BTL5-A/C/E/G1_-M/U_ _ _ _-T-_S 32
Micropulse Linear Transducer - Rod Style
7
english
6
Calibration procedure (cont.)
Fig. 6-4: Manual adjust procedure
6.4
Reset
The reset function can be used to
restore the transducer to its factory
default settings.
➥
➥
➥
➥
➥
Section 9 Resetting all values
(Reset)
6.5
Online-setting
Setting the start and end values is
done while the system is running.
➥
➥
➥
➥
➥
Section 10 Online setting mode
6.3
Manual adjust
This method allows you to set a
new start and/or end value. This
may be useful if the magnet can
6.1
Selecting calibration mode
System not running:
Depending on the application use
either Teach-in or manual adjust.
System running:
In special situations the online set-
ting mode may be used.
Note:
The calibration procedure must
be performed identically and us-
ing the same values for each
measuring unit
6.2
Teach-in
The factory-set null- and endpoints
will be replaced by the new null-
and endpoints. First move the mag-
net to the new null position, then to
the new end position, and press the
buttons to accept the correspond-
ing value.
➥
➥
➥
➥
➥
Section 7 Teach-in mode
1 2
1
2
Fig. 6-1: Calibration device
(shown on transducer)
= Button 2
gray
End
value
Accept new
end value
Accept new
null value
rising
Null
value
falling
before
after
2nd step: Move magnet to new end
position
1st step: Move magnet to new
null position
New stroke 100 %
before
after
Fig. 6-3: Teach-in procedure
New end
value
New start
value
Null point
Move magnet to new desired
start position.
Move magnet to new
end position
End
point
before
after
before
after
1
/ 2
1
1
2
1
1
1
+ 2
1
+ 2
1
+ 2
2 +
1
2
2
2
Teach-in
Adjust
Null
point
End
point
Fig. 6-2: Selecting calibration mode
Buttons
disabled
Buttons
enabled
Null
point
End
point
Online-
setting
Null point
End point
Buttons
disabled
Buttons
enabled
Online-
setting
not be brought to the null or end
point of the transducer.
To do this, the magnet is brought
alternately to the new start and end
position, and the displayed values
are adjusted by keystroke or press-
ing the buttons until the desired
values are reached.
➥
➥
➥
➥
➥
Section 8 Manual adjust mode
= Button 1
blue
Reset