12
english
Ignition protection
“nA” and “tb”
Fig. 4-7:
Magnet
(e.g. BTL-P-1028-15R)
Supporting rod made of non-magnetizable material
Example 2, transducer installed with supporting rod
4.4
Electrical connection
Depending on the model, the electrical connection is made
using a cable (BTL7-…-K) or a connector (BTL7-…-SR32).
The connection or pin assignments for the respective
version can be found in Table 4-2.
Note the information on shielding and cable
routing.
4
Installation and connection (continued)
4.4.1 Connector SR32/cable connection K_ _
Pin
Cable color
-A_10
-G_10
-C_00
-C_70
-E_00
-E_70
Fig. 4-8: Pin assignment of SR32
(view of connector pins of
transducer), 8-pin M16
circular plug
1
YE yellow
Not used
1)
0…20 mA
20…0 mA
4…20 mA
20…4 mA
2
GY gray
0 V
3
PK pink
10…0 V
10…−10 V
10…0 V
3)
4
RD red
La (programming input)
5
GN green
0…10 V
−10…10 V
0…10 V
3)
6
BU blue
GND
2)
7
BN brown
10…30 V
8
WH white
Lb (programming input)
1) Unassigned leads can be connected to the GND on the controller side but not to the shield.
2) Reference potential for supply voltage and EMC-GND.
3) The voltage outputs may exhibit a minimal offset to the harmonized current output.
Tab. 4-2: Connection assignment BTL7-…-SR32/K_ _
4.5
Shielding and cable routing
Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
– Connect transducer and controller using a shielded
cable.
Shielding: Braided copper shield with minimum 85%.
– Connector version: Shield is internally connected to
connector housing.
– Cable version: On the transducer side, the cable
shielding is connected to the housing.
Ground the cable shielding on the controller side
(connect with the protective earth conductor).
Magnetic fields
The linear encoder is a magnetostrictive system. It is
important to maintain adequate distance between the
transducer/holding cylinder and strong, external magnetic
fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-A/G
Max. 30 m
1)
BTL7-C/E
Max. 100 m
1)
1) Prerequisite: Construction, shielding and routing preclude the effect of
any external noise fields.
Tab. 4-3: Cable lengths BTL7
BTL7-A/C/E/G5 _ _ -M _ _ _ _ -K(8)-NEX-SR32/K_ _ _