BP1600 230V Conversions
T
HE
F
OLLOWING
P
AGES
A
RE
BP1600 230V S
ETUPS
There are 6 setups, and each setup is capable of running at 230V 16A or 32A.
Two major changes in each setup is with the Dip Switch settings and moving
wiring from J12 to J13, or vice versa, depending on the system that is set up.
Recheck all wiring for each setup before power up.
L2
L1
N
F3 10A 250V
F2 3A 250V
F6 0.1A 250V
J44
J48
J1
J2
J24
J45
J49
J15
J16
J47
J13
J27
J25
J26
J23
J33
J28
J30
J31
J32
J29
J12
J46
J20
J57
J8
J14
J22
J21
J56
F5 30A
GND
K3
K5
K6
K2
K1
K4
OZ
ONE
22117_B
RED AC
GND
GND
WHT AC
HTR A
HTR B
UNFUSED
J45
J46
J24
F4 1A 250V
J18
J19
K7
T1
J15
J33
J31 HCE
J30 TST
J27
H3
J22
J26 H2
J25 H1
J17
J16
J29 VAC
J28 AUX FRZ
J5
LIGHT
ON
22121_C
CONTROL PANEL
TO J33
AUX
TO J5
1
6
S1
ALL UNUSED SWITCHES
SHOULD BE OFF
STORE SETTINGS*
SPECIAL AMPERAGE RULE OFF
DON’T ADD 4 HS PUMPS W/HTR
DON’T ADD 2 HS PUMPS W/HTR
DON’T ADD 1 HS PUMP W/HTR
TEST MODE OFF
MEMORY RESET*
SPECIAL AMPERAGE RULE ON
ADD 4 HS PUMPS WITH HEAT
ADD 2 HS PUMPS WITH HEAT
ADD 1 HS PUMP WITH HEAT
TEST MODE ON
6
5
4
3
2
1
ON POSITION
S1 SWITCH #
OFF POSITION
*SWITCH #
6
SHOULD BE SET TO OFF
UPON FINAL INSTALLATION.
SENSOR A
SENSOR B
NO
T USED
2S PUMP 1
BL
OWER
WHITE
BLACK
RED
GRN
4.0 kW
ALL UNUSED SWITCHES SHOULD BE OFF
STORE SETTINGS*
SPECIAL AMPERAGE RULE OFF
DON’T ADD 4 HS PUMPS W/HTR
DON’T ADD 2 HS PUMPS W/HTR
DON’T ADD 1 HS PUMP W/HTR
TEST MODE OFF
MEMORY RESET*
SPECIAL AMPERAGE RULE ON
ADD 4 HS PUMPS WITH HEAT
ADD 2 HS PUMPS WITH HEAT
ADD 1 HS PUMP WITH HEAT
TEST MODE ON
6
5
4
3
2
1
ON POSITION
S1 SWITCH #
OFF POSITION
*SWITCH #
6
SHOULD BE SET TO OFF
UPON FINAL INSTALLATION.
A common setup change involves a High Speed
Pump with Heat (Dip Switch number 2).
A manufactured setup (16A) has the Special
Amperage Rule to ON.