INTRODUCTION
NOMENCLATURE
1 - 4
I-E96-419A
®
NOMENCLATURE
is a list of related hardware.
SPECIFICATIONS
Refer to Table
for the specifications of the NTTA01 termina-
tion unit.
Table 1-3. Nomenclature
Nomenclature
Description
IMAMM03
Analog master module.
IMASM02
Analog slave module (T/C, millivolt).
NKAI01
Cold junction compensation1 cable, PVC.
NKAI11
Cold junction compensation1 cable, non-PVC.
NKTU01
Termination unit cable, PVC.
NKTU11
Termination unit cable, non-PVC.
NOTE:
1. In a TTA termination unit configuration, the NKAI01 and NKAI11 Cold Junction Compensation
Cables are used for termination unit interconnection, not cold junction compensation.
Table 1-4. Specifications
Property
Characteristic/Value
Surge Protection
Meets IEEE-472-1974 surge withstand capability test.
Wire Size:
Minimum
Maximum
22 gauge
12 gauge
Power Consumption
5 mA
Mounting
Occupies one slot in a standard field termination panel.
Environmental:
Electromagnetic/Radio
Frequency Interference
Ambient Temperature
Relative Humidity
Atmospheric Pressure
Air Quality
No values available at this time. Keep cabinet doors closed. Do not use
communication equipment closer than 2 meters from the cabinet.
0° to 70°C (32° to 158°F)
0% to 95% up to 55°C (131°F) noncondensing
0% to 45% up to 70°C (158°F) noncondensing
Sea level to 3 km (1.86 mi.)
Bailey equipment should be operated and stored in a noncorrosive environment.
Cooling Requirements
No cooling is necessary when used in Bailey cabinets and operated within
stated environmental limits.
Certification
CSA certified for use as process control equipment in an ordinary
(nonhazardous) location.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE