3-4  Receiving & Installation

MN2417

Electrical Connections

  Class 1 wiring methods must be used for field wiring connections to terminals of a class 2

circuit.   It is the responsibility of the owner/operator to arrange for these procedures to be

performed by a licensed electrical contractor and ensure conformance to all applicable codes

including local codes peculiar to your municipality/city/county and state.  Wire size and insulation

type should be as required by NEC (National Electrical Code) and local codes.

Warning: Never connect this generator to the electrical system of any building unless a licensed

electrician has installed an approved transfer switch.  The national electrical code (NEC)

requires that connection of a generator to any electrical circuit normally powered by means of

an electric utility must be connected by means of approved transfer switch equipment to

isolate the electrical circuit from the utility distribution system when the generator is

operating.  Failure to isolate the electrical circuits by such means may result in injury or death

to utility power workers due to backfeed of electrical energy onto the utility lines.

Warning: Incorrect installation of this generator set could result in property damage, injury or death.

Connection of the generator to its fuel source must be done by a qualified professional

technician or contractor.

WARNING: Be sure the system is properly grounded before applying power.  Do not apply AC power before

you ensure that grounds are connected.  Electrical shock can cause serious or fatal injury.   NEC

requires that the frame and exposed conductive surfaces (metal parts) be connected to an

approved earth ground.  Local codes may also require proper grounding of generator systems.

Intended Use

The intended purpose of this generator set is to provide electrical power when the main utility power

supply is interrupted. Therefore, it is important that all the wiring that connects the generator set with

your house, transfer switch, distribution box, battery charger, etc. be properly installed.

Protection

  

Single Phase

 circuit protection is provided within the generator.  The power output connections

are rated and sized according to the KW of the generator. Proper lead wire from these points to

the automatic transfer switch (or load switching device) is mandatory. See transfer switch

information for corresponding generator input terminals. 

Three phase

 circuit protection is provided by the generator.  When connecting the generator

output to an electrical load, a UL listed circuit breaker with the appropriate ratings shall be

provided within 25 feet of the Genset. Use only copper wires.

Table 3-3  Standby Power Ratings

Generator

Electrical Load Capacity Standby Power Ratings

Generator

Catalog

1 Phase

3 Phase

Catalog

No.

kVA kW

Volts

Amps *

kVA

kW

Volts

Amps

TS25

18

18

240/120

75/2x75

25/25/25

20/20/20

208/240/480

69/60/30

TS35

25

25

240/120

104/2x104

37/37/37

30/30/30

208/240/480

104/90/45

TS45

27

27

240/120

112/x2112

46/46/48

37/37/38

208/240/480

128/111/57

TS60

43

43

240/120

179/2x179

60/60/61

48/48/49

208/240/480

166/144/73

TS80

45

45

240/120

187/2x187

72/72/81

58/58/65

208/240/480

201/174/97

TS130

70

70

240/120

291/2x291

131/131/134

105/105/107

208/240/480

364/315/160

TS175

100 100

240/120

416/2x416

169/169/175

135/135/140

208/240/480

468/405/210

TS250

175 175

240/120

729/2x729

250/250/250

200/200/200

208/240/480

693/601/300

TS400

250 250

240/120

1041/2x1041

400/400/400

320/320/320

208/240/480

1110/962/481

*  Example 2x75 means 2 lines (Line to Neutral) of 120V @ 75 amps each.

Table 3-4  Prime Power Ratings

Generator

Electrical Load Capacity Prime Power Ratings

Generator

Catalog

1 Phase

3 Phase

Catalog

No.

kVA kW

Volts

Amps *

kVA

kW

Volts

Amps

TS25

18

18

240/120

75/2x75

23/23/23

18/18/18

208/240/480

62/54/27

TS35

22

22

240/120

91/2x91

33/33/33

27/27/27

208/240/480

93/81/40

TS45

25

25

240/120

104/2x104

44/44/44

35/35/35

208/240/480

121/105/52

TS60

40

40

240/120

166/2x166

56/56/56

45/45/45

208/240/480

156/135/67

TS80

43

43

240/120

179/2x179

69/69/75

55/55/60

208/240/480

190/165/90

TS130

66

66

240/120

275/2x275

119/119/121

95/95/97

208/240/480

329/285/145

TS175

95

95

240/120

395/2x395

156/156/159

125/125/127

208/240/480

433/375/190

TS250

160 160

240/120

666/2x666

227/227/227

180/180/180

208/240/480

624/541/270

TS400

240 240

240/120

1000/2x1000

365/365/365

292/292/292

208/240/480

1013/878/439

*  Example 2x75 means 2 lines (Line to Neutral) of 75 amps each.

Содержание TS25

Страница 1: ...Tier 2 3 Towable Generators Trailer and Skid Mounted Diesel Liquid Cooled TS25 35 45 60 80 130 175 250 and 400 Installation Operating Manual 8 06 MN2417...

