Micropulse AT Transducer in round profile housing
5
english
Pin
BTL6-A301...
BTL6-G301...
Cable BKS
Output signal:
5
A1: 0...10 V
➀
A1: -10...+10 V
➀
GN green
3
A2: 0...10 V
➀
A2: -10...+10 V
➀
PK pink
2
0 V
(output)
GY gray
Supply voltage (external):
6
GND
BU blue
7
+24 V
BN brown
Programming inputs:
1
La
➁
YE yellow
4
Lb
➁
RD red
Reserved leads must remain unconnected.
8
reserved
WH white
4
Wiring
Note the following when making electrical connections:
System and control cabinet must be at the same ground potential.
To ensure electromagnetic compatibility (EMC), which Balluff verifies by the CE Marking, the following points must be
strictly observed.
• BTL transducer and the controller must be connected using shielded cable.
• Shielding: Copper filament braided, 85 % coverage.
• The cable shield must be grounded on the control side, i.e., connected to the protection ground.
Wiring assignments can be found in
➥
➥
➥
➥
➥
Table 4-1.
➀
If there is no magnet within the measuring range, a voltage of approx. 10.5 V
is output as an error indication.
If necessary the outputs can be reconfigured for a falling output (10...0V or
+10...-10V) .
➁
After programming, the programming inputs should be tied to Pin 2
(0V
(output)
).
Table 4-1: Wiring assignment