INSTALLATION
SETUP/PHYSICAL INSTALLATION
2 - 4
I-E96-406A
®
Figure 2-2. Cable Connections for NTAM01 Unit
Table 2-1. NTAM01 Cable Applications
Cable
Application
Connector
Maximum
Length
NKTU01 (PVC)
Connects NTAM01 unit to primary
IMAMM03 module
P2 on NTAM01 unit to MMU
backplane
61 m
(200 ft)
NKTU11 (non-PVC)
NKTU01 (PVC)
Connects NTAM01 unit to redun-
dant IMAMM03 module
P3 on NTAM01 unit to MMU
backplane
61 m
(200 ft)
NKTU11 (non-PVC)
NKAI01 (PVC)
Connects NTAM01 unit to NTAI02
unit
P1 on NTAM01 unit to P4 on
NTAI02 unit
1.5 m
(5 ft)
NKAI11 (non-PVC)
NKDS01 (PVC)
Connects NTAM01 unit to a single
NDIS01 station
P4 on NTAM01 unit to P1
1
on
NDIS01 station
120 m
(400 ft)
NKDS11 (non-PVC)
IMAMM03
(PRIMARY)
IMAMM03
(REDUNDANT)
IMASM02
IMASM02
P1
P1
P1
P1
P3
P3
P3
P3
P2
P2
P2
P2
NKTU01/11
NKTU01/11
NTAI02
RTD
PAIR A
TO P4 ON NEXT
INTERCONNECTED NTAI02.
TO RTD PAIR B THROUGH
RTD PAIR D IF REQUIRED.
NTAM01
P1
P1
P1
J3
J1
J3
P3
P2
P1
P4
P3
P2
P5
P4
NKTU01/11
NKTU01/11
NKAI01/11
NKAI01/11
NKDS02/12 OR NKDS01/11
FOR A SINGLE NIDS01
NDIS01
NIDS01
T00465A
NOTES:
1. MAXIMUM OF 4 NTAI02 UNITS WITH RTD PAIR A TO RTD PAIR D.
2. NTAM01 IS NOT REQUIRED IF NDIS01 IS NOT USED AND ONLY
PRIMARY IMAMM03 IS USED.