![Balluff BNI IOL-104-002-Z046 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/balluff/bni-iol-104-002-z046/bni-iol-104-002-z046_user-manual_3696651022.webp)
Balluff Network Interface / IO-Link BNI IOL-104-002-Z046
www.balluff.com
22
10 Function indicators
Digital LED
indicators for
inputs/outputs
LED 2, Input Pin 4
Status
Function
off
Input signal = 0
Yellow
Input signal = 1
Red
Sensor supply short-circuit
Extension port
The table is valid if the extension port is active. If the extension port is used as a standard I,
then the description from "Digital LED indicators for inputs" can be used.
Status
Function
Green
IO-Link – connection active
Green, flashing
No IO-Link connection or faulty IO-Link device
Red, flashing
Incorrect IO-Link device or incorrect configuration (0x55)
Red
IO-Link short-circuit on Pin 4
All manuals and user guides at all-guides.com