![Balluff BNI IOL-302-000-Z026 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/balluff/bni-iol-302-000-z026/bni-iol-302-000-z026_user-manual_3627605007.webp)
Balluff Network Interface / IO-Link BNI IOL-302-xxx-Z026
www.balluff.com
6
3
Getting started
3.3.3 Sensor-Actuator
Standard I/O port (M12, A coded, female)
interface
Pin
Function
1
+24V, 300mA
2
Input 2 / Output 2
3
GND
4
Input 1 / Output 1
5
FE
Note!
For the digital sensor inputs follow the input guideline per EN61131-2, type 2.
Note!
Outputs: Maximum 2A per output.
Total current of actuator supply is maximum 9A
Note!