Страница 2: ...hemicals known to the state of California to cause cancer birth defects and other reproductive harm WARNING CALIFORNIA PROPOSITION 65 WARNING Battery posts terminals and related accessories are known...

Страница 3: ...ctions 3 4 Battery Connections 3 7 Recommended Engine Oil and Battery Type 3 9 Post Installation Checks 3 9 Section 4 Operation 4 1 Towing the Generator 4 1 Selecting the Proper Towing Equipment 4 1 S...

Страница 4: ...ii Table of Contents MN2417...

Страница 5: ...e that operates this equipment at all times Keep non qualified personnel at a safe distance from this equipment Only qualified personnel familiar with the safe installation operation and maintenance o...

Страница 6: ...efore use after 25 miles of operation and every 100 miles of operation thereafter Failure to check the lug nuts for proper tightness can result in an accident due to a wheel falling from the trailer W...

Страница 7: ...in water on wet ground or with wet hands feet or shoes or while barefoot WARNING High voltage is present whenever the engine is running Electrical shock can cause serious or fatal injury Always stop...

Страница 8: ...proper grounding of generator systems WARNING Place protective covers over all rotating parts such as drive shaft pulley belt etc Rotating parts cause extremely dangerous situations because they can...

Страница 9: ...wires with damaged insulation immediately Electrical shock can cause serious or fatal injury WARNING Disconnect all electrical wires and load devices from generator power outlets before servicing the...

Страница 10: ...voltage and output frequency Caution Never operate the engine without a muffler The engine is designed to have the correct exhaust components installed and operating without these components can pres...

Страница 11: ...stallation shipment or otherwise Problems with Baldor products can be due to improper maintenance faulty installation non Baldor additions or modifications or other problems not due to defects in Bald...

Страница 12: ...2 2 General Information MN2417...

Страница 13: ...pacity and tires for the terrain to avoid becoming stuck or tipping over If the shipping pallet is intact use a fork lift to move the generator If the shipping pallet has been removed use the Lift Poi...

Страница 14: ...to be opened or removed for service and maintenance 7 Maximum Ambient temperature is 122 F 50 C Figure 3 2 Generator Mounting Skid B1 B A A2 A1 TS130 175 only 4 Holes A2 A1 TS25 45 80 only 3 Holes A1...

Страница 15: ...hat an exhaust rain cap be used whenever it is possible that rain could get into the system This will help to prevent corrosion and damage to the exhaust system and engine Installation The generator i...

Страница 16: ...erator The power output connections are rated and sized according to the KW of the generator Proper lead wire from these points to the automatic transfer switch or load switching device is mandatory S...

Страница 17: ...connections are weather tight Figure 3 3 Receptacle Panel Single Phase Single phase power is always available GOLD X GOLD Y G SILVER W CS6369 125 250V 50A X Y W Test Reset CS6365N GFI Outlet 120V 20A...

Страница 18: ...h may also be used to start the generator Shore Power Use extension cord with appropriately sized conductors to connect the optional Shore Power receptacle to 120VAC 240VAC for TS400 single phase util...

Страница 19: ...nel away from batteries WARNING Do not dispose of battery or batteries in a fire The battery is capable of exploding If the battery explodes electrolyte solution will be released in all directions Bat...

Страница 20: ...battery cables from the battery the negative first then the positive 3 Remove the Battery Hold Down Bar and Rods 4 Remove the old battery and place the correct new battery see Table 3 5 on the tray 5...

Страница 21: ...e generator to the factory for repair and consequent expense and loss of time Note These precautions are especially necessary in locations such as seaboard installations and other high humidity areas...

Страница 22: ...iately and repair the leak before proceeding b Verify there are no coolant or oil leaks If a leak is detected stop the engine set the Master Control in the Stop position immediately and repair the lea...

Страница 23: ...ransport passengers in any trailer S Reduce weight in car trunk and rear seat areas by the amount of tongue weight of your trailer S Any alterations or changes made to the trailer void any express or...

Страница 24: ...nd weather conditions Avoid sudden stops if possible 3 Passing Accelerating and passing should be done slowly to allow extra distance for passing Signal well in advance when passing and returning to t...

Страница 25: ...to drag on ground or roadway 8 Test breakaway system Hydraulic surge brake system normally have a cable or chain connected to the tow vehicle In a break away condition this cable or chain activates t...

Страница 26: ...inflation 13 Check wheel lug nuts for correct tightness see Lug Nut Tightness Wheel nuts bolts should be torqued before the first road use and after each wheel removal Check and re torque after the f...

Страница 27: ...cords or external devices WARNING High voltage is present whenever engine is running Electrical shock can cause serious or fatal injury Never operate electrical equipment while standing in water on w...

Страница 28: ...ctions see Figure 4 4 1 240 120VAC voltage is present at the receptacle panel at all times when generator is running 2 Carefully inspect all Individual load cables for broken insulation or other signs...

Страница 29: ...zer sounds an alarm when operator attention is needed Voltage Select Switch switch Selects 208 120 240 120 or 480 277VAC OFF 1 2 Auto Start Connection for external two wire starting from transfer swit...

Страница 30: ...connected and connections are secure 9 Ensure that an external ground connection is made when required for safety 10 Ensure that the Remote Start wires are properly connected if used 11 Use disconnect...

Страница 31: ...Warning X High Coolant temperature X Low Oil pressure X Low Fuel level X Generator Over Voltage X Generator Over Frequency X Generator Over Current X Generator Overspeed X Coolant temperature High Lo...

Страница 32: ...in Figure 4 7 displays the operating mode and operating parameters such as kW engine RPM etc Figure 4 7 Measurement Menu OFF MAN AUT Ready PF RPM Timer 0 00 0 0 0 kW Control Mode Operating Modes and H...

Страница 33: ...ng RPM 0 or any other shutdown condition READY TO LOAD off FUEL SOLENOID off Shutdown Generator CB Closed Loaded Generator CB Opened Running Loaded RPM 0 or any other shutdown condition FUEL SOLENOID...

Страница 34: ...ut are closed Active or not reset protection disables start Table 4 5 Possible Warnings Events specification Protection type Binary output available Table 4 7 Wrn Oil press WRN YES Sd Oil press SD YES...

Страница 35: ...y energizes the starter motor The relay opens if The firing speed is reached or Maximum time of cranking is exceeded or Request to stop occurs Fuel solenoid relay output Closed output opens the fuel s...

Страница 36: ...is not active and FAULT RESET is pressed Note Treshhold level for D input is 80 supply voltage Vgen failed Output is closed if the generator over under voltage shutdown alarm or voltage asymmetry shu...

Страница 37: ...loses if the generator over under voltage warning alarm activates fgen warning Output closes if the generator over under frequency warning alarm activates Overload wrn Output closes if the generator o...

Страница 38: ...te identification at remote phone or mobile connection Gen set name is max 14 characters long and have to be entered using LiteEdit software Nomin power 3ph Nominal power of the generator in three pha...

Страница 39: ...Step 1s Range 1 60 s CrnkFail pause Pause between crank attempts Step 1s Range 5 60 s Crank attemps Max number of crank attempts Step 1 Range 1 10 Idle time Idle time delay starts when RPM exceeds Sta...

Страница 40: ...etpoint value Eng prot del During the start of the gen set some engine protections have to be blocked e g Oil pressure The protections are unblocked after the Protection del time The time starts after...

Страница 41: ...overvoltage All three phases are checked Maximum out of three is used Step 1 of Nominal voltage Range Gen V Wrn Gen V Gen V Wrn Warning level for generator under voltage All three phases are checked M...

Страница 42: ...3 lev1 The level for IOM ANALOG INPUT 3 alarm detection Step 1 Range 100 to 10000 AnlInIOM3 lev2 The level for IOM ANALOG INPUT 3 alarm detection Step 1 Range 100 to 10000 AnlInIOM3 del Delay for IOM...

Страница 43: ...NOID L1 L2 L3 N Generator C B ANALOG INPUTS BINARY OUTPUTS RPM RPM IN COM BO6 BO3 BO4 BO5 BO1 START BO2 FUEL AI1 OIL AI2 TEMP AI3 FUEL RPM GND POWER 8 36 V DC EXTENSION MODULES GENERATOR CURRENT GENER...

Страница 44: ...er at o r C B PRESTART PE RS 232C Int erface Modem or PC C O NT RO L SI GNALS ALARM RE ADY TO L OA D D CHRG ALT ER NATOR BINARY INP UTS RPM RPM IN COM BO3 BO4 BO5 BO6 BO1 START BO2 FUEL AI1 OIL AI2 T...

Страница 45: ...air filters per the engine manufacturers guidelines 2 Check oil level regularly at least every 5 to 8 operating hours Maintain the proper oil level 3 Change the oil as is recommended in the engine ma...

Страница 46: ...e voltage meter with an accurate voltmeter to verify Check continuity across Breaker Fuse Replace if defective Check wiring including grounds crimps and connection points Repair defects The generator...

Страница 47: ...gher than rear of tow vehicle when additional supports have been removed View and make adjustments while vehicle and trailer are on level surface Seek expert advise Reduce tow vehicle speed and use ca...

Страница 48: ...5 4 Troubleshooting and Maintenance MN2417...

Страница 49: ...tified in the engine manual that was provided with your generator set IMPORTANT Fuses are installed in the control box to protect the engine controller and associated control circuits When replacing f...

Страница 50: ...A 2 Wiring Diagrams MN2417 Figure A 1 TS25 Connection Diagram...

Страница 51: ...Wiring Diagrams A 3 MN2417 Figure A 2 TS25 Connection Diagram...

Страница 52: ...A 4 Wiring Diagrams MN2417 Figure A 3 TS25 Connection Diagram...

Страница 53: ...Wiring Diagrams A 5 MN2417 Figure A 4 TS25 Connection Diagram...

Страница 54: ...A 6 Wiring Diagrams MN2417 Figure A 5 TS25 Connection Diagram...

Страница 55: ...Wiring Diagrams A 7 MN2417 Figure A 6 TS25 Connection Diagram...

Страница 56: ...A 8 Wiring Diagrams MN2417 Figure A 7 TS35 Connection Diagram...

Страница 57: ...Wiring Diagrams A 9 MN2417 Figure A 8 TS35 Connection Diagram...

Страница 58: ...A 10 Wiring Diagrams MN2417 Figure A 9 TS35 Connection Diagram...

Страница 59: ...Wiring Diagrams A 11 MN2417 Figure A 10 TS35 Connection Diagram...

Страница 60: ...A 12 Wiring Diagrams MN2417 Figure A 11 TS35 Connection Diagram...

Страница 61: ...Wiring Diagrams A 13 MN2417 Figure A 12 TS35 Connection Diagram...

Страница 62: ...A 14 Wiring Diagrams MN2417 Figure A 13 TS35 Power Connection Diagram...

Страница 63: ...Wiring Diagrams A 15 MN2417 Figure A 14 TS60 Connection Diagram...

Страница 64: ...A 16 Wiring Diagrams MN2417 Figure A 15 TS60 Connection Diagram...

Страница 65: ...Wiring Diagrams A 17 MN2417 Figure A 16 TS60 Connection Diagram...

Страница 66: ...A 18 Wiring Diagrams MN2417 Figure A 17 TS60 Connection Diagram...

Страница 67: ...Wiring Diagrams A 19 MN2417 Figure A 18 TS60 Connection Diagram...

Страница 68: ...A 20 Wiring Diagrams MN2417 Figure A 19 TS60 Connection Diagram...

Страница 69: ...Wiring Diagrams A 21 MN2417 Figure A 20 TS60 Connection Diagram...

Страница 70: ...A 22 Wiring Diagrams MN2417 Figure A 21 TS80 Connection Diagram...

Страница 71: ...Wiring Diagrams A 23 MN2417 Figure A 22 TS80 Connection Diagram...

Страница 72: ...A 24 Wiring Diagrams MN2417 Figure A 23 TS80 Connection Diagram...

Страница 73: ...Wiring Diagrams A 25 MN2417 Figure A 24 TS80 Connection Diagram...

Страница 74: ...A 26 Wiring Diagrams MN2417 Figure A 25 TS80 Connection Diagram...

Страница 75: ...Wiring Diagrams A 27 MN2417 Figure A 26 TS80 Connection Diagram...

Страница 76: ...A 28 Wiring Diagrams MN2417 Figure A 27 TS80 Connection Diagram...

Страница 77: ...Wiring Diagrams A 29 MN2417 Figure A 28 TS80 Connection Diagram...

Страница 78: ...A 30 Wiring Diagrams MN2417 Figure A 29 TS80 Connection Diagram...

Страница 79: ...Wiring Diagrams A 31 MN2417 Figure A 30 TS80 Connection Diagram...

Страница 80: ...A 32 Wiring Diagrams MN2417 Figure A 31 TS400 Connection Diagram...

Страница 81: ...Wiring Diagrams A 33 MN2417 Figure A 32 TS400 Connection Diagram...

Страница 82: ...A 34 Wiring Diagrams MN2417 Figure A 33 TS400 Connection Diagram...

Страница 83: ...Wiring Diagrams A 35 MN2417 Figure A 34 TS400 Connection Diagram...

Страница 84: ...A 36 Wiring Diagrams MN2417 Figure A 35 TS400 Connection Diagram...

Страница 85: ...Wiring Diagrams A 37 MN2417 Figure A 36 TS400 Connection Diagram...

Страница 86: ...A 38 Wiring Diagrams MN2417 Figure A 37 TS400 Connection Diagram...

Страница 87: ...Wiring Diagrams A 39 MN2417 Figure A 38 TS400 Connection Diagram...

Страница 88: ...A 40 Wiring Diagrams MN2417 Figure A 39 TS400 Connection Diagram...

Страница 89: ...Baldor District Offices...

Страница 90: ...e of California to cause cancer birth defects and other reproductive harm WARNING CALIFORNIA PROPOSITION 65 WARNING Battery posts terminals and related accessories are known to the state of California...

Отзывы: