8.1

 

Hazardous Location 

Refer to the device label for the description of the environment in which the device may be installed. 

 

8.2

 

Field Wiring 

Intrinsically Safe wiring must be made with grounded cable or installed in grounded metal conduit. 
(CHAQUE CABLE A SECURITE INTRINSEQUE DOIT INCLURE UN BLINDAGE MIS A LA TERRE OU DOIT 
FONCTIONNER DANS UN CONDUIT EN METAL SEPARE) The installation including the barrier earthing 
requirements must comply with the installation requirements of the country of use.  

Requirements:  

(USA): ANSI/ISA RP12.6 Installation of Intrinsically Safe Systems for Hazardous (Classified) Locations and the 
National Electrical Code, ANSI/NFPA 70.   

CSA (Canada): Canadian Electrical Code Part 1.  

ATEX (EU): Intrinsically safe installations must be installed per EN60079-10 and EN60079-14 as they apply to the 
specific category. 

8.2.1

 

4 to 20mA Input Terminals 

These terminals power the SVI3 and are equipped on the Main Module.  This is a standard 
component within every SVI3 product.   

 

Entity/NIFW Parameters:  

Ui 

Ii 

Pi 

Ci 

Li 

30 Vdc 

125 mA 

900 mW 

6.5 nF 

µ

 

8.2.2

 

Options Module: 

All functions listed in this section are included with the Options Module peripheral. 

WARNING: 

Using the Options Module in an I.S. installation will result in reduced T ratings from the base model.  

Please refer to Section 7.1 for ratings. 

 

8.2.2.1

 

SW Output Terminals 

There are two independent isolated switch contact outputs labeled SW#1 and SW#2. The 
switches are polarity sensitive, conventional current flows into the plus terminal.    

 

Entity/NIFW Parameters:

 

Ui 

Ii 

Pi 

Ci 

Li 

30 Vdc 

125 mA 

385 mW 

5.1 nF 

2.4 

µ

 

8.2.2.2

 

Position Retransmit (0-20mA Output) Terminals 

The position retransmit returns the measured position represented by a current value between 
0-20mA.  A certified active or passive barrier may be used for this connection. 

 

Entity/NIFW Parameters: 

Ui 

Ii 

Pi 

Ci 

Li 

30 Vdc 

125 mA 

650 mW 

9 nF 

µ

 

 

Содержание Masoneilan SVI3

Страница 1: ...ES 817 Rev D SPECIAL INSTRUCTIONS FOR INSTALLING MASONEILAN SVI3 IN AREAS WHERE THERE IS A POTENTIAL FOR EXPLOSIVE GAS AND DUST ATMOSPHERES...

Страница 2: ...6 INTRINSICALLY SAFE REQUIREMENTS 6 6 1 I S BARRIERS 6 6 2 INSTALLED MODULE BASED TEMPERATURE RATINGS ADJUSTMENTS 6 7 AGENCY MARKINGS 7 7 1 AGENCY APPROVALS 7 7 2 US AND CANADIAN STANDARDS 9 7 3 ENCL...

Страница 3: ...m The SVI3 positioner is designed by Dresser LLC 12970 Normandy Blvd Jacksonville FL 32221 USA The SVI3 Positioner is manufactured in India 2 Model Codes Covered by this Document Model Code SVI3 ABCDE...

Страница 4: ...on and other safety measures may be required to maintain a safe environment Verify that the markings on the label are consistent with the application Verify that the air supply pressure cannot exceed...

Страница 5: ...ations as shown Shown with cover removed 4 2 Entries and Cable Glands Certified cable glands are required based on the hazardous area the device is installed in The NPT conduit plug supplied with the...

Страница 6: ...al 1 13 N m Options Terminal Connections o Min 0 5 N m o Max 0 6 N m Conductor Size Range 4 20 mA Input Terminals 22 AWG to 12 AWG Options Terminal Connections 26 AWG to 14 AWG 6 Intrinsically Safe Re...

Страница 7: ...Zone 21 Ex ia tb IIIC T20091 C Db Intrinsically Safe Explosive Gas Base Positioner Temperature Classification IEC Ex ia IIC T6 T4 Ga T4 Ta 55 C to 85 C ATEX II 1G Ex ia IIC T6 T4 Ga T5 Ta 55 C to 75 C...

Страница 8: ...EC Class II Division 1 Groups E F G T6 T4 Class III Zone 20 Ex ia IIIC T20091 C Da Increased Safety Non Incendive Marking for Explosive Gas Dust Temperature Classification IEC Ex ec ic IIC T6 T4 Gc T4...

Страница 9: ...1 60079 11 1203 60079 31 60079 7 and 121201 Certified to CSA STDs C22 2 94 1 94 2 61010 1 12 60079 0 60079 1 60079 11 30 60079 31 25 60079 7 and 213 7 3 Enclosure Ratings NEMA 4X IP66 Type 4X 7 4 Ope...

Страница 10: ...8 2 SVI3 Options Module 1 2 3 R E M Remote Mount 4 20 mA OUT SW 1 2 PV 1 5 VDC OPTIONAL HAND HELD COMMUNICATOR 1 2 4 3 1 2 4 3 1 2 4 3 Optional Field Load SEE NOTE 8 3 2 Certified Active or Passive IS...

Страница 11: ...nd EN60079 14 as they apply to the specific category 8 2 1 4 to 20mA Input Terminals These terminals power the SVI3 and are equipped on the Main Module This is a standard component within every SVI3 p...

Страница 12: ...tions card add on Entity NIFW Parameters Uo Io Co Lo Po 5 4 Vdc 5 8 mA 64 F 500 H 8 mW 8 3 Entity Requirement Cable capacitance and inductance plus the I S apparatus unprotected capacitance Ci and ind...

Страница 13: ...s For more information contact Masoneilan Dresser LLC 12970 Normandy Blvd Jacksonville FL 32221 USA Dresser LLC For assistance contact the nearest sales office your local representative or email svisu...

Страница 14: ...Modify Model Code Identifier G and H added statement on replacement of NPT s 12 10 20 C 2 4 1 D M ECO 0043804 Removed note on use of Teflon tape changed Model Code Identifier H such that any single ch...

Отзывы: