ F_ _...
Страница 98: ...www balluff com...