background image

INTRODUCTION

GLOSSARY OF TERMS AND ABBREVIATIONS

I-E96-407A   

1 - 3

GLOSSARY OF TERMS AND ABBREVIATIONS

Table 

1-2

 lists definitions of the terms and abbreviations used

in this instruction.

NOMENCLATURE

Table 

1-3

 is a list of related hardware.

SPECIFICATIONS

Refer to Table 

1-4

 for the specifications of the NTAO01 termi-

nation unit.

Table 1-2.  Glossary of Terms and Abbreviations

Term

Definition

Analog

Continuously variable as opposed to discretely variable.

Configuration

The act of setting up equipment to accomplish specific functions or a list of parame-
ters associated with such a setup.

Dipshunt

Dual in-line package with shorting straps.

Dipswitch

A dual in-line package that contains switches.

FTP

Field termination panel. A panel inside the INFI 90 cabinet on which to mount termina-
tion units.

INFI-NET

Advanced data communication highway.

Module Bus

Peer to peer communication link used to transfer information between intelligent mod-
ules within a process control unit.

Plant Loop

Network 90

®

 data communication highway.

Termination
Unit

Provides input/output connection between plant equipment and the INFI 90/ Network 
90 modules.

Table 1-3.  Nomenclature

Nomenclature

Hardware

IMAOM01

Analog Output Module

NKTU01

Termination Unit Cable (PVC)

NKTU11

Termination Module Cable (non-PVC)

Table 1-4.  Specifications

Property

Characteristic/Value

Surge Protection

Meets IEEE-472-1974 surge withstand capability test.

Wire Size 

Minimum

Maximum

22 gauge

12 gauge

Mounting

Occupies one slot in a standard field termination panel.

® Network 90 is a registered trademark of Elsag Bailey Process Automation.

Содержание Infi 90 NTAO01

Страница 1: ...Process Control and Automation Solutions from Elsag Bailey Group E96 407 Analog Output Termination Unit NTAO01...

Страница 2: ...UIPEMENTS LECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FR QUENCE RADIO DES PR CAUTIONS DEVRONT TRE PRISES LORS DE L UTILISATION DU MAT RIEL DE COMMUNICATION PORTATIF LA PRUDENCE EXIGE QUE LES PR...

Страница 3: ...modules The NTAO01 Analog Output Termination Unit provides an interface between the IMAOM01 Analog Output Module and eight analog outputs This product instruction explains how to install and use the...

Страница 4: ...hrough 4 3 Original 5 1 Original A 1 through A 2 Original Index 1 Original When an update is received insert the latest changed pages and dispose of the super seded pages NOTE On an updated page the c...

Страница 5: ...servicing Special Handling This module uses electrostatic sensitive devices SPECIFIC CAUTIONS It is strongly recommended that all power cabinet I O etc be turned off before doing any termination unit...

Страница 6: ...e module contient des composantes sensibles aux decharges electro statiques ATTENTIONS D ORDRE SP CIFIQUE II est fortement recommand que toutes les alimentations armoire E S etc soient coup es avant d...

Страница 7: ...INSTALLATION 2 2 Fuse Installation 2 2 Dipshunt Configuration 2 2 Installing the Termination Unit 2 4 Cabling Connections 2 5 Cable Installation 2 6 Power Wiring 2 6 Terminal Wiring 2 7 SECTION 3 MAI...

Страница 8: ...le Connections 2 5 2 6 NTAO01 Terminal Assignments and Application Examples 2 7 A 1 Analog Output Module Layout A 1 List of Tables No Title Page 1 1 Reference Documents 1 2 1 2 Glossary of Terms and A...

Страница 9: ...vice A field device may be system powered from the termina tion unit Figure 1 1 shows an example TAO application INTENDED USER System engineers and technicians should read this manual before installin...

Страница 10: ...ibes precautions to observe when handling modules and setup procedures required before unit operation This section discusses dipshunt settings and installation procedures Maintenance Provides a mainte...

Страница 11: ...s FTP Field termination panel A panel inside the INFI 90 cabinet on which to mount termina tion units INFI NET Advanced data communication highway Module Bus Peer to peer communication link used to tr...

Страница 12: ...to 45 up to 70 C 158 F noncondensing Atmospheric Pressure Sea level to 3 km 1 86 mi Air Quality Bailey Controls equipment should be operated and stored in a noncorrosive environment Cooling Requiremen...

Страница 13: ...dy to install them in the system Save the bag for future use 2 Ground Bag Before Opening Before opening a bag con taining an assembly with CMOS devices touch it to the equip ment housing or a ground t...

Страница 14: ...wer for the AOM module Fuse F2 is a 3 0 amp 250 volt fuse Bailey Controls part number 1948776A13001 used for 24 VDC I O power for external devices Dipshunt Configuration The dipshunts select the analo...

Страница 15: ...TB2 NTAO01 TB3 TB1 TERMINAL BLOCKS TB1 TB4 TERMINAL 1 TERMINAL 8 DIPSHUNTS XU1 XU4 CHASSIS GROUND 24 VDC COMMON DIPSHUNTS XU5 XU8 FUSES F1 F2 SOCKET P1 I1 I1 I1 I1 V1 V1 V1 V1 I1 I1 I1 I1 V1 V1 V1 V1...

Страница 16: ...board to the field termi nation panel with two number ten self tapping screws Figure 2 2 NTAO01 Termination Unit Typical Current Output Circuit Figure 2 3 NTAO01 Termination Unit Typical Voltage Outp...

Страница 17: ...ion unit supports the analog output module AOM Figure 2 5 shows the cable connection between the TAO termination unit and the AOM module The cable is either the NKTU01 or NKTU11 Termination Unit Cable...

Страница 18: ...d latch securely in place Power Wiring There is one terminal E1 that connects to 24 VDC and one terminal E2 that connects to system common Figure 2 1 shows their locations on the TAO circuit board To...

Страница 19: ...d 5 All field wiring is complete 6 Power is connected and applied to the termination unit Figure 2 6 NTAO01 Terminal Assignments and Application Examples 1 1 1 1 2 2 2 2 7 7 7 7 6 6 6 6 5 5 5 5 4 4 4...

Страница 20: ...aintenance schedule MAINTENANCE SCHEDULE Execute the tasks in Table 3 1 at the specified intervals Table 3 1 Maintenance Schedule Task Interval Clean and tighten all power and field wiring connections...

Страница 21: ...ROCEDURES If a TAO termination unit is faulty replace it with a new one Do not try to repair the unit replacing components may affect the performance and certification of the unit Table 4 1 Recommende...

Страница 22: ...TB1 through TB4 2 Label and disconnect the cable connected to the termina tion unit at P1 3 Label and disconnect system 24 VDC I O power and sys tem common from the E1 and E2 terminals 4 Remove the 2...

Страница 23: ...TERMINATION UNIT REPLACEMENT PROCEDURES I E96 407A 4 3 9 Connect the cable to the P1 connector 10 Verify all connections to the TAO termination unit 11 Energize the cabinet power supply that provides...

Страница 24: ...and quantity 2 Model and serial numbers if applicable 3 Bailey Controls instruction manual number page number and reference figure that identifies the part Order parts without commercial descriptions...

Страница 25: ...milliamps or zero to ten VDC for all eight outputs When jumper E3 is configured for zero to ten VDC all outputs must be configured for voltage outputs Table A 2 shows how to set the E3 jumper on the m...

Страница 26: ...0 1 1 1 15 0 1 1 1 1 31 1 1 1 1 1 NOTE 0 CLOSED or ON 1 OPEN or OFF Table A 2 Settings for Jumper E3 Signal Jumper 4 to 20 mA 1 to 5 VDC 0 to 10 VDC Table A 3 Settings for Jumpers E6 through E13 Jumpe...

Страница 27: ...module A 1 NTAO01 termination unit 2 3 M Maintenance schedule 3 1 Mounting diagram 2 5 N Nomenclature 1 3 O Output circuit Current 2 4 Voltage 2 4 Overview 1 1 R Reference documents 1 2 Replacement Fu...

Страница 28: ...8756 ASIA PACIFIC 152 Beach Road Gateway East 20 04 Singapore 189721 Telephone 65 391 0800 Telefax 65 292 9011 EUROPE AFRICA MIDDLE EAST Via Puccini 2 16154 Genoa Italy Telephone 39 10 6582 943 Telefa...

Отзывы